For the Zetron 1708
Page 33
MODBUS SYSTEM SET UP This section describes the functioning of the Model 1700 controller and Model 1708/1716 RTUs in a MODBUS system. MODBUS OPTION The Model 1700 controller has an optional implementation of the industry standard MODBUS protocol. This option is provided by means of a replacement EPROM containing code to support the MODBUS protocol when communicating with the PC running the MODBUS application. The Model 1708 and Model 1716 RTUs do not require any modification to support the MODBUS protocol if they are communicating only with the Model 1700. There are optional EPROMs for both of the RTU models that will allow them to be interfaced directly to the PC, by-passing the Model 1700 controller. The MODBUS implementation makes the devices compatible with nearly all SCADA programs as well as with many PLCs. The Model 1700 is compatible with most MODBUS programs that use five-digit MODBUS addresses and limit themselves to the functions listed in Table 10. Table 10. Compatible MODBUS Functions MODBUS Function
Function Code
Used for...
Read Coil Status
01
Digital Outputs
Read Input Status
02
Digital Inputs
Read Holding Registers
03
Analog Outputs, Counters, Accumulators
Read Input Registers
04
Analog Inputs
Force Single Coil
05
Digital Outputs
Preset Single Register
06
Analog Outputs, Counters, Accumulators
Force Multiple Coils
0F
Digital Outputs
Preset Multiple Registers
10
Analog Outputs, Counters, Accumulators
The correspondence between Zetron and MODBUS I/O terminology is listed in Table 11. Table 11. Zetron and MODBUS I/O Terminology Zetron I/O Type
025-9209
MODBUS I/O Type
Digital/Relay Output
Coil
Digital Input
Input Status
Analog Input
Input Register
Analog Output
Holding Register
Accumulator
Holding Register
Counter
Holding Register
Run-time
Holding Register
23
Page 34
MODBUS System Set Up COMMUNICATIONS In a MODBUS system using radio or wireline communications, only the controller speaks MODBUS. For queries addressed to RTUs, the controller translates back and forth between the MODBUS protocol and the RTU radio protocol. There are two ways to set up a MODBUS system using the Model 1700 controller with the MODBUS option: Polled-only and report-by-exception. Polled-Only System In a polled-only system, the “master” PC or PLC controls all communication in the system. When a MODBUS query is sent to an RTU through the Model 1700 controller, the controller always translates the query to the RTU FFSK protocol and sends it out over the radio. When the RTU responds, the response is translated from RTU FFSK protocol to MODBUS protocol and sent back to the master through the serial port of the Model 1700 controller. Configuring a system as polled-only gives the master complete control over communications, particularly use of the radio channel, which can be a bottleneck. Radio communications occur only when the master polls an RTU. The RTUs never transmit except in response to a poll. There is no possibility of data collisions, which completely eliminates one cause of communication failures. On the other hand, there is one major disadvantage to a polled-only system. The master will not be able to see changes in RTU input status that occur between polls. It only sees the current input status at the time each poll response is sent. Any RTU input changes that occur between polls are lost. Report-By-Exception System In a report-by-exception system, RTUs report changes in I/O status as they occur without waiting to be polled by the master. The Model 1700 controller stores this status within its own memory. When the master polls for status from an RTU, the Model 1700 controller builds the poll response from this stored status, and sends it back to the master immediately. A radio transmission occurs only if the master tries to control an RTU output or asks for RTU status that the Model 1700 controller does not have. In this case, the Model 1700 must try to obtain the RTU status over the radio before it can build the response to send back to the master. A report-by-exception system should also use the Model 1700 controller autopoll feature. This causes the Model 1700 to periodically poll the input status for all RTUs in the system. If an RTU or its radio fails, the Model 1700 will not get a response to the poll and it will invalidate the status of the RTU. The next time the master tries to poll that RTU, a communications failure will occur unless the RTU has been fixed. The advantage to a report-by-exception system is that the master sees changes in RTU I/O status almost immediately. The main disadvantage is that data collisions can occur between polls from the master and exceptions from RTUs or between exceptions from different 24
025-9209
Page 35
MODBUS System Set Up RTUs. In a large system with lots of I/O activity, this can result in frequent communications failures. Which Is Better - Polled-Only or Report-By-Exception? A polled-only system is easier to configure. Problems in a polled-only system can be much easier to diagnose. For example, if a communications failure occurs, it can not be due to data collisions, but is probably a true indication of a problem with the RTU, radio or communications path. Therefore, a polled-only system should be favored over a report-byexception system. A report-by-exception configuration may be needed if the system is very large so that the polling loop takes a long time, or if some signal changes are short duration and need to be reported automatically by the RTU. For a small system where a radio channel is also used for voice communications, report-by-exception can reduce the amount of airtime used for data transmission. MODBUS MASTER REQUIREMENTS In a MODBUS system, the “master” will typically be a PC running a software application that is compatible with the MODBUS protocol. The following list contains some of the major requirements for this “master” to be compatible with the Model 1700 controller and the Model 1708/1716 RTUs. •
The serial port(s) on the PC must be capable of supporting a three-wire version of RS232 communications (Tx, Rx, ground). The communication parameters used are: 4800 baud, 8 data bits, no parity, and 2 stop bits.
