Page 1 of Application Note: Interfacing DS/DD Bar Code Decoder to PLC-5

Manual · Allen-Bradley

Application Note: Interfacing DS/DD Bar Code Decoder to PLC-5

Manual12 pagesPDF 75 KB

Application note on connecting Allen-Bradley 2755-DS/DD bar code decoders to a PLC-5 over DH485 through a 2760-RB module.

Download the PDF75 KB

Covers · 2 models

The models it covers

Summary

What is in it

Allen-Bradley application note explaining how to interface the 2755-DS/DD bar code decoder to the 2760-RB network interface module using the DH485 protocol and the 2760-SFC2 protocol cartridge, so bar code data reaches a PLC-5. It lists the hardware and software needed, DIP switch settings, the decoder and 2760-RB configuration screens, normal-operation LEDs, the PLC data table format, sample ladder programs and cable diagrams.

Its parts

  1. Overview
  2. Hardware Requirements
  3. Software Requirements
  4. Related Publications
  5. Configuration
  6. Running the Application

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Allen-Bradley application note (publication 2755-2.55, September 1995) on connecting 2755-DS/DD bar code decoders to a PLC-5 through a 2760-RB network interface module over DH485. It gives example DIP switch settings, configuration screens, a sample ladder program and cable diagrams so bar code data reaches the PLC data table.

Network
DH485 link to a 2760-RB module fitted with a 2760-SFC2 protocol cartridge p. 1
Decoders per module
Up to thirty one on each of three ports, ninety three per 2760-RB p. 1
Hardware needed
2760-RB in a Bulletin 1771 rack with a PLC-5, 2760-SFC2 cartridge, 1784-KT or equivalent card, DH485 cables, PC or VT-100 terminal p. 1
Software needed
Bulletin 6200 PLC-5 development software; terminal emulation such as Procomm or Windows Terminal p. 1
Network cable
Beldon 9842 or equivalent (spelling as printed) p. 10
Host connection
Decoder host port (25-pin D male) to 2760-RB Port 1 (25-pin D male) over RS-485 p. 10
Decoder mode
RS485 ASCII Mode 1 or Mode 2; the decoder waits for a poll from the 2760-RB p. 4
Module placement
2760-RB in Slot 0 of the 1771 chassis, next to the PLC; decoder on Port 1 p. 2
Port speed
2760-RB example: 19200 bits per second, BCD node numbers and byte swapping enabled p. 7
Data in the PLC
Byte count in BCD, data source and destination, LSAP number (always 80H) and node number, then data p. 4
Normal operation LEDs
2760-RB Active/Fault LED flashes green, Port 1 LED dim green; decoder yellow Communication LED solid on p. 4
Remote I/O option
A 1771-ASB module can reach the 2760-RB over the backplane via Remote I/O p. 2
Related manuals
Decoder User Manual publication 2755-833; 2760-RB details in publication 2760-ND001 p. 2

What this manual walks you through

  • Setting the PLC-5, chassis backplane and 2760-RB DIP switches p. 3
  • Entering the 2760-RB configuration screens 3, 21 and 11 p. 5, 6, 7
  • Writing the sample block transfer program for the PLC-5 p. 8
  • Adding an Immediate Input rung for New Generation PLC-5 processors p. 9
  • Wiring the configuration, auxiliary and host port cables p. 10
  • Checking normal operation and reading bar code data in the PLC p. 4
  • Choosing the PLC program for each 2760-RB revision and PLC-5 generation p. 2

Good to know

  • If the 2760-RB is not set to poll a decoder's node, that decoder will not read any bar codes. p. 4
  • Reset the 2760-RB to factory defaults with Main Menu Selection 90B before entering the screens. p. 5
  • The Block Transfer Read must come before the Block Transfer Write. p. 9
  • Symbology and trigger settings are outside this note; it points to publication 2755-833. p. 2

Questions this manual answers

How many 2755-DS decoders can one 2760-RB module handle?

Up to thirty one decoders on each of its three network ports, ninety three in all. p. 1

What cable connects a 2755-DS/DD decoder to the 2760-RB?

An RS-485 cable from the decoder host port to 2760-RB Port 1, using Beldon 9842 cable or equivalent. p. 10

Why does my 2755-DS decoder refuse to read bar codes on DH485?

In network mode the decoder waits for a poll; if the 2760-RB is not set to poll its node, it will not read. p. 4

Which LEDs show the 2755-DS/DD link is working?

The 2760-RB Active/Fault LED flashes green, its Port 1 LED is dim green, and the decoder's yellow Communication LED is solid on. p. 4

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Overview1
  2. Hardware Requirements1
  3. Software Requirements1
  4. Related Publications2
  5. Configuration2
  6. Running the Application4
  7. Back Cover12

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 31-3
  2. Pages 4 to 124-12

The file

Revision and size

Part no.2755-2.55
RevisionSeptember 1995
PublisherAllen-Bradley
Pages12
PDF75 KB
TextText from the PDF itself.
2755-2.55

The first pages · 3 of 12

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 12
Page 2
Page 2of 12
Page 3
Page 3of 12