Application Note: Interfacing DS/DD Bar Code Decoder to PLC-5, pages 4 to 12

Pages 4 to 12 of 12: Running the Application; Back Cover

The original document is the PDF (75 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 2755-DD and Allen-Bradley 2755-DS

Page 4

4

Running the Application

The configuration screens for the 2760-RB and the 2755-DS/DD decoder should be entered exactly as shown in the following pages. Save them, and then restart the decoder. Connect a network cable from the host port of the 2755-DD/DS decoder to port #1 of the 2760-RB. See Figure 6 for cable construction information. When the 2755-DS/DD is in the network mode (RS485 ASCII Mode 1 or RS485 ASCII Mode 2) it will be waiting for a poll from the 2760-RB module. If the 2760-RB is not configured to poll a node that is physically installed on the network, the decoder will refuse to read any bar codes. When the decoder has valid bar code data or a ”no read message” it will transmit the data to the 2760-RB on receipt of a poll. You can recognize “Normal operation ” by green LED’s on the 2760-RB module

• The Active/Fault LED will flash green. • The Port 1 LED will be dim green. In addition, the yellow Communication LED on the 2755-DS/DD Decoder will be “Solid ON”. The bar code data will appear in the PLC data table in the following format: 0

BYTE COUNT IN BCD

BYTE COUNT IN BCD

1

DATA SOURCE

DATA DESTINATION

2

LSAP NUMBER (ALWAYS 80H)

NODE NUMBER

3

DATA

DATA

4

DATA

DATA

5

DATA

DATA

See the 2760-RB and the 2760-SFC2 User Manuals for further information.

2755-2.55 – September 1995

Page 5

5

Figure 2 2755-DS/DD Host Communications Configuration Screens

Important: When configuring the 2760-RB module, first select “Main Menu Selection 90B” to reset the unit to factory defaults. Then configure screens 3, 21, and 11 in that order exactly as shown below.

2755-2.55 – September 1995

Page 6

6

Figure 3a 2760-RB Module Configuration Screens

2760–RB SERIES A REVISION J COPYRIGHT 1989 ALLEN–BRADLEY COMPANY, INC. –––––––––––––––––––––––––––––––––––––––––––––––––––– 1X – CONFIGURATION PARAMETERS 2X – IDENTIFICATION NUMBERS 3 – DEVICE PORT PROTOCOL NAMES 4DM – MATCH CODE ENTRIES 5I – DISCRETE BYTE INPUT ENTRIES 6 – THE DATA MATRIX ENTRIES 7 – THE PASS THROUGH ENTRIES 8 – NON–VOLATILE SCRATCH PAD AREA 9XF – RB MODULE FUNCTIONS AX – HARDWARE DIAGNOSTICS BX – SOFTWARE DIAGNOSTICS C – EXIT CONFIGURATION MODE WHERE X (0 TO 7) AND D (1 TO 3) ARE PORT NUMBERS WHICH ARE DEFINED BELOW : 0 – RB CMMND PRCSS 2 – SERIAL PORT 2 4 – CONFIG PORT 6 – I/O RACK SLT 1 1 – SERIAL PORT 1 3 – SERIAL PORT 3 5 – I/O RACK SLT 0 7 – RESERVED WHERE F (A TO E) ARE FUNCTIONS THAT RB CAN PERFORM WHICH ARE DEFINED BELOW : A – RESET B – SET DEFAULTS C – FLUSH D – INITIALIZE E – CLEAR DIAGS WHERE M (A TO T) AND I (A TO H) ARE ENTRY NUMBERS FOR THE SELECTION MADE ABOVE. ENTER A MAIN MENU SELECTION:

ENTER A MAIN MENU SELECTION: 3 PORT 1 = COPYRIGHT 1989 ALLEN–BRADLEY COMPANY, INC. 2760–SFC2 LAN , SERIES A , REVISION A (YES/NO) = YES. PORT 2 = COPYRIGHT 1989 ALLEN–BRADLEY COMPANY, INC. 2760–SFC2 DT , SERIES A , REVISION A (YES/NO) = YES. PORT 3 = COPYRIGHT 1989 ALLEN–BRADLEY COMPANY, INC. 2760–SFC2 LAN , SERIES A , REVISION A (YES/NO) = YES. EDIT THIS SELECTION (YES/NO) ?

2755-2.55 – September 1995

Page 7

7

Figure 3b 2760-RB Module Configuration Screens

ENTER A MAIN MENU SELECTION: 21 RS485 LAN 2755-DM6 ASCII MODE 3, 0h (YES/NO) = YES EDIT THIS SELECTION (YES/NO) ?

ENTER A MAIN MENU SELECTION: 11 SLOT TIME (NO. CHARS) (DEC 0...255) = 7. INTER-CHAR TIME (NO. CHARS) (DEC 0...255) = 7. IDLE TIME (NO. CHARS) (DEC 0...255) = 3. RETRIES (DEC 0...255) = 3. 19200 BITS PER SECOND (YES/NO) = YES. BCD NODE NUMBERS (ENABLE/DISABLE) = ENABLE. BYTE SWAPPING (ENABLE/DISABLE) = ENABLE. RECEIVE MATRIXING (ENABLE/DISABLE) = DISABLE. MATRIX ADDRESS (HEX 0...ffff) = 0. RE–ESTABLISH FREQUENCY (DEC 0...255) = 5. POLL FREQUENCY/DESTINATION[0] (HEX 0...ffff) = 5. POLL FREQUENCY/DESTINATION[1] (HEX 0...ffff) = 105. POLL FREQUENCY/DESTINATION[2] (HEX 0...ffff) = 5. POLL FREQUENCY/DESTINATION[3] (HEX 0...ffff) = 5. POLL FREQUENCY/DESTINATION[4] (HEX 0...ffff) = 5. POLL FREQUENCY/DESTINATION[5] (HEX 0...ffff) = 5. POLL FREQUENCY/DESTINATION[6] (HEX 0...ffff) = 5. POLL FREQUENCY/DESTINATION[7] (HEX 0...ffff) = 5. POLL FREQUENCY/DESTINATION[8] (HEX 0...ffff) = 5. POLL FREQUENCY/DESTINATION[9] (HEX 0...ffff) = 5. POLL FREQUENCY/DESTINATION[10] (HEX 0...ffff) = 5. CONTINUE THIS SELECTION (YES/NO) ? EDIT THIS SELECTION (YES/NO) ?