•
The application must have a configurable polling timeout period. The range must allow enough time for a radio transmission to be sent to an RTU and for the response to be sent back (3 to 5 seconds minimum).
•
The application must limit itself to the command codes listed in Table 10.
•
The application must support the MODBUS RTU protocol (as opposed to the MODBUS ASCII or MODBUS Plus protocols).
Fortunately, most PC software packages that support MODBUS protocol follow these rules. In some software packages, MODBUS protocol support is a standard feature. For others, the MODBUS protocol must be purchased separately as an option. As long as the software meets the above requirements, it will work with the Model 1700 controller. Some of the software packages that work with the Model 1700 MODBUS option are listed on page 36.
025-9209
25
Page 36
MODBUS System Set Up CONFIGURING THE 1700 CONTROLLER When using the MODBUS option, the Model 1700 controller address is usually set to “1” (DIP switch 1 ON, DIP switches 2 through 6 OFF). Any address in the range of “1” to “63” could be used. It should never be set to “0”.ii The Model 1700 controller has built-in configuration menus that can be accessed through a PC with a terminal program. For more information on the general configuration of a controller, please see the “PROGRAMMABLE FEATURES” subsection of the “Model 1700 Controller Installation and Operation” manual, part number 025-9209. Only the menu items that apply to the MODBUS option are discussed here. MODBUS Menu When the MODBUS option is installed in the controller, the main menu displayed contains an additional item right after the RS232 {W}atchdog item, {M}odbus. Typing an “m” will open the menu listed in Table 12. Table 12. 1700 Controller MODBUS Menu Menu Selections
Range
Factory Settings
{R}TU status storage
Enable, Disable
Enabled
{A}utopoll...
Autopoll interval (0 to 65535 minutes) First autopoll RTU (1 to 255) Number of RTUs (1 to 255)
Autopoll interval = 0 First RTU = 1 Number of RTUs = 1
E{x}it
The following two subsections make reference to the items on the MODBUS menu. Polled-Only Configuration For a MODBUS, polled-only system, you must configure the following items. This is in addition to any other parameters you configure on the controller. 1.
From the controller main menu, type “M” to open the MODBUS menu.
2.
From the MODBUS menu, type “R” to open the RTU Status Storage item.
3.
At the RTU Status Storage prompt, type “D” to disable the status storage feature. This should return you to the MODBUS menu.
ii
The address “0” is a reserved address in the MODBUS protocol. If you give a controller or RTU an address of “0”, the PC or PLC will not be able to communicate with it.
26
025-9209
Page 37
MODBUS System Set Up 4.
From the MODBUS menu, type “A” to open the Autopoll menu.
5.
From the Autopoll menu, type “I” to open the Interval item.
6.
At the Autopoll Interval prompt, type in zero (0) and then press ENTER to disable the autopoll feature.
7.
At the Autopoll menu, type “X” to return to the MODBUS menu. At the MODBUS menu, type “X” to return to the controller main menu.
You may now exit the programming mode or continue with any other configuration programming you need to perform on this controller. Report-By-Exception Configuration For a MODBUS, report-by-exception system, you must configure the following items. This is in addition to any other parameters you configure on the controller. 1.
From the controller main menu, type “M” to open the MODBUS menu.
2.
