The text of a manual · part 7 of 12
Models 1708 and 1716 Remote Terminal Units Installation and Operation Manual: SET UP AND INSTALLATION
Pages 47 to 56 of 86, from Models 1708 and 1716 Remote Terminal Units Installation and Operation Manual
The original document is the PDF (5.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Zetron 1708
Page 47
SET UP AND INSTALLATION
INSTALLATION The Model 1708/1716 may be wall-mounted or mounted within a standard industrial enclosure. See the Model 1700 series enclosure outline (024-0057, page 52) and instructions (024-0056, page 53) for details on mounting the unit. Power Connection The power connection is made on the same connector as the radio connections. The RTU operates from 10.5-16 Vdc. Since it requires less than 150 mA, the radio power supply (if it provides 10.5-16 Vdc) is often used to power the RTU. A 12-volt sealed lead acid battery (Gel Cell) can be used with a 12-volt power supply to power the radio and RTU and to provide back-up operating power in case of a main power failure. System Grounding To prevent static discharge from affecting the system, the chassis ground must be connected to the earth ground. See the instructions (024-0056) on page 53 for the location of the chassis ground post provided.
CAUTION The chassis ground must be connected to the earth ground using the field wiring.
025-9209
37
Page 48
Setup and Installation Radio Connection The Radio Connector P3 on the RTU requires a minimum of six connections to interface with the radio. The shaded rows in Table 19 indicate that those connections are optional. Table 19. RTU Radio Connector (P3) Pinout Pin #
Connection
Schematic Label
1
Power
+12Vdc
2
Ground
GND
3
Push to Talk
PTT OUT
4
Push to Talk Common
PTT COM
5
N/A
6
Carrier Detect
7
Ground
COR GND iii
8
Transmit Request
TXREQ
9
Transmit Audio
TXAUD
10
Receive Audio
RXAUD
Step 1. Cable Connection You should find a small clear plastic bag containing a plastic 10-pin connector and 10 metal crimp pins. This connector mates with the Radio Connector P3 on the RTU. Construct a cable using this connector to provide an interface to the radio that provides the six connections listed above. Step 2. Carrier Detect and Push to Talk Settings Verify correct jumper settings for Carrier Detect and Push To Talk (PTT) based on the radio you are using. Carrier Detect JP1
A = 10 kΩ pull-down to ground on Carrier Detect input B = 10 kΩ pull-up to +12 Vdc on Carrier Detect input
If your radio provides a logic change of 0-5 Vdc when channel is busy, install JP1 in the A position and set the Carrier detect level as high in the RTU.
iii
Transmit Request, This line will allow up to 15 RTUs to connect to a single Radio Transceiver. Transmit Request prevents multiple units from transmitting simultaneously. To use, just connect a single wire to this pin between all the RTUs on the same Radio Transceiver. The RTU with the lowest ID will have priority in using the Radio.
38
025-9209
Page 49
Setup and Installation If your radio provides a logic change of 5-0 Vdc when channel is busy, install JP1 in the A position and leave the RTU setting for Carrier detect as the factory default setting of low. If your radio provides a relay contact closure to ground or open collector output, install JP1 in the B position and leave the RTU setting for Carrier detect as the factory default setting of low. You may wish to refer to “Channel Busy Detect” (on page 11) which discusses the carrier detect setting. There is a software controlled LED that will be lit when carrier is detected (based on what was set during configuration). PTT JP3
A = PTT completes the connection between P3 Pin 3 and Pin 4. B = PTT provides a ground on P3 Pin 3. (Pin 4 not used)
JP4
IN = PTT provides a +5 Vdc pull-up on P3 Pin 3 when not engaged. OUT = PTT goes to an open circuit on P3 Pin 3 when not engaged.
