Models 1708 and 1716 Remote Terminal Units Installation and Operation Manual, pages 15 to 23

Pages 15 to 23 of 86: SPECIFICATIONS; OPERATION

The original document is the PDF (5.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Zetron 1708

Page 15

SPECIFICATIONS PHYSICAL SPECIFICATIONS Power

10.5-16 Vdc

Current

75 mA typical, 150 mA maximum

Temperature

0 to +60 degrees C

Size

7.25"W x 10.5"L x 2.25"H

Weight

2 pounds

RS-232 INTERFACE Baud Rate

4800

Parity

None

Bits

8

Stop Bits

1

RADIO INTERFACE Audio Output

20 mV to 2 V p-p (mic level audio), 1 kΩ

Audio Input

100 mV to 4 V p-p, 50 kΩ

Channel Busy Input

Low: 0 to 0.7 Vdc, <100 Ω to ground High: 3.5 to 12 Vdc, >10 kΩ to ground

PTT output

Relay contact closure, 300 mA max

Radio Modem Specifications Data Rate

1200 baud

Signaling

Minimum Shift Keying (MSK)

025-9209

5

Page 16

Specifications Signal Integrity Required Signal Strength

95% success at 12 dB SINAD

Probability of False Data

1 in 109 (0.0000001%)

I/O SPECIFICATIONS External Inputs Contact Closure Inputs

Model 1708: 8 inputs Model 1716: 16 inputs Contact closure to ground or 0-5 V or 5-0 V voltage change Logic low: <500 Ω or <0.8 Vdc Logic high: >2.5 kΩ or >2.0 Vdc Protected to +50 VDC

Analog Inputs

Model 1708: 4 inputs Model 1716: 8 inputs 0 to 5 Vdc analog sensor with 8-bit A/D input

External Outputs

6

Open Collector Outputs

Model 1708: 8 outputs Model 1716: 16 outputs 12 Vdc, 100 mA max

Analog Outputs

Model 1716: 4 outputs 0 to 5 Vdc 8-bit D/A

025-9209

Page 17

OPERATION

GENERAL OPERATION The Model 1708 and Model 1716 Remote Terminal Units (RTUs) perform two basic tasks: 1. RTUs report changes in input/output to the Controller 2. RTUs respond to commands from the Controller. Analog and digital inputs may be configured to report changes as they occur without being polled by the Controller (report by exception). When the RTU recognizes an alarm condition, it will check to see if the radio channel is busy. If the channel is busy, the RTU will wait for the channel to clear. If the channel is not busy, the RTU will transmit its data and wait for a reply from the Controller indicating that the alarm was received. If the RTU has not received a reply within 15 seconds, it will re-send the packet and wait for a reply. In all cases, the RTU will continue attempting to complete the transmission sequence until it receives the correct response. Each RTU can be configured differently so that the user can customize operation to match the requirements of the application.

025-9209

7

Page 18

Operation ADDRESSING THE RTU The RTU is DIP switch addressable from 1 to 255. This is done by using the 8-position DIP switch labeled SW1. Position #1 is the LSB and position #8 is the MSB. All switches off corresponds to 0, and all switches on is 255. The count is binary: #1

→

1

#2

→

2

#3

→

4

#4

→

8

#5

→ 16

#6

→ 32

#7

→ 64

#8

→ 128

Each unit on a system must have a different ID in order to respond. Examples: 1

2

3

4

5

6

7

8

ON OFF

The configuration above would define this unit as #3: 1 + 2 = 3 1

2

3

4

5

6

7

8

ON OFF

The configuration above would define this unit as #26: 2 + 8 + 16 = 26

Note The RTU may be given an address greater than 255 by changing the address extension through the configuration menus. See “Address Extension” on page 11.