From the MODBUS menu, type “R” to open the RTU Status Storage item. At the RTU Status Storage prompt, type “E” to enable the status storage feature. This should return you to the MODBUS menu.
3.
From the MODBUS menu, type “A” to open the Autopoll menu.
4.
From the Autopoll menu, type “I” to open the Interval item. At the Autopoll Interval prompt, type in the time in minutes that the 1700 controller must wait in between polls of all the RTUs in the system. Press ENTER to return to the Autopoll menu.
5.
From the Autopoll menu, type “F” to open the First RTU item. At the First RTU prompt, type in the address of the lowest numbered RTU in the system. Press ENTER to return to the Autopoll menu.
6.
From the Autopoll menu, type “N” to open the Number of RTUs item. At the Number of RTUs prompt, type in the total number of RTUs in the system. (It is highly recommended that the RTUs be consecutively numbered in any system that is automatically polled.) Press ENTER to return to the Autopoll menu.
7.
At the Autopoll menu, type “X” to return to the MODBUS menu. At the MODBUS menu, type “X” to return to the controller main menu.
8.
At the main controller menu, type “R” to open the Radio menu. At the Radio menu, type “R” to open the RTU response timeout item. At the RTU response timeout prompt, type in the number of seconds the controller should wait for an individual RTU to respond and press ENTER. This will return you to the Radio menu.
9.
From the Radio menu, type in “X” to return to the controller main menu.
025-9209
27
Page 38
MODBUS System Set Up You may now exit the programming mode or continue with any other configuration programming that you need to perform on this controller.
Note The RTU Response Timeout sets the period for which the controller will wait for a response whenever it polls an individual RTU. A period of 5 to 10 seconds will normally be adequate; however, if the store-and-forward method is being used, the timeout period might have to be set to a larger value. This value needs to be the smallest number of seconds that produces reliable results because it can affect the total amount of time required to poll all of the RTUs in the system. RS-232 Watchdog Configuration The Model 1700 controller has the ability to monitor the RS-232 serial connection for MODBUS protocol queries. If the master fails to send a MODBUS query for a specific amount of time, the Model 1700 controller will turn on its output number “1”. This output could be connected to some kind of alarm that would notify the system operator that either the master itself has failed or the RS-232 connection between the master and the Model 1700 controller has failed. This feature can be enabled or disabled, and the timeout period set through the Model 1700 controller RS-232 watchdog menu. The default setting is disabled. The range for the timeout period is 10 to 65535 in seconds (just over 18 hours maximum). CONFIGURING THE RTUs Unless an RTU is interfaced directly to the master PC that is running the MODBUS program, there is no special configuration necessary. The RTU communicates with the Model 1700 and the controller takes care of translating the information received into the MODBUS protocol format. The same applies to any commands sent from the master PC out to the RTUs by means of the controller. If the RTU is to interfaced directly to a serial port on the master PC, then it must have the optional MODBUS version of the firmware installed. This version of the RTU firmware does not show any radio configuration options since the RTU communicates directly with the master PC. Assign Addresses The default setting for the RTU address is zero. This should be set to a number between one and 255 (not the same address as the Model 1700 controller). Each RTU must have a unique address. See “ADDRESSING THE RTU” on page 8 for more information on setting the RTU address.
28
025-9209
Page 39
MODBUS System Set Up MODBUS Version of the RTU Menu When you access the program mode for a Model 1708/1716 that has been equipped with the MODBUS version of the RTU firmware, a shortened version of the main menu appears. Table 13 lists this modified menu. Basically, all the menu items dealing with radio communication or the controller addressing have been removed. Table 13. RTU Main Menu with MODBUS Option Installed Menu Selections {O}utput Definition {D}igital Input Definition {A}nalog Input Definition RS232 {W}atchdog... {F}actory defaults E{x}it
With the exception of the last two menu items ({F}actory defaults and E{x}it), typing in the letter for a menu item opens a submenu. The I/O menu items work just as they would for a regular RTU. The item that is new to the MODBUS version is the RS232 {W}atchdog item. This is the same watchdog feature offered in the Model 1700 controller menu. Since the RTU is connected to the master PC in this configuration, it has the same need to alert the system operator if the serial communication link to the master PC is lost. CONFIGURING THE MASTER PC (OR PLC) Each MODBUS software package or PLC is configured differently, so we can only give general guidelines for configuring them here. The areas we will touch on include: serial communications, polling intervals, timeout periods, and retries. Serial Communications
The serial communication parameters used by the master never vary. They must always be set to 4800 baud, 8 data bits, no parity, and 2 stop bits.