Step 3. Transmit and Receive Audio Adjustment Connect two RTUs to their radios and power supply, and turn power on. There are two jumpers located on the PCB next to the large square IC. These jumpers are labeled Test A and Test B. With power on, putting a jumper on Test A and/or Test B will cause the unit to enable Push to Talk and send the tones listed in Table 20. Table 20. RTU Audio Adjustment Test Tones Test A
Test B
Tone out out in in out in out in
None 1200 Hz 1800 Hz Alternating 1200 and 1800 Hz
In RTU #1, put test A and test B jumpers in place. This will cause the radio to key up and transmit an alternating 1200 Hz and 1800 Hz tone. On RTU #1, adjust the TX AUD pot to provide an audio output level that meets the radio manufacturer’s specification. Look at TP1 on RTU #2 with an oscilloscope or voltmeter with an AC setting. Use any ground point, such as the metal enclosure, as a reference. Adjust the RX AUD pot and JP7 on RTU #2 until TP1 measures 1 Vpp. JP7
025-9209
A = Low 1x gain on Receive Audio B = High 10x gain on Receive Audio
39
Page 50
Setup and Installation TP1 (Audio in) Set to 1V P-P using RXAUD pot. Repeat Step 3 but for transmit audio on RTU #2 and receive audio on RTU #1.
CAUTION Remove the jumpers when finished testing. Do not to leave the radios transmitting continuously as this can harm some radios. MODEL 1708 JUMPERS AND I/O The jumper and I/O connector information in this subsection applies to the Model 1708 (Part No. 901-9260). For similar information applying to the 1716, see page 42. Model 1708 Jumper Settings Jumper
40
Name/Signal
Description
JP1
Carrier Detect
A = 47kΩ pull down to ground B = 47kΩ pull-up to +12 Vdc
JP2
Serial Port Power
Connects +12 Vdc (fused) to J2 Pin 6 of RS-232 Connector (DB9)
JP3
Push-To-Talk
A = PTT completes the connection between P3 Pin 3 and Pin 4. B = PTT provides a ground indication on P3 Pin 3.
JP4
Push-To-Talk
IN = Push to Talk provides a +5 Vdc pull up on release. OUT = Push to Talk goes to open upon release.
JP5
Test A
1800 Hz Test Tone, See Table 20 for instructions
JP6
Test B
1200 Hz Test Tone, See Table 20 for instructions
JP7
Receive Audio Gain
A = Low 1x gain on Receive Audio B = High 10x gain on Receive Audio
JP8
External Audio
A = External Audio Source Input B = No External Audio
JP9
Transmit Audio
A = 50 Ω impedance B = 600 Ω impedance
JP10
Carrier Detect Adjust
A = Adjustable Carrier Detect threshold, 0 to 10 Vdc B = 0-0.7 Vdc Logic low, 3.5-5.0 Vdc Logic high
JP11
Analog Input #1
Adds 249 Ω load resistor
JP12
Analog Input #2
Adds 249 Ω load resistor
JP13
Analog Input #3
Adds 249 Ω load resistor
JP14
Analog Input #4
Adds 249 Ω load resistor
JP19
+5 Vdc Output
IN = +5 Vdc enabled on J1 pin 16 OUT = +5 Vdc disconnected on J1 pin 16
025-9209
Page 51
Setup and Installation Model 1708 I/O Connections J2 DB9-S(9-pin RS-232 Port) Pin #
Connection
1
N/C
2
N/C
3
Transmit from RTU (TXD)
4
Receive from external device (RXD)
5
Ground
6
+12Vdc (fused) - JP2 enable jumper
7
N/C
8
N/C
9
DTR
J1 Pin #
Connection
Pin #
Connection
1
Ground
10
Ground
2
Digital Input #1
11
Analog Input #1
3
Digital Input #2
12
Analog Input #2
4
Digital Input #3
13
Analog Input #3
5
Digital Input #4
14
Analog Input #4
6
Digital Input #5
15
External Audio In
7
Digital Input #6
16
+5 Vdc (regulated) - JP19 enable jumper
8
Digital Input #7
17
Ground
9
Digital Input #8
18
+12 Vdc (fused)
J4 Pin #
Connection
1
Ground
2
Digital Output #1
3
Digital Output #2
4
Digital Output #3
5
Digital Output #4
6
Digital Output #5
7
Digital Output #6
8
Digital Output #7
9
Digital Output #8
025-9209
41
Page 52
Setup and Installation MODEL 1716 JUMPERS AND I/O The jumper and I/O connector information in this subsection applies to the Model 1716 (Part No. 901-9261). For similar information applying to the 1708, see page 40. Model 1716 Jumper Settings Jumper
42
Name/Signal
Description
JP1
Carrier Detect
A = 47kΩ pull-down to ground B = 47kΩ pull-up to +12 Vdc
JP2
Serial Port Power
Connects +12 VDC (fused) to J2 Pin 6 of RS-232 Connector (DB9)
JP3
Push-To-Talk
A = PTT completes the connection between P3 Pin 3 and Pin 4. B = PTT provides a ground indication on P3 Pin 3.
