Page 47

SET UP AND INSTALLATION

INSTALLATION The Model 1708/1716 may be wall-mounted or mounted within a standard industrial enclosure. See the Model 1700 series enclosure outline (024-0057, page 52) and instructions (024-0056, page 53) for details on mounting the unit. Power Connection The power connection is made on the same connector as the radio connections. The RTU operates from 10.5-16 Vdc. Since it requires less than 150 mA, the radio power supply (if it provides 10.5-16 Vdc) is often used to power the RTU. A 12-volt sealed lead acid battery (Gel Cell) can be used with a 12-volt power supply to power the radio and RTU and to provide back-up operating power in case of a main power failure. System Grounding To prevent static discharge from affecting the system, the chassis ground must be connected to the earth ground. See the instructions (024-0056) on page 53 for the location of the chassis ground post provided.

CAUTION The chassis ground must be connected to the earth ground using the field wiring.

025-9209

37

Page 48

Setup and Installation Radio Connection The Radio Connector P3 on the RTU requires a minimum of six connections to interface with the radio. The shaded rows in Table 19 indicate that those connections are optional. Table 19. RTU Radio Connector (P3) Pinout Pin #

Connection

Schematic Label

1

Power

+12Vdc

2

Ground

GND

3

Push to Talk

PTT OUT

4

Push to Talk Common

PTT COM

5

N/A

6

Carrier Detect

7

Ground

COR GND iii

8

Transmit Request

TXREQ

9

Transmit Audio

TXAUD

10

Receive Audio

RXAUD

Step 1. Cable Connection You should find a small clear plastic bag containing a plastic 10-pin connector and 10 metal crimp pins. This connector mates with the Radio Connector P3 on the RTU. Construct a cable using this connector to provide an interface to the radio that provides the six connections listed above. Step 2. Carrier Detect and Push to Talk Settings Verify correct jumper settings for Carrier Detect and Push To Talk (PTT) based on the radio you are using. Carrier Detect JP1

A = 10 kΩ pull-down to ground on Carrier Detect input B = 10 kΩ pull-up to +12 Vdc on Carrier Detect input

If your radio provides a logic change of 0-5 Vdc when channel is busy, install JP1 in the A position and set the Carrier detect level as high in the RTU.

iii

Transmit Request, This line will allow up to 15 RTUs to connect to a single Radio Transceiver. Transmit Request prevents multiple units from transmitting simultaneously. To use, just connect a single wire to this pin between all the RTUs on the same Radio Transceiver. The RTU with the lowest ID will have priority in using the Radio.

38

025-9209

Page 49

Setup and Installation If your radio provides a logic change of 5-0 Vdc when channel is busy, install JP1 in the A position and leave the RTU setting for Carrier detect as the factory default setting of low. If your radio provides a relay contact closure to ground or open collector output, install JP1 in the B position and leave the RTU setting for Carrier detect as the factory default setting of low. You may wish to refer to “Channel Busy Detect” (on page 11) which discusses the carrier detect setting. There is a software controlled LED that will be lit when carrier is detected (based on what was set during configuration). PTT JP3

A = PTT completes the connection between P3 Pin 3 and Pin 4. B = PTT provides a ground on P3 Pin 3. (Pin 4 not used)

JP4

IN = PTT provides a +5 Vdc pull-up on P3 Pin 3 when not engaged. OUT = PTT goes to an open circuit on P3 Pin 3 when not engaged.