Polling Intervals
Report-by-Exception
In a report-by-exception system, the polling interval used by the master can be set to a short period (on the order of 1 second). Much of the time the Model 1700 will be responding to the polls using the last known RTU status stored in its memory. Polled-Only
In poll-only systems, the polling interval is generally set to a value that allows the master enough time to have polled all the RTUs in the system. Example: if it takes five seconds for each RTU, and the system has 10 RTUs, the polling interval would be 50 seconds minimum (it could be longer). Some software packages allow different polling intervals for each RTU, so more important or 025-9209
29
Page 40
MODBUS System Set Up rapidly changing signals could be polled more often than less important or slowly changing signals. Timeout Periods
The timeout period should be the same for both poll-only and report-by-exception systems. The period should be set to minimum time that it takes for a poll to go out over the radio to an RTU and for the response to return to the master. A typical value is five seconds. However, if the RTUs are doing store-and-forward, or there is a lot of traffic on the radio channel, a longer timeout may be needed.
Retries
The master can usually be configured to retry a poll for a specified number of times before giving up and signaling a communications failure for that RTU. The appropriate setting for retries is really system dependent, but a value of 2 or 3 is usually a good starting place.
BASIC MODBUS I/O ADDRESSING The basic I/O capability of the Model 1700 controller consists of four digital outputs. These are open-collector outputs capable of sinking up to 100 mA and dealing with voltages up to 50 Vdc. In the MODBUS protocol, each I/O point is given a unique address. This address not only identifies a unique point within the system, it also tells the master what type of I/O point the address identifies. The MODBUS protocol also has its own nomenclature for the various I/O types. It also has its own set of ranges for data. Table 14 shows the relationship between MODBUS nomenclature for I/O addressing and the Zetron nomenclature used in the Model 1700, Model 1708, and the Model 1716. Table 14. MODBUS versus Zetron I/O Addressing Zetron Values
30
MODBUS Values
I/O Type
Address Range
Value Range
I/O Type
Address Range
Value Range (Raw)
Digital Outputs
1 to 16
OFF, ON
Coils
1 to 16
0 (off), 1 (on)
Digital Inputs
1 to 16
Open Circuit, Grounded
Input Status
10001 to 10016
0 (open circuit) 1 (grounded)
Analog Inputs
1 to 8
0 to 5 V or 0 to 20 mA
Input Registers
30001 to 30008
0 to 32767
Analog Outputs
1 to 4
0 to 5 V
Holding Registers
40001 to 40004
0 to 32767
025-9209
Page 41
MODBUS System Set Up Within the MODBUS protocol, the Input Status and Input Register signal types (digital and analog inputs) are read-only. The Coil and Holding Register signal types (digital and analog outputs) may be both read from and written to. When configuring the MODBUS master, the MODBUS addresses and value ranges must be used. Table 15 lists the allowable range values in relation to the signal types. Table 15. MODBUS Values versus Signal Types I/O Type ⇓ MODBUS Value ⇒
0
1
Coil (digital output)
OFF (open circuit)
N/A
ON (grounded)
Input Status
OFF (open circuit or high voltage)
N/A
ON (ground or low voltage)
0
6553
32767
I/O Type ⇓ MODBUS Value ⇒ Input Register (analog input)
0 V or 0 mA
1 V or 4 mA
5 V or 20 mA
Holding Register (analog output)
0V
1V
5V
The most common usage for analog inputs and outputs is with transducers that convert some real world value either into a voltage (in the range 0 to 5V or 0 to 10V) or a current (in the range 4 to 20mA). Most MODBUS master software packages provide a way to configure input registers and holding registers so that the conversion from raw units used in the MODBUS protocol to real world units is done automatically. Here is an example. A sensor that measures water flow and outputs a current of 4mA for a flow of 0 gal/min and a current of 20mA for a flow of 100 gal/min. This sensor is connected to analog input number 5 of a Model 1716 RTU. In the MODBUS master software, input register 30005 would be configured with a raw range of 6553 (4mA) to 32767 (20mA) and a real world range of 0 gal/min to 100 gal/min. USING ACCUMULATORS AND COUNTERS Configuring the master to be able to access accumulators and counters is more difficult than for basic RTU I/O, and requires a good working knowledge of the MODBUS master software package. Analog input accumulators keep a running total of the analog input value over a period of time. There is one accumulator for each analog input on the Model 1708 or Model 1716 RTU. Each accumulator consists of three values: the accumulated total (sum of samples from the analog input), the total number of samples taken, and the sample rate (how often the analog input is read). Accumulators are usually used to keep a running total of some flow through a system. For example, if a sensor measuring flow in gal/min is connected to a Model 1708 RTU, the total flow in gallons can be tracked through the use of an accumulator. Accumulators can also be used to calculate the average value of an analog input. 025-9209