8

025-9209

Page 19

Operation CONFIGURATION Each RTU will need to be configured prior to its use unless the factory default initialization values are satisfactory for the application. To configure an RTU, you will need: 1. A “dumb terminal” or a PC running in the dumb terminal mode. Software programs such as CrossTalk, Kermit, ZCU, Procomm, and others will provide terminal emulation on a PC. 2. A cable with a male 9-pin, D-style connector on one end to interface with the RTU and a connector on the other end to interface with the serial port of your PC or dumb terminal.

Note The pins on the RTU are different from those of other serial ports found on printers and modems. You will need to use the cable provided with the Model 1700 Controller, make up your own cable, or purchase an additional cable from Zetron for programming the RTUs. Accessing the RTU Program Mode 1. Connect the serial cable between J2, the 9-pin “D” style connector on the RTU, and the serial port of the PC or dumb terminal. 2. Connect a 12-volt power supply with power off to the RTU pin 1 of P3 and ground to pin 2 of P3. 3. Make sure your dumb terminal or PC is set at 4800 baud, 8 bit, no parity, 1 stop bit. 4. Turn the 12-volt power supply on. You should see the RTU model number and the software version displayed on the CRT. 5. Press the space bar three times to enter the Main Menu.

025-9209

9

Page 20

Operation MAIN MENU Table 2. RTU Main Menu Menu Selections

Range

Factory Settings

{P}rekey time

0-40 (x0.1 second)

5 (0.5 second)

{C}hannel busy detect

Low or High

Low (inhibit on logic low)

Channel {B}usy Timeout

0-40 (x0.1 second)

0.5 second

{T}ransceiver type

Conventional or Trunking

Conventional

Add{r}ess extension

0-65280

0

Co{N}troller Address

0-65535

0

{G}roup Call Address

0-65535

65535

Fai{L} safe setup {S}tore and Forward {O}utput Definition {D}igital Input Definition {A}nalog Input Definition {F}actory defaults E{x}it

To select a menu item, press any key that is within braces {}. Simply pressing ENTER will redisplay the current menu. If you do not press a key for 30 seconds, the RTU will automatically exit the menus. You must press the space bar three times to re-access. Prekey Time This menu selection allows the user to change the delay between the time PTT is activated and the time the MSK signaling begins. The default is 500 milliseconds and can range from 0 to 4 seconds in 100 millisecond increments. For trunked operation, this is the delay from the time a channel-acquired signal is received on the COR input until the data is sent. If there is no delay required (as should be with trunked radio), set this to zero.

CAUTION THE RTU CONTAINS A DATA COLLISION ALGORITHM. TO AVOID MULTIPLE DATA COLLISIONS, SET THE PREKEY TIME OF EACH RTU TO THE SAME VALUE!

10

025-9209

Page 21

Operation Channel Busy Detect To identify when the channel is in use, the carrier must be set to inhibit transmission on either High (+5 or open) or Low (0 V). The level entered here will PREVENT transmission. For trunked operation, this is used the same way to inhibit transmission. The proper name for this parameter should be “channel-acquired indication” when a trunked system is being used. Channel Busy Timeout Enter the amount of time (in tenths of seconds) that the channel has to be available before the RTU can seize the channel. This can prevent the RTU from interrupting a conversation. For trunked operation, this is used to determine that the TX indicator has stopped flashing (requesting a channel) and is on long enough to verify that the channel has been acquired. (This is only if you are using the TX indicator to provide the channel-acquired signal.) Transceiver Type This lets the user select whether the RTU is to be used on a conventional or trunking radio system. The difference being that in trunking, you request a channel by giving PTT and in conventional, you first look to see if the channel is available before giving PTT. For trunked operation timing, PTT is pressed for 15 seconds while looking for a channel. If a channel is acquired prior to the 15 seconds (this is based on the logic indication on the COR input), the RTU will wait the Prekey delay, send the data, and release PTT. After 15 seconds, if no channel is available, the RTU will release PTT, wait 30 seconds, and retry. Address Extension If you have more than 255 RTUs, enter the number to be added to the dip switch address for this RTU. It is suggested that you enter a multiple of 256 (256, 512, 768, 1024 etc.) and use this same number for the rest of the extended address RTUs (up to 255). Record this number on the sheet provided on the inside top cover of the RTU. Controller Address Enter the address of the unit that is to receive alarms from this RTU. The default is the Controller address 0. Group Call Address The Group Call Address allows outputs on several RTUs to be controlled in a single transmission from the Model 1700 Controller. When the controller sends an output control command to a group call address, all RTUs in the group will execute the command, but will not send back a response (in the case of momentary outputs, each RTU makes an exception report when the output returns to its idle state). Since the RTUs do not send response messages, the group call address cannot be used to poll inputs or outputs. 025-9209

