The text of a manual · part 5 of 12
Models 1708 and 1716 Remote Terminal Units Installation and Operation Manual, pages 24 to 32
Pages 24 to 32 of 86
The original document is the PDF (5.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Zetron 1708
Page 24
Operation Slot No. There are up to 16 slots to configure. Source Address Input the address of the transmitting unit. Destination Address Input the address of the unit that the transmitting unit is trying to reach. Replacement Source Address Input the new address of the transmitting unit. Replacement Destination Address Input the new destination address of the transmitting unit. Next slot Go to the next slot. Exit This selection will take the user back to the main menu. Example Controller Unit #0
RTU #5
RTU #150
If RTU #150 is out of range of Controller Unit #0, but RTU #5 is in range of both Controller Unit #0 and RTU #150, we would configure RTU #5 as the store and forward unit with the values shown in Table 5. Table 5. Store and Forward Address Assignments Parameter
14
Value
Parameter
Value
SLOT # 1 Source Address
0
SLOT # 2 Source Address
150
Destination Address
10
Destination Address
5
Replacement Source Address
5
Replacement Source Address
10
Replacement Destination Address
150
Replacement Destination Address
0
025-9209
Page 25
Operation We have configured RTU #5 to act as the store and forward unit between Controller Unit #0 and RTU #150. If Controller Unit #0 tries to poll RTU #10 (a fake address for RTU #150), the transmissions listed in Table 6 will occur. Table 6. Store and Forward Traffic Flow Transmission
From
To
Description
No. 1
#0
#10
Controller Unit #0 polls RTU #10.
No. 2
#5
#150
RTU #5 has been configured in Slot #1 to recognize and re-send all transmissions of 0-to-10 as 5-to-150.
No. 3
#150
#5
RTU #150 receives the poll from RTU #5 and sends its response back to RTU #5.
No. 4
#10
#0
RTU has been configured in Slot #2 to recognize and re-send all transmissions of 150-to-5 as 10-to-0. This completes the cycle.
Note Enter the ID of the out-of-range RTU higher than the largest ID of the in-range RTUs. Set the Controller address in the out-of-range RTU to its store and forward unit. This is done in the Co{N}troller Address section of the main menu. DIGITAL INPUT DEFINITION Table 7. RTU Digital Input Definition Menu Menu Selections
Range
{E}nable Input
Factory Settings Enabled
{D}isable Input N/{O} Input N/{C} Input {S}tatus Input De{b}ounce time
Status 0-65535 (x0.1 s)
0 seconds
{N}ext Input E{x}it
These menu selections control the performance of each input. Enable Input To allow the RTU to report an alarm from this input without being polled, the input must be enabled.
025-9209
15
Page 26
Operation Disable Input If the input is disabled, its status will still be sent during a poll response, but any change in the state of the input will not cause the RTU to transmit an alarm. N/O Input In the normally open mode, the input will cause an alarm transmission whenever it detects a change from high to low or open to closed (closure to ground). N/C Input In the normally closed mode, the input will cause an alarm transmission whenever it detects a change from low to high or closed to open. Status Input A status input will send an alarm message every time the input changes state. When the input changes, the alarm message will indicate the new state, high or low. Debounce Time Each input has a “debounce” time. Debounce is the amount of time the input must reside in the alarm condition in order to trigger the alarm. If this time is set to 3 seconds, the input must stay in the alarm condition for more than 3 seconds before the input will transpond an alarm message. The default setting is for no debounce time. The debounce time can be set from 0 to 6553.5 seconds in 0.1 second increments. Next Input This menu selection will increment the current input number for modification. If this is the last input on the RTU, the menu will wrap back to input #1. Exit This selection will take the user back to the main menu.
