Models 1708 and 1716 Remote Terminal Units Installation and Operation Manual: INTRODUCTION

Pages 11 to 14 of 86, from Models 1708 and 1716 Remote Terminal Units Installation and Operation Manual

The original document is the PDF (5.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Zetron 1708

Page 11

INTRODUCTION

GENERAL A Model 1708 or 1716 Remote Terminal Unit (RTU) is one part of a wireless SCADAi telemetry system. A SCADA system typically consists of a PC with software connected to a Controller and one or more RTUs at multiple distant locations. The Controller and RTU are both microprocessor controlled and, along with the user’s radio link, make up the communications network necessary for monitoring and controlling equipment at remote sites. The Controller is typically located at a central office and can address up to 65,535 RTUs located at various remote sites. Using the Controller and the RTUs, the user at the central office can control equipment or retrieve information from the remote sites. The size of a system is dependent on airtime available and the total transmissions required. To determine the maximum number of RTUs your system will support, call Zetron at (425)820-6363. The RTU interfaces directly to a wide variety of two-way radios, either conventional or trunking. The RTU is designed to connect to remote sensing devices that can provide dry contact closure to ground, TTL level voltage changes or 0 to 5 volts and 4 to 20 mA for analog measurement. Table 1 lists the I/O capability of the Models 1708 and 1716 RTUs and the Model 1700 Controller.

i

SCADA = Supervisory Control and Data Acquisition. A general term for an industrial measurement, data gathering, and control system.

025-9209

1

Page 12

Introduction Table 1. Digital and Analog I/O Capability I/O

1708

1716

1700

Digital In Digital Out Analog In Analog Out

8 8 4 0

16 16 8 4

0 4 0 0

The RTU is initialized through the RS-232 port, which allows the user to customize the parameters for each RTU to best fit the application. SYSTEM DESCRIPTION

Transceiver

Model 1700 Control Unit

1708/1716 RTU Unit #1 I/O Lines

Transceiver Transceiver

1708/1716 RTU Unit #2 I/O Lines

PC, CRT, Printer or Status Panel Transceiver

1708/1716 RTU Unit #9 I/O Lines

Figure 1. A Typical System with One Controller and Nine RTUs Figure 1 depicts a model system that might be used to monitor and control pump stations. This system gives the user PC or status panel control of turning pumps on or off and of polling the sites to verify status and to receive alarm reports of pump failures or communications failures. MODBUS SYSTEM MODBUS is an industry-standard protocol used to transfer commands and data. An example of a SCADA program that uses the MODBUS protocol is Lookout (by National Instruments). Many PLCs also use the MODBUS protocol. A MODBUS option for the Model 1700 controller allows the controller and Zetron RTUs to be used in a MODBUS system.

2

025-9209

Page 13

Introduction A MODBUS SCADA system with a Model 1700 controller is shown in Figure 2. In a MODBUS system, the PC can communicate with up to 150 Model 1708 or Model 1716 RTUs over radio or wireline through a single Model 1700 controller. A system can be expanded beyond 150 RTUs by adding additional controllers and using additional serial ports on the PC. The total number of RTUs in a system is limited only by the number of serial ports available on the PC, and by the MODBUS slave address limit of 247. M1708/ M1716 RF

RS232

M1700 with

MODBUS Protocol

MODBUS option

Modbus PLC - or PC with Modbus SCADA Program

M1708/ M1716

RF

RS232

MODBUS Protocol

RF M1708/1716 with MODBUS

RF - Store & Forward option

M1708/ M1716

M1708/ M1716

Note: all RF connections could be replaced with leased lines

Figure 2. Generalized MODBUS System CONNECTIONS

Radio Connections

Model 1716 Remote Terminal Unit

Digital Inputs

#1 • • •

Main Power Flow Detector Door Open High Water High Temperature Panic Button

#16 Analog Inputs Digital Outputs #16 • • • #1

#1 • • • #8

Battery Level Tank Level

Pump Control On/Off Alarm On/Off Panic Acknowledge On/Off Back Up Power On/Off

Figure 3. Model 1716 RTU Standard Connections for a Pump Site A standard application of monitoring and controlling a remote pump site could be accomplished by using output #1 to control the pumps on/off switch and by connecting input #1 to a flow meter to determine if the pump is pumping. If the control relay on the RTU is damaged, the pipe is blocked, or a short or open circuit to the pump control has occurred, then the RTU will report that no liquid is flowing.

025-9209

3

Page 14

Introduction There are a variety of other status points that may be monitored: open door or window, high water alarm, high temperature, main power, panic button for man at site, etc. The RTU analog input range is 0 to 5 Vdc, and the levels being monitored should be electrically scaled to fall within this voltage range. Many sensing devices output 0 to 5 Vdc. However, some sensor outputs are 4 to 20 mA current loops, or an input may be using a 12volt power supply. The diagram below shows how to convert these two power sources into 0 to 5 Vdc levels for the RTU (4-20 mA Loop would be converted to 1-5 Vdc). There is a 249 Ω resistor in the RTU that may be used to convert 4-20 mA to volts. 12 Vdc Power Supply 470 kΩ Analog Input

330 kΩ

Analog Input

4 - 20 mA Loop 249 Ω

Figure 4. Common Conversion Circuits for 0-5 Vdc Scaling

4

025-9209