Step 3. Transmit and Receive Audio Adjustment Connect two RTUs to their radios and power supply, and turn power on. There are two jumpers located on the PCB next to the large square IC. These jumpers are labeled Test A and Test B. With power on, putting a jumper on Test A and/or Test B will cause the unit to enable Push to Talk and send the tones listed in Table 20. Table 20. RTU Audio Adjustment Test Tones Test A

Test B

Tone out out in in out in out in

None 1200 Hz 1800 Hz Alternating 1200 and 1800 Hz

In RTU #1, put test A and test B jumpers in place. This will cause the radio to key up and transmit an alternating 1200 Hz and 1800 Hz tone. On RTU #1, adjust the TX AUD pot to provide an audio output level that meets the radio manufacturer’s specification. Look at TP1 on RTU #2 with an oscilloscope or voltmeter with an AC setting. Use any ground point, such as the metal enclosure, as a reference. Adjust the RX AUD pot and JP7 on RTU #2 until TP1 measures 1 Vpp. JP7

025-9209

A = Low 1x gain on Receive Audio B = High 10x gain on Receive Audio

39

Page 50

Setup and Installation TP1 (Audio in) Set to 1V P-P using RXAUD pot. Repeat Step 3 but for transmit audio on RTU #2 and receive audio on RTU #1.

CAUTION Remove the jumpers when finished testing. Do not to leave the radios transmitting continuously as this can harm some radios. MODEL 1708 JUMPERS AND I/O The jumper and I/O connector information in this subsection applies to the Model 1708 (Part No. 901-9260). For similar information applying to the 1716, see page 42. Model 1708 Jumper Settings Jumper

40

Name/Signal

Description

JP1

Carrier Detect

A = 47kΩ pull down to ground B = 47kΩ pull-up to +12 Vdc

JP2

Serial Port Power

Connects +12 Vdc (fused) to J2 Pin 6 of RS-232 Connector (DB9)

JP3

Push-To-Talk

A = PTT completes the connection between P3 Pin 3 and Pin 4. B = PTT provides a ground indication on P3 Pin 3.

JP4

Push-To-Talk

IN = Push to Talk provides a +5 Vdc pull up on release. OUT = Push to Talk goes to open upon release.

JP5

Test A

1800 Hz Test Tone, See Table 20 for instructions

JP6

Test B

1200 Hz Test Tone, See Table 20 for instructions

JP7

Receive Audio Gain

A = Low 1x gain on Receive Audio B = High 10x gain on Receive Audio

JP8

External Audio

A = External Audio Source Input B = No External Audio

JP9

Transmit Audio

A = 50 Ω impedance B = 600 Ω impedance

JP10

Carrier Detect Adjust

A = Adjustable Carrier Detect threshold, 0 to 10 Vdc B = 0-0.7 Vdc Logic low, 3.5-5.0 Vdc Logic high

JP11

Analog Input #1

Adds 249 Ω load resistor

JP12

Analog Input #2

Adds 249 Ω load resistor

JP13

Analog Input #3

Adds 249 Ω load resistor

JP14

Analog Input #4

Adds 249 Ω load resistor

JP19

+5 Vdc Output

IN = +5 Vdc enabled on J1 pin 16 OUT = +5 Vdc disconnected on J1 pin 16

025-9209

Page 51

Setup and Installation Model 1708 I/O Connections J2 DB9-S(9-pin RS-232 Port) Pin #

Connection

1

N/C

2

N/C

3

Transmit from RTU (TXD)

4

Receive from external device (RXD)

5

Ground

6

+12Vdc (fused) - JP2 enable jumper

7

N/C

8

N/C

9

DTR

J1 Pin #

Connection

Pin #

Connection

1

Ground

10

Ground

2

Digital Input #1

11

Analog Input #1

3

Digital Input #2

12

Analog Input #2

4

Digital Input #3

13

Analog Input #3

5

Digital Input #4

14

Analog Input #4

6

Digital Input #5

15

External Audio In

7

Digital Input #6

16

+5 Vdc (regulated) - JP19 enable jumper

8

Digital Input #7

17

Ground

9

Digital Input #8

18

+12 Vdc (fused)