16
025-9209
Page 27
Operation DIGITAL OUTPUT DEFINITION Table 8. RTU Digital Output Definition Menu Menu Selections
Range
{L}atched mode {M}omentary mode
Factory Settings Latched
0-255 seconds
0 seconds
{O}utput ON {F}orce output OFF {N}ext output E{x}it
Latched Mode When latched mode is selected, if the output is commanded on, it will remain in that position until it is commanded off (or power is removed). Momentary Mode When momentary mode is selected, the user will be prompted for a time in seconds that the output is to remain in the on position after the output is commanded on. This value, 0-255, will cause the output to automatically return to the off position after the time has expired. Output On This menu selection allows the user to locally control the outputs. This is used to check operation and setting of the momentary time. Force Output Off This menu selection allows the user to locally control the outputs. This is used to check operation and setting of the momentary time. Next Output This menu selection allows the user to increment the current output number. Once incremented, the parameters for the new current output will be displayed along with the menu. Once the user reaches the last output for the RTU, this item will change the current output back to output number 1. Exit This selection takes the user back to the main menu.
025-9209
17
Page 28
Operation ANALOG INPUT DEFINITION Table 9. RTU Analog Input Definition Menu Menu Selections
Range
{E}nable Input
Factory Settings Enabled
{D}isable Input {H}igh Threshold Value
0-5.00 volts
5.00 volts
{L}ow Threshold Value
0-5.00 volts
0.00 volts
High {R}eset Value
0-5.00 volts
5.00 volts
Lo{w} Reset Value
0-5.00 volts
0.00 volts
Accumulator {S}ampling Rate
1 to 65535 (x0.1 second)
10 (1 sample per second)
% {C}hange alert
0 to 100%
1.9%
% Change de{B}ounce
0 to 250 (x0.1 second)
0.5 second
{N}ext Input E{x}it
Enable Input To allow the RTU to report an alarm from this input without being polled, the input must be enabled. Disable Input If the input is disabled, its status will still be sent during a poll response, but any change in state of the input will not cause the RTU to transmit an alarm. High Threshold If the voltage being measured exceeds this threshold and the input is enabled, the RTU will automatically report an alarm. The threshold value is 0-255, 0 corresponding to 0 volts and 255 corresponding to 5 volts. Low Threshold If the voltage being measured drops below this threshold and the input is enabled, the RTU will automatically report an alarm. The threshold value is 0-255, 0 corresponding to 0 volts and 255 corresponding to 5 volts. The threshold values set the limit. A low threshold of 0 and a high threshold of 255 effectively disable the alarm since these values cannot be surpassed.
18
025-9209
Page 29
Operation High Reset To provide for hysteresis, set this value slightly below the high threshold value. The voltage being measured must drop below the High Reset value before another alarm can be initiated. This prevents chattering when a voltage hovers right at the threshold value. Low Reset To provide for hysteresis, set this value slightly above the low threshold value. The voltage being measured must rise above the Low Reset value before another alarm can be initiated. Accumulator Sampling Rate Set the time between samples in 10th seconds. For example, “1” is 10 samples per second, “2” is 5 samples per second, “100” is one sample every 10 seconds, and “1000” is one sample every 100 seconds. The valid range is 1 to 65535, which represents from 0.1 to 6553.5 seconds between samples. % Change Alert % Change alert is the percent change of full scale from the last reported value that will cause another report. For example, if we are measuring feet of water in a 100-foot tank and we wish to know a minimum of every 4-ft change, we would set the % Change alert to 4/100 or 4.0%. If our starting value is 30 ft and the tank is rising, we should get an update at 34 ft, 38 ft, 42 ft, etc. % Change Debounce % Change de{B}ounce is the amount of time in seconds that the change must exist before the update can be sent. If, in the example in the previous paragraph, we have the debounce set to 5 seconds and the level rises from 30 to 34 feet for 3 seconds and then drops to 33 feet, no report would be sent. This programming option helps filter out noise spikes and reduce airtime usage. Next Input This will increment the current input number for modification. If the current input number is the last input for the RTU, the menu will wrap back to input #1. Exit This selection will take the user back to the main menu.
025-9209
19
Page 30
Operation SYSTEM OPERATIONAL LIMITS Inputs Chatter
Chattering occurs when a status being monitored changes rapidly, that is, more than once every few seconds. Chattering can cause the RTU to send multiple reports using excessive airtime. The debounce time and hog time in the RTU should be used to prevent excessive transmissions.
