Models 1708 and 1716 Remote Terminal Units Installation and Operation Manual
Manual86 pagesPDF 5.3 MB
Installation and operation manual for the Zetron Model 1708 and 1716 Remote Terminal Units used in wireless SCADA telemetry systems.
Covers · 1 model
The models it covers
Summary
What is in it
The installation and operation manual for the Zetron Model 1708 and 1716 Remote Terminal Units (RTUs), which work with a Model 1700 Controller and two-way radios to monitor and control equipment at remote sites. It gives specifications, then covers RTU addressing and configuration menus, fail safe setup, store and forward, digital and analog input and output definitions, MODBUS system setup, installation and radio connection, jumper settings and I/O connections for each model, theory of operation, troubleshooting and repair.
Its parts
- Introduction
- Specifications
- Operation
- MODBUS System Set Up
- Set Up and Installation
- Theory of Operation
- Troubleshooting Guide
- Repair
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Installation and operation manual (2004, part 025-9209J) for the Zetron Model 1708 and Model 1716 remote terminal units (RTUs), used with the Model 1700 controller in a radio SCADA telemetry system. It covers the specifications, addressing and menu configuration, MODBUS setup, radio wiring and jumpers, I/O pinouts, and troubleshooting.
- Device
- Remote terminal unit (RTU) of a wireless SCADA telemetry system, working with a Model 1700 controller over two-way radio p. 11
- Digital I/O
- 1708: 8 contact closure inputs and 8 open collector outputs, 12 Vdc, 100 mA max (1716: 16 each) p. 16
- Analog I/O
- 1708: 4 inputs, 0 to 5 Vdc, 8-bit A/D (1716: 8); analog outputs on the 1716 only p. 16
- Power
- 10.5-16 Vdc; 75 mA typical, 150 mA maximum p. 15
- Size and weight
- 7.25"W x 10.5"L x 2.25"H; 2 pounds p. 15
- Operating temperature
- 0 to +60 degrees C p. 15
- RS-232 port
- DB9 (J2), 4800 baud, 8 bits, no parity, 1 stop bit; used only for programming p. 15, 30, 51
- Radio interface
- 1200 baud data; audio out 20 mV to 2 V p-p, audio in 100 mV to 4 V p-p; PTT relay contact, 300 mA max p. 15
- Inputs
- Contact closure to ground or 0-5 V change; logic low under 0.8 Vdc, high over 2.0 Vdc; protected to +50 VDC p. 16
- Addressing
- 8-position DIP switch SW1 sets addresses 1 to 255; an address extension in the menus allows higher ones p. 18
- Part number
- Model 1708: Part No. 901-9260 (Model 1716: 901-9261) p. 50, 52
- MODBUS
- Up to 150 RTUs per Model 1700 controller with its MODBUS option; optional RTU EPROMs connect directly to the PC p. 13, 33
- Shared radio
- Transmit Request line lets up to 15 RTUs share one radio transceiver p. 48
- Low power reset
- Power is disconnected when supply drops below 9.35 volts ±5% p. 31
What this manual walks you through
- Setting the RTU address on the DIP switch p. 18
- Connecting a terminal and entering the configuration menus p. 19
- Main menu settings such as prekey time, channel busy and transceiver type p. 20
- Scaling 4-20 mA and 12-volt sensors to the 0-5 Vdc analog inputs p. 14
- Setting up MODBUS functions and I/O types p. 33
- Power, grounding and radio connector (P3) wiring p. 47, 48
- Carrier detect, PTT jumpers and audio level adjustment with test tones p. 48, 49, 50
- Model 1708 jumper settings and I/O connector pinouts p. 50, 51
- Connecting a local RTU to the Model 1700 controller p. 54
- Troubleshooting communication and radio keying problems p. 59, 60
Good to know
- Set the same prekey time on every RTU to avoid repeated data collisions. p. 20
- The chassis ground must be connected to earth ground with the field wiring. p. 47
- Remove the test jumpers when done; leaving radios transmitting continuously can harm some radios. p. 50
- Programming mode times out after 30 seconds, and radio data is suspended while in it. p. 30
- An analog source impedance over 5 kΩ makes the input more open to noise. p. 30
Questions this manual answers
What terminal settings do I use to program a Zetron 1708?
4800 baud, 8 bit, no parity, 1 stop bit; power the RTU, then press the space bar three times for the Main Menu. p. 19
How do I set the address of a Zetron 1708 RTU?
With the 8-position DIP switch SW1, counted in binary from 1 to 255; each unit needs a different ID. p. 18
What power does the Zetron 1708 need?
10.5-16 Vdc at less than 150 mA, so the radio's power supply is often used; a 12-volt gel cell can give backup. p. 47
Can the Zetron 1708 read 4-20 mA sensors?
Yes, by converting the loop to 1-5 Vdc with a 249 Ω resistor; jumpers JP11 to JP14 add that resistor on analog inputs 1 to 4. p. 14, 50
How many Zetron RTUs can share one radio?
Up to 15, by joining their Transmit Request pins; the RTU with the lowest ID has priority. p. 48