J4 Pin #

Connection

1

Ground

2

Digital Output #1

3

Digital Output #2

4

Digital Output #3

5

Digital Output #4

6

Digital Output #5

7

Digital Output #6

8

Digital Output #7

9

Digital Output #8

025-9209

41

Page 52

Setup and Installation MODEL 1716 JUMPERS AND I/O The jumper and I/O connector information in this subsection applies to the Model 1716 (Part No. 901-9261). For similar information applying to the 1708, see page 40. Model 1716 Jumper Settings Jumper

42

Name/Signal

Description

JP1

Carrier Detect

A = 47kΩ pull-down to ground B = 47kΩ pull-up to +12 Vdc

JP2

Serial Port Power

Connects +12 VDC (fused) to J2 Pin 6 of RS-232 Connector (DB9)

JP3

Push-To-Talk

A = PTT completes the connection between P3 Pin 3 and Pin 4. B = PTT provides a ground indication on P3 Pin 3.

JP4

Push-To-Talk

IN = Push to Talk provides a +5 Vdc pull up on release. OUT = Push to Talk goes to open upon release.

JP5

Test A

1800 Hz Test Tone, See Table 20 for instructions

JP6

Test B

1200 Hz Test Tone, See Table 20 for instructions

JP7

Receive Audio Gain

A = Low 1x gain on Receive Audio B = High 10x gain on Receive Audio

JP8

External Audio

A = External Audio Source Input B = No External Audio

JP9

Transmit Audio

IN = 50 Ω impedance OUT = 600 Ω impedance

JP10

Carrier Detect Adjust

A = Adjustable Carrier Detect threshold, 0 to 18 Vdc B = 0-0.7 Vdc Logic low, 3.5-5.0 Vdc Logic high

JP11

Analog Input #1

Adds 249 Ω load resistor

JP12

Analog Input #2

Adds 249 Ω load resistor

JP13

Analog Input #3

Adds 249 Ω load resistor

JP14

Analog Input #4

Adds 249 Ω load resistor

JP15

Analog Input #5

Adds 249 Ω load resistor

JP16

Analog Input #6

Adds 249 Ω load resistor

JP17

Analog Input #7

Adds 249 Ω load resistor

JP18

Analog Input #8

Adds 249 Ω load resistor

JP19

+5 Vdc Output

IN = +5 Vdc enabled on J1 pin 16 OUT = +5 Vdc disconnected on J1 pin 16

JP21 to JP37

Optional I/O board configuration jumpers

See “50-PIN INDUSTRIAL I/O BOARD CONNECTOR” on page 45 for more information.

025-9209

Page 53

Setup and Installation Model 1716 I/O CONNECTIONS The I/O connector information in this subsection applies ONLY to the Model 1716 (Part No. 901-9261). For similar information applying to the 1708, see page 40. J2 DB9-S(9-pin RS-232 Port) Pin #

Connection

1

N/C

2

N/C

3

Transmit from RTU (TXD)

4

Receive from external device (RXD)

5

Ground

6

+12 Vdc (fused) - JP2 enable jumper

7

N/C

8

N/C

9

DTR (Data Terminal Ready)

J1 Pin #

Connection

Pin #

Connection

1

Ground

10

Ground

2

Analog Input #1

11

Analog Output #1

3

Analog Input #2

12

Analog Output #2

4

Analog Input #3

13

Analog Output #3

5

Analog Input #4

14

Analog Output #4

6

Analog Input #5

15

External Audio In

7

Analog Input #6

16

+5 Vdc (regulated) - JP19 enable jumper

8

Analog Input #7

17

Ground

9

Analog Input #8

18

+12 Vdc (fused)

