Application Note: Interfacing DS/DD Bar Code Decoder to PLC-5, pages 1 to 3

Pages 1 to 3 of 12: Overview; Related Publications

The original document is the PDF (75 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 2755-DD and Allen-Bradley 2755-DS

Page 1

Application Note

- - %- -

- " Overview

The purpose of this application note is to explain how to interface the 2755-DS/DD Bar Code Decoder to the 2760-RB Network Interface Module via Allen Bradley’s proprietary DH485 communications protocol using the 2760-SFC2 protocol cartridge. Up to thirty one decoders can be interfaced to each of the three network interface ports for a total of up to ninety three decoders per 2760-RB module. This document includes cable diagrams and configuration information for the 2760-RB and the 2755-DS/DD decoder. Also included is an introductory PLC program necessary to establish communication from the PLC to the 2760-RB interface module.

Hardware Requirements

Implementation of the procedure described in this application note requires the following Allen-Bradley hardware: • Allen Bradley 2755 family of unattended bar code decoders. • Bulletin 2760-RB in a Bulletin 1771 rack with a PLC-5 processor • 2760-SFC2 protocol cartridge. • Personal computer (PC) with terminal emulator software or VT-100 type terminal to configure the 2755-DS/DD bar code decoder and the 2760-RB network interface module • Appropriate cables to program the PLC-5 and configure the Bulletin 2755 bar code decoder. Refer to hardware manuals for cable requirements. • Catalog Number 1784-KT or equivalent card installed in your personal computer to enable you to program the PLC-5. • DH485 network cables.

Software Requirements

Implementation of the procedure described in this application note requires the following Allen-Bradley software:

• Bulletin 6200 development software for the PLC-5 • Terminal Emulation Package (such as or Terminal) if a personal computer is used to configure the 2755 DS/DD.

2755-2.55 – September 1995

Page 2

2

Related Publications

This document refers to the following publications, which should be available for reference while working through this application note: Publication Number

Configuration

Title

1785-XXX

User Manual for your PLC-5

6200-XXX

Programming Manual for your PLC-5

2755-833

Bulletin 2755-DS/DD Enhanced Decoder User Manual

2760-ND001

Bulletin 2760 Flexible Interface Module User Manual

2755-822

Bulletin 2760 RS485 LAN Master/Slave Protocol Cartridge User Manual

Mount the Catalog Number 2760-RB interface module in Slot 0 of the 1771 chassis (next to the PLC). The Bulletin 2755-DS/DD bar code decoder communicates through Port 1 of the 2760-RB module. A Catalog Number 1771-ASB interface module can also be used to communicate with the 2760-RB module over the chassis backplane via Remote I/O. The 2760-RB configuration example in this document includes configuration screens and DIP switch settings necessary to establish communications with the 2755-DS/DD decoder via DH485. The 2760-RB and the 1771 chassis are set up for two slot addressing. There are other 2760-RB configuration features available and not used. See Publication 2760-ND001 for additional information. The 2755-DS/DD decoder configuration shows only the screens necessary to establish communications to the 2760-RB module. Other decoder configuration parameters such as selecting bar code symbology or a decoder trigger method are beyond the scope of this document. See the Decoder User Manual Publication 2755-833 for additional information. The PLC program is a minimum mode example showing that data can be moved into the PLC. Use the following table as a configuration guideline when using the examples shown in this document. PLC 5 COMPATABILITY

2760-RB In Use Series A, Rev. G or below Series A, Rev H or Above

2755-2.55 – September 1995

PLC-5, -15, -25, etc. Follow example PLC program as shown in Figure No. 4.

New Generation PLC-5 (Series A, Rev. C or above only) Set BT Compatibility Bit S26/4 while in program mode. Use example PLC program shown Figure No. 4. Add ladder logic using IIN update of RB. BTR must be before ‘BTW. Refer to Figure No. 5

Page 3

3

Figure 1 Configuration 2760-SFC2

PLC-5

2760-RB

1771-P4 Power Supply

Bulletin 1771 Rack

Bulletin 2755-L Scanner

Dumb Terminal or PC Running Terminal Emulation Software

DH485 Host Port

Beldon 9842 Cable or Equivalant

2755-DD/DS, -DM6/9

Table A (Example) PLC-5 Processor Dip Switch Settings Switch No.

1

2

3

4

5

6

7

8

SWI-1 on on on on on on on off

SWI-2 off on on on on on on off

SW-3 on on off off

Table B (Example) I/O Chassis Backplane Dip Switch Settings 1

2

3

4

5

6

7

8 off off off off off on off off

Table C (Example) 2760-RB Module Dip Switch Settings Switch No.

1

2

3

4

5

6

7

8

SWI-1 off off off off off off off off

SWI-2 off off off off off off off off

SW-3 off off off off

SW-4 off off on off

2755-2.55 – September 1995