JP4
Push-To-Talk
IN = Push to Talk provides a +5 Vdc pull up on release. OUT = Push to Talk goes to open upon release.
JP5
Test A
1800 Hz Test Tone, See Table 20 for instructions
JP6
Test B
1200 Hz Test Tone, See Table 20 for instructions
JP7
Receive Audio Gain
A = Low 1x gain on Receive Audio B = High 10x gain on Receive Audio
JP8
External Audio
A = External Audio Source Input B = No External Audio
JP9
Transmit Audio
IN = 50 Ω impedance OUT = 600 Ω impedance
JP10
Carrier Detect Adjust
A = Adjustable Carrier Detect threshold, 0 to 18 Vdc B = 0-0.7 Vdc Logic low, 3.5-5.0 Vdc Logic high
JP11
Analog Input #1
Adds 249 Ω load resistor
JP12
Analog Input #2
Adds 249 Ω load resistor
JP13
Analog Input #3
Adds 249 Ω load resistor
JP14
Analog Input #4
Adds 249 Ω load resistor
JP15
Analog Input #5
Adds 249 Ω load resistor
JP16
Analog Input #6
Adds 249 Ω load resistor
JP17
Analog Input #7
Adds 249 Ω load resistor
JP18
Analog Input #8
Adds 249 Ω load resistor
JP19
+5 Vdc Output
IN = +5 Vdc enabled on J1 pin 16 OUT = +5 Vdc disconnected on J1 pin 16
JP21 to JP37
Optional I/O board configuration jumpers
See “50-PIN INDUSTRIAL I/O BOARD CONNECTOR” on page 45 for more information.
025-9209
Page 53
Setup and Installation Model 1716 I/O CONNECTIONS The I/O connector information in this subsection applies ONLY to the Model 1716 (Part No. 901-9261). For similar information applying to the 1708, see page 40. J2 DB9-S(9-pin RS-232 Port) Pin #
Connection
1
N/C
2
N/C
3
Transmit from RTU (TXD)
4
Receive from external device (RXD)
5
Ground
6
+12 Vdc (fused) - JP2 enable jumper
7
N/C
8
N/C
9
DTR (Data Terminal Ready)
J1 Pin #
Connection
Pin #
Connection
1
Ground
10
Ground
2
Analog Input #1
11
Analog Output #1
3
Analog Input #2
12
Analog Output #2
4
Analog Input #3
13
Analog Output #3
5
Analog Input #4
14
Analog Output #4
6
Analog Input #5
15
External Audio In
7
Analog Input #6
16
+5 Vdc (regulated) - JP19 enable jumper
8
Analog Input #7
17
Ground
9
Analog Input #8
18
+12 Vdc (fused)
J4 Pin #
Connection
Pin #
Connection
1
Ground
10
Ground
2
Digital Input #1
11
Digital Input #9
3
Digital Input #2
12
Digital Input #10
4
Digital Input #3
13
Digital Input #11
5
Digital Input #4
14
Digital Input #12
6
Digital Input #5
15
Digital Input #13
7
Digital Input #6
16
Digital Input #14
8
Digital Input #7
17
Digital Input #15
9
Digital Input #8
18
Digital Input #16
025-9209
43
Page 54
Setup and Installation J5 Pin #
Connection
Pin #
Connection
1
Ground
10
Ground
2
Digital Output #1
11
Digital Output #9
3
Digital Output #2
12
Digital Output #10
4
Digital Output #3
13
Digital Output #11
5
Digital Output #4
14
Digital Output #12
6
Digital Output #5
15
Digital Output #13
7
Digital Output #6
16
Digital Output #14
8
Digital Output #7
17
Digital Output #15
9
Digital Output #8
18
Digital Output #16