Broken Connection
Analog Input - The voltage read by the analog input would float, following the voltage of the previous analog input. More than 5 kΩ source impedance will increase susceptibility to noise. Digital Input - The digital inputs have a +12 Vdc pull up and will read a logic high with nothing connected.
Outputs
20
Power Up State
The analog inputs power up in a 0 volt state. The digital outputs power up in a high impedance, open collector state.
Power Off State
The analog inputs power off in a 0 volt state. The digital outputs power off in a high impedance.
Unit Over Voltage
Over voltage damage to any of the I/O, power supply, or RF inputs caused by lightning, improper connection, etc. can cause unpredictable behavior in any of the electronic components. The RTU provides safeguards against this type of damage, but damage is still possible. Full testing of suspect hardware should be performed.
RS-232
Currently the RTU only uses the serial port for programming. If the RTU is left in programming mode, the unit times out after 30 seconds and normal operation resume. While in programming mode, transmission and reception of data via FFSK is suspended.
025-9209
Page 31
Operation Power Brown Power
There is a low power reset circuit in the RTU which will disconnect power when supply voltage drops below 9.35 volts ±5%.
Power Up Conditions
The RTU performs a self-test on power up. If there are errors detected during the self-test, operation is suspended. The digital and analog output states are designed to be in a high impedance and 0 Vdc state respectively. If the self-test fails, these default values may not be valid.
Radio Connections and Associated Problems Loss of transmit or receive audio anywhere along the communications path (repeater, radio, connector or RTU) will cause a communications failure at both the RTU and Controller. Carrier Detect
Failed Connection - If the carrier detect fails, the RTU will transmit at will or be inhibited from transmitting. Transmitting at will increases the risk of collisions. Never transmitting causes a communications failure alarm at the Controller and a communications failure state at the RTU.
Push to Talk
If Push to Talk fails, the radio will either transmit no data or be locked in transmit and block all other transmissions on the channel. There are jumper settings to provide proper default open or closed conditions for power off and standby for most radios.
Transmit Request
Failed Connection - If the transmit request line is disconnected, collisions with the RTUs sharing the same radio may increase. If the transmit request line is shorted, this will cause a communications fail alarm at the Controller and a communications fail state at the RTU.
Addressing
DIP Switch Failure - If an RTU has a DIP switch failure causing a change in address, there is no provision for the Controller to recognize the error other than to show a communications failure for the old address. Data sent by the new address has the potential to false the data of another RTU at the same address. If there is a DIP switch failure causing a change in address, the Controller will not be able to communicate with the RTUs and possibly the PC.
025-9209
21
Page 32
Operation Radio System
A radio stuck in transmit for any reason (PTT held in, electronic failure, chattering PTT, etc.) will prevent or interfere with other transmissions. Radios should provide a PTT timer that prevents continuous transmission for extended periods, usually three minutes. This only helps if the radios are functioning properly. It will not prevent all cases of transmit lock-out.
RS-232
Transmit or receive data failure will cause loss of communications between the PC and the Controller. This will cause communications failure states at all RTUs and the Controller.
Buffering
If communications fail, the Controller will buffer 200 bytes, a minimum of 10 messages. After the buffer is full, the controller will stop acknowledging the RTUs and a critical system communications fail status will occur.
Ground
Poor grounding or no common signal ground can cause intermittent communications. A power cycle may appear to cure this situation for short periods of time.
Critical System Failures Summary Critical system failures can be caused by any of the following conditions:
22
•
Chattering input causing repeated transmissions
•
Radio stuck in transmit due to: ¾ PTT held on by RTU, user, or radio failure with no timeout ¾ Radio locked in transmit due to radio failure ¾ Carrier from another radio system causing interference ¾ Hardware/firmware failure causing chattering PTT
•
Repeater down
•
Controller radio down with no standby or backup
•
Controller is down due to: ¾ COR stuck active ¾ Power failure ¾ Equipment failure ¾ Hardware/firmware failure causing chattering PTT
•
RS-232 connection to Controller is down
•
PC or software failure
025-9209