2755-2.55 – September 1995

Page 8

8

Figure 4 Sample PLC Program PLC 5/15/25 Etc. to 2760-RB

| I:000 N7:0 N7:5 +–––––––––––––––––––––––+ | +–––] [–––––]/[––––––]/[––––––––+Block Transfer Read +––O––+ | 13 15 15 |Rack 0| | | |Group 1| | | |Module 0| | | |Control Block N7:100+––O––+ | |Length 0| | | |Continuous N| | | +–––––––––––––––––––––––+ | | | | | | Write | | Data N7:0 N7:5 +–––––––––––––––––––––––+ | +–––] [–––––]/[––––––]/[––––––––+Block Transfer Write | | | 15 15 |Rack 0| | | |Group 1+––O––+ | |Module 0| | | |Control Block N7:5| | | |Data File N7:200+––O––| | |Length 0| | | |Continuous N| | | +–––––––––––––––––––––––+ | | |

Refer to your PLC-5 Instruction Reference Manual for detailed information on using the PLC-5 programming software.

2755-2.55 – September 1995

Page 9

9

Using the 2760-RB, Revision H or Above, with the New Generation PLC5 When the 2760-RB, Revision H or above, is used with the New Generation PLC5 processors in a local rack, there is a possibility that the PLC will not see the BRR bit from the 2760-RB. For the PLC5 to see the BTR bit, an odd number of image scans must occur. To ensure that the BTR instruction sees the BRR bit (bit 13) you must place an Immediate Input Instruction addressed to the BRR bit in another rung just before the Block Transfer Read (BTR) rung. This ensures that the BRR bit is seen by the NP-5 processor. See Figure 5 below. Figure 5 Sample PLC Program 2760-RB, Revision H or J to PLC 5/20/30/40/50

| BRR BT7:5 BT7:25 001 | +–––]/[–––––]/[––––––]/[–––––––––––––––( IIN )––––––––––––––––+ | | | BTR | | BRR BT7:5 BT7:25 +––––––––––––––––––––––+ | +–––] [–––––]/[––––––]/[–––––––––+Rack 0| | | EN EN |Group 1| | | |Module 0+––O––+ | |Control Block BT7:5| | | |Data File N7:200| | | |Length 0+––O––+ | |Continuous N| | | +––––––––––––––––––––––+ | | | | | | Write BTW | | Data BT7:5 BT7:25 +––––––––––––––––––––––+ | +–––] [–––––]/[––––––]/[–––––––––+Rack 0| | | EN EN |Group 1| | | |Module 0+––O––+ | |Control Block BT7:25| | | |Data File N7:400| | | |Length 0+––O––+ | |Continuous N| | | +––––––––––––––––––––––+ | | | | | | | | |

Note: BTR must come before BTW.

2755-2.55 – September 1995

Page 10

10

Figure 6 Cable diagrams 2760-RB Module (Configuration Port) 25-pin “D”, Male to

TX 2 RX 3

1784-T45 (Terminal Mode) 25-pin “D”, Female

3 RX 2 TX 7 GND 4 – 5 jumper 6 – 20 jumper

GND 7

2760-RB Module (Configuration Port) 25-pin “D”, Male to

Dumb Terminal (VT-100) 25-pin “D”, Female

3 RX 2 TX 7 GND

TX 2 RX 3 GND 7

2755-DSIA (Auxiliary Port) 25-pin “D”, Male to

Dumb Terminal (VT-100) 25-pin “D”, Female

RX 2 TX 3 GND 7

2 TX 3 RX 7 GND

2755-DSIA (Host Port) 25-pin “D” male

2760-RB (Port 1) * 25-pin “D” male to

(–) RS-485 14

14 (–) RS-485

(+) RS-485 13 Jumper 12

15 (+) RS-485

Cable Shield 1 Com 7

7 GND

Note: Use Beldon 9842 Cable or Equivalant. *Note: Refer to Publication 2760-822 (Pages 4-11 and 5-5) for further RS-485 wiring details, especially if using the node connectors provided with the 2760-SFC2 Protocol Cartridges.

2755-2.55 – September 1995 or 9-pin PC Com Port

2 RX 3 TX 5 GND 4 – 6 jumper 7 – 8 jumper or 9-pin PC Com Port

3 TX 2 RX 5 GND 4 – 6 jumper 7 – 8 jumper

Page 11

11

Notes:

2755-2.55 – September 1995

Page 12

SLC 5/03, SLC 5/04, DH+, and INTERCHANGE are trademarks of Allen-Bradley Company, Inc. OS/2 is a registered trademark of International Business Machines, Incorporated. Gateway 2000 and COLORBOOK are trademarks of Gateway 2000, Inc. Microsoft and MS are registered trademarks, and Windows is a trademark of Microsoft Corp. VERSA is a trademark of Nippon Electric Information Systems Inc.

Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the worlds leading technology companies.

Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia

Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444

Publication 2755-2.55 – September 1995

40062-320-01(A) Copyright 1995 Allen-Bradley Company, Inc. Printed in USA

1