31
Page 42
MODBUS System Set Up There is one digital input counter for each input of the Model 1708 or Model 1716 RTU. Each counter consists of two values: the count and the time period since the counter was last cleared. The count value increments each time the input activates. When the input is set up as status mode, the count increments every time the input changes state. If the input is set up as normally open or normally closed, the count increments when the input is grounded or disconnected respectively. The accumulators and counters are accessed through MODBUS holding registers. Each accumulator or counter value (except for the accumulator sample rate) is spread across three separate holding registers. The lower four decimal digits are in the first register, the middle four decimal digits in the middle register, and the upper four decimal digits in the third register. The example in Table 16 shows accumulator 1 with a current accumulated value of 2,156,349,078, number of samples of 634,127,890, and sample rate of 2,354: Table 16. How Accumulator 1 Stores Data Register
Value
Description
41011
9078
Accumulated Value lower four decimal digits
41012
5634
Accumulated Value middle four decimal digits
41013
0021
Accumulated Value upper four decimal digits
41014
7890
Number of Samples lower four decimal digits
41015
3412
Number of Samples middle four decimal digits
41016
0006
Number of Samples upper four decimal digits
41017
2354
Sample rate (the sample rate uses one register)
Some MODBUS software packages (e.g. WonderWare’s Intouch) can automatically combine these registers into a single value. Others, (e.g. National Instrument’s Lookout) require the user to combine the registers into a single value in a “script”. For example, in Lookout, the “script” for the accumulated value might look like the following equation,
(((Rtu1.41013 × 10000) + Rtu1.41012) × 10000) + Rtu1.41011 Queries to read an accumulator or counter must request all associated registers or an illegal data address exception will be returned. An illegal data address exception will also be returned to queries that overlap accumulator or counter address boundaries by requesting more than nine registers. Writing to the first holding register address used by particular accumulator or counter will cause it to be cleared. The value written does not matter; the act of writing to the register causes the clearing. It is not possible to clear just part of an accumulator or counter. For example, you cannot clear the accumulator total without also clearing the number of samples.
32
025-9209
Page 43
MODBUS System Set Up An illegal data address exception will be returned to queries beginning at unused addresses, 40005 - 41010, 41088 - 42010, and 42167 - 99999. Only one accumulator or counter can be polled at a time. Table 17. Analog Accumulator Holding Register Addresses Accumulator
Value
# Samples
Sample Rate
1
41011 - 41013
41014 - 41016
41017
2
41021 - 41023
41024 - 41026
41027
3
41031 - 41033
41034 - 41036
41037
4
41041 - 41043
41044 - 41046
41047
5
41051 - 41053
41054 - 41056
41057
6
41061 - 41063
41064 - 41066
41067
7
41071 - 41073
41074 - 41076
41077
8
41081 - 41083
41084 - 41086
41087
Table 17 shows the MODBUS holding register addresses used for analog input accumulators. The average value of the accumulator and the total accumulated value - scaled to real world units - can be calculated with the formulas presented below. An example will follow to help clarify things, but first, some definitions. Values to be calculated are:
A T P
= Average analog input value scaled to real world units. = Total accumulated value, scaled to real world units. = The time period, in seconds, that the accumulator has been running.
Values returned when the accumulator is read are:
V N R
= Accumulator value, unscaled. = Accumulator number of samples. = Sample rate
Values that are dependent on the sensor being used are:
ML MH SL SH I
= lowest real world value measured by the sensor. = highest real world value measured by the sensor. = sensor output corresponding to ML - in Volts or mA. = sensor output corresponding to MH - in Volts or mA. = analog input range - 5 Volts or 20mA depending on the type of sensor.