CONNECTION OF LOCAL RTU TO MODEL 1700 CONTROLLER When a local RTU (Model 1708 or Model 1716) is connected to the Model 1700, the sense of the RX and TX lines are swapped. The COR, and TxREQ remain the same. The local RTU does not use the radio but uses the radio interface to communicate with the Model 1700. See Figure 5. Model 1700
Radio
PTT
PTT
TX
TX
RX
RX
TxREQ COR
COR
Model 1708 PTT
N/C
TX RX TxREQ COR
Figure 5. Local RTU Connections
44
025-9209
Page 55
Setup and Installation 50-PIN INDUSTRIAL I/O BOARD CONNECTOR The 50-Pin Industrial I/O Board Connector P6 is designed for connection to many industrial I/O and signal conditioning boards available from a variety of manufacturers. This allows connection to these boards using a standard 50-conductor ribbon cable. The jumpers JP21 to JP36 allow the modular I/O connections to be configured as inputs or outputs. Digital Output #1 I/O Board Connection Digital Input #1
1 2 3
Figure 6. Functional Pinout for Model 1716 Jumpers 21 to 37 A jumper connecting Pin #1 and Pin #2 will connect digital output #1 to module 1 of the I/O board. A jumper connecting Pin #2 and Pin #3 will connect digital input #1 to module 1 of the I/O board. This connector, P6, supports 4, 8, and 16 module optically isolated I/O boards. The 50-pin connectors provide common ground on the even numbered pins, +5 Vdc on pin 49 and channels 1 to 24 on the odd numbered pins starting with pin 47 and counting backwards from there. A 24 I/O board is also supported, but channels 17-24 are not equipped with the jumper in the diagram above. For channels 17-24, a single stake pin is exposed for each channel on the Control Link and must be connected to the appropriate input or output. A total of 16 inputs and 16 outputs are available to be routed to a standard I/O board by means of jumpers or wire wrap and a 50-pin ribbon cable. The 16 I/O points are also available on the J4 and J5 screw terminal block.
Note Pin 1 and Pin 49 may be connected by a jumper on the I/O board. Remove this jumper if you are installing a 24-module I/O board.
025-9209
45
Page 56
Setup and Installation P6 Pin #
46
Connection
Pin #
Connection
1
Module I/O 24
26
Ground
2
Ground
27
Module I/O 11
3
Module I/O 23
28
Ground
4
Ground
29
Module I/O 10
5
Module I/O 22
30
Ground
6
Ground
31
Module I/O 9
7
Module I/O 21
32
Ground
8
Ground
33
Module I/O 8
9
Module I/O 20
34
Ground
10
Ground
35
Module I/O 7
11
Module I/O 19
36
Ground
12
Ground
37
Module I/O 6
13
Module I/O 18
38
Ground
14
Ground
39
Module I/O 5
15
Module I/O 17
40
Ground
16
Ground
41
Module I/O 4
17
Module I/O 16
42
Ground
18
Ground
43
Module I/O 3
19
Module I/O 15
44
Ground
20
Ground
45
Module I/O 2
21
Module I/O 14
46
Ground
22
Ground
47
Module I/O 1
23
Module I/O 13
48
Ground
24
Ground
49
+ 5 Volts DC
25
Module I/O 12
50
Ground
025-9209