J4 Pin #

Connection

Pin #

Connection

1

Ground

10

Ground

2

Digital Input #1

11

Digital Input #9

3

Digital Input #2

12

Digital Input #10

4

Digital Input #3

13

Digital Input #11

5

Digital Input #4

14

Digital Input #12

6

Digital Input #5

15

Digital Input #13

7

Digital Input #6

16

Digital Input #14

8

Digital Input #7

17

Digital Input #15

9

Digital Input #8

18

Digital Input #16

025-9209

43

Page 54

Setup and Installation J5 Pin #

Connection

Pin #

Connection

1

Ground

10

Ground

2

Digital Output #1

11

Digital Output #9

3

Digital Output #2

12

Digital Output #10

4

Digital Output #3

13

Digital Output #11

5

Digital Output #4

14

Digital Output #12

6

Digital Output #5

15

Digital Output #13

7

Digital Output #6

16

Digital Output #14

8

Digital Output #7

17

Digital Output #15

9

Digital Output #8

18

Digital Output #16

CONNECTION OF LOCAL RTU TO MODEL 1700 CONTROLLER When a local RTU (Model 1708 or Model 1716) is connected to the Model 1700, the sense of the RX and TX lines are swapped. The COR, and TxREQ remain the same. The local RTU does not use the radio but uses the radio interface to communicate with the Model 1700. See Figure 5. Model 1700

Radio

PTT

PTT

TX

TX

RX

RX

TxREQ COR

COR

Model 1708 PTT

N/C

TX RX TxREQ COR

Figure 5. Local RTU Connections

44

025-9209

Page 55

Setup and Installation 50-PIN INDUSTRIAL I/O BOARD CONNECTOR The 50-Pin Industrial I/O Board Connector P6 is designed for connection to many industrial I/O and signal conditioning boards available from a variety of manufacturers. This allows connection to these boards using a standard 50-conductor ribbon cable. The jumpers JP21 to JP36 allow the modular I/O connections to be configured as inputs or outputs. Digital Output #1 I/O Board Connection Digital Input #1

1 2 3

Figure 6. Functional Pinout for Model 1716 Jumpers 21 to 37 A jumper connecting Pin #1 and Pin #2 will connect digital output #1 to module 1 of the I/O board. A jumper connecting Pin #2 and Pin #3 will connect digital input #1 to module 1 of the I/O board. This connector, P6, supports 4, 8, and 16 module optically isolated I/O boards. The 50-pin connectors provide common ground on the even numbered pins, +5 Vdc on pin 49 and channels 1 to 24 on the odd numbered pins starting with pin 47 and counting backwards from there. A 24 I/O board is also supported, but channels 17-24 are not equipped with the jumper in the diagram above. For channels 17-24, a single stake pin is exposed for each channel on the Control Link and must be connected to the appropriate input or output. A total of 16 inputs and 16 outputs are available to be routed to a standard I/O board by means of jumpers or wire wrap and a 50-pin ribbon cable. The 16 I/O points are also available on the J4 and J5 screw terminal block.

Note Pin 1 and Pin 49 may be connected by a jumper on the I/O board. Remove this jumper if you are installing a 24-module I/O board.

025-9209

45

Page 56

Setup and Installation P6 Pin #

46

Connection

Pin #

Connection

1

Module I/O 24

26

Ground

2

Ground

27

Module I/O 11

3

Module I/O 23

28

Ground

4

Ground

29

Module I/O 10

5

Module I/O 22

30

Ground

6

Ground

31

Module I/O 9

7

Module I/O 21

32

Ground

8

Ground

33

Module I/O 8

9

Module I/O 20

34

Ground

10

Ground

35

Module I/O 7

11

Module I/O 19

36

Ground

12

Ground

37

Module I/O 6

13

Module I/O 18

38

Ground

14

Ground

39

Module I/O 5

15

Module I/O 17

40

Ground

16

Ground

41

Module I/O 4

17

Module I/O 16

42

Ground

18

Ground

43

Module I/O 3

19

Module I/O 15

44

Ground

20

Ground

45

Module I/O 2

21

Module I/O 14

46

Ground

22

Ground

47

Module I/O 1

23

Module I/O 13

48

Ground

24

Ground

49

+ 5 Volts DC

25

Module I/O 12

50

Ground

025-9209