The formula for calculating the average analog input value in real world units is:
025-9209
33
Page 44
MODBUS System Set Up V×I MH − ML A= − SL × + ML N × 256 SH − SL The sample rate is returned in 10ths of a second. The default sample rate is 10, or 1 sample per second. The time period (in seconds) over which the accumulation took place can be calculated as:
P = N × R ÷ 10 Once the scaled average value and time period are known, the total can be calculated by multiplying the average value by the time period. If the time units for the sensor are something other than seconds, a conversion factor will also have to be included.
T=
A×P SecondsPerSensorTimeUnits
Here is an example. We will use the same sensor that we used in our discussion of analog input configuration. It measures water flow and outputs a current of 4mA for a flow of 0 gal/min and a current of 20mA for a flow of 100 gal/min. When the accumulator is read, we get a value of 12345678, number of samples of 66666 and sample rate of 20. Therefore, we know the following: V = 12345678 N = 66666 samples R = 20 ML = 0 gal/min
MH = 100 gal/min SL = 4 mA SH = 20 mA I = 20 mA
Plugging these into the equation for the scaled average value results in the following equation.
12345678 × 20mA 100gal / min − 0gal / min A= − 4mA × + 0gal / min 65432 × 256
20mA − 4mA 6.25gal / min A = (14.74mA − 4mA ) × + 0gal / min
1mA A = 67.13gal / min The time period over which the value was accumulated is:
P = 65432 × 20 ÷ 10 P = 130864Sec Finally, the total scaled accumulated value is:
34
025-9209
Page 45
MODBUS System Set Up T=
67.13gal / min × 130864Sec 60Sec / min T = 146415gal
Table 18 shows the MODBUS holding register addresses used for digital input counters. Table 18. Digital Input Counter Holding Register Addresses Counter
Value
Period
Counter
Value
Period
1
42011 – 42013
42014 - 42016
9
42091 - 42093
42094 – 42096
2
42021 – 42023
42024 - 42026
10
42101 - 42103
42104 – 42106
3
42031 – 42033
42034 - 42036
11
42111 - 42113
42114 – 42116
4
42041 – 42043
42044 - 42046
12
42121 - 42123
42124 – 42126
5
42051 – 42053
42054 - 42056
13
42131 - 42133
42134 – 42136
6
42061 – 42063
42064 - 42066
14
42141 - 42143
42144 – 42146
7
42071 – 42073
42074 - 42076
15
42151 - 42153
42154 – 42166
8
42081 – 42083
42084 - 42086
16
42161 - 42163
42164 – 42166
The counter value, as mentioned previously, is a count of the number of times the corresponding digital input has activated. This can be converted to engineering units simply by multiplying the count by a conversion factor. For example, if a flow sensor outputs one pulse for every 100 gallons of flow through a pipe. The count can be multiplied by 100 to get the total flow in gallons. The counter period is returned in 10ths of a second, so the period in seconds is: Counter period in seconds = Period ÷10
025-9209
35
Page 46
MODBUS System Set Up SOFTWARE PRODUCTS FOR THE MODBUS PROTOCOL The following list contains some of the software packages known to work with the Model 1700 Controller MODBUS option. Please note that Zetron does not sell or support these packages. For sales and support, please contact the manufacturer directly. FIX
Lookout
Intellution One Edgewater Drive Norwood, MA 02062
National Instruments Corporation 11500 North Mopac Expressway Austin, TX 78759
Tel: 781-769-8878 Fax: 781-769-1990 www.intellution.com
Tel: 512-794-0100 Fax: 512-683-8411 www.NI.com/lookout
Genesis
RealFlex
Iconics 100 Foxborough Boulevard Foxborough, MA 02035
RealFlex Systems Inc. 12000 Aerospace Avenue, Suite 300 Houston, TX 77034
Tel: 508-543-8600 Fax: 508-543-1503 www.iconics.com
Tel: 281-922-4357 Fax: 281-922-5109 www.realflex.com
InTouch Wonderware 100 Technology Drive Irvine, CA 92618 Tel: 949-727-3200 Fax: 949-727-3270 www.wonderware.com
36
025-9209