11

Page 22

Operation All RTUs in a system can have the same group call address, or you can achieve a zoning effect by assigning one address to one group of RTUs and another address to a different group. The group call address should not be the same as the RTUs DIP switch address. Factory Defaults This menu selection will allow the user to reset all configurable parameters to the defaults set at the factory including input/output definitions. The user is prompted again to make sure all definitions really should be cleared. Exit This menu selection will take the user out of the configuration mode and reset the RTU to its “online” mode. FAIL SAFE SETUP The fail-safe menu contains several items that determine how the RTUs behave under abnormal conditions. In many installations, these features will not be needed, so they are disabled by default. Table 3. RTU Fail Safe Setup Menu Menu Selections {C}ommunication failure enable

Range

Factory Settings

0-10

0 (disabled)

Time period

0 to 30 minutes

0 (disabled)

# of reports

1 to 999

100

Time out interval

1 to 10 minutes

5 minutes

Channel {U}se limits

{E}nable exception reports enabled

{D}isable exception reports E{X}it

Communication Failure Enable Selecting this menu item allows you to set the number of times an exception report (power up alarm, input change alarm, or output change alarm) is sent without acknowledgement from its controller before the RTU enters the communications fail state. The range is 1 to 10 times. Entering a “0” (the default value) disables communications failure detection. In the failed state, all outputs on the RTU will be turned off - digital outputs go in to the high impedance state and analog outputs go to 0 volts. The outputs remain off even after communications are restored; they remain off until turned on again by a command from the controller. 12

025-9209

Page 23

Operation WARNING Do NOT enable the Communication Failure feature if you are using a Model 17 or Model 1700 Controller with a software version lower than 3.10. Doing so can cause permanent loss of communications between the RTU and the Controller and require a trip into the field to cycle power on the RTU. Channel Use Limits Failure of a transducer or other device attached to the inputs of an RTU may cause random alarm transmissions that tie up the radio channel. The RTU allows you to limit the number of exception reports (alarms) the RTU transmits within a specified period. If this number is exceeded, the RTU stays off the channel for a while before resuming alarm transmission. The period to monitor can be set in the range 1 to 30 minutes. The default value is zero, which disables this feature. The number of reports allowed during the period can range from 1 to 999 (100 is the default), and the time out interval can be from 1 to 10 minutes (5 minutes is the default). During the time out interval, any new alarms that may be detected are buffered (until the buffer gets full) and are sent when the interval ends. Enable/Disable Exception Reports The RTU can be set to poll-only mode by disabling exception reporting (alarms). This is a global setting that overrides the alarm enables on the individual inputs. This function is useful for temporarily disabling alarms while debugging an installation. STORE AND FORWARD Store and forward (also called “digi-peat” and “packet”) lets an RTU decode the information from another RTU and retransmit that information. This solves the problem of an RTU out of radio range of the controller. The RTU can pass its data through one or more RTUs to get to the Controller. Remember that this will increase the amount of time required for the transmission. Table 4. RTU Store and Forward Menu Menu Selections

Range

Factory Settings

{S}ource Address

0-65535

0

{D}estination Address

0-65535

0

Replacement S{o}urce Address

0-65535

0

Replacement D{e}stination Address

0-65535

0

{N}ext Slot E{x}it

025-9209

13