Models 1708 and 1716 Remote Terminal Units Installation and Operation Manual, pages 67 to 74

Pages 67 to 74 of 86: APPENDIX A; APPENDIX B

The original document is the PDF (5.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Zetron 1708

Page 67

APPENDIX A COMMUNICATING OVER TWO-WIRE BALANCED LINE (600Ω) Zetron’s Model 1700, 1708, and 1716 RTUs all have similar data transmission circuitry. That circuitry is designed to operate with most makes and models of two-way radios. This applications note is designed to assist in connecting the Model 17xx units over wireline for data transmission over long distances. RTU P3 1

Jumper Positions

+12 VDC

JP3: Pos B (PTT to GND) JP9: Pos B (600 ohm TX)

GND PTT OUT PTT COM

R1

COR GND

Impedance Matching Transformer T1

TXREQ TXAUD RXAUD 10

R2

600

600

Dedicated Leased Line

External Devices: R1=560, R2=10K, T1=(600 ohm)

Figure 8. Leased Line Interface Circuit Notes Loss of signal will result from lack of proper grounding. Transformer will have to be a balanced 600Ω transformer for this to work properly, otherwise there will be additional signal loss. Transformers can be purchased through Zetron, part # 305-0022, or through a vendor. Resistor values should be observed. Leased Lines This application is for a dedicated leased line. Normal dial-up lines will not work. RTUs do not have the capability of dialing and waiting for a response. In this situation, when the unit reports a change of state, it will simply send the information.

025-9209

57

Page 68

Appendix A Simple copper-pair wire will require line drivers over long distances since attenuation is high. Leased lines from the phone company should not require external amplification devices. Collisions There is no data flow control provided in the transformer coupling. If a busy indication is available, it can be connected to the COR input P3-6 of the unit. If no busy indication is available, make sure the COR input is left at factory defaults, channel busy on logic low, and that jumper JP10 is in the “B” position. This will enable the units to transmit at all times.

58

025-9209

Page 69

APPENDIX B MODEL 1730/1732 COMMUNICATIONS AND I/O TEST PROGRAM The Model 1730 - Model 1732 Communications And I/O Test program is a troubleshooting tool for the Model 1730 Controller and Model 1732, Model 1716 and Model 1708 RTUs. With it you can:

• • • • verify or debug radio communications between the M1730 Controller and RTUs verify proper wiring of Controller and RTU i/o points to equipment verify that i/o points on the Controller and RTUs are configured properly monitor the operation of an RTUBASIC program running in a M1732 RTU by watching changes in the RTUs inputs and outputs

STARTING THE PROGRAM The setup process adds the program “M1730-M1732 Comm And I/O Test” to your Windows Start menu in the “Programs\Zetron\M1730-M1732 Comm And I/O Test” group. Select this menu item to start the test program. If the setup process created a shortcut on your desktop, you may also double click on this icon to start the program. The main window is shown in Figure 9. To use the test program, you must connect one of your PC’s RS232 ports to connector J2 on the Model 1730 controller or Model 1732 RTU. Use the same cable that you use to configure the Model 1730 or Model 1732.

Figure 9. Communications and I/O Test Main Window When connected to the Model 1730 controller, you will be able to test not only the controller but any RTU that communicates with that controller over the radio as well. If the Model 025-9209

59

Page 70

Appendix B 1730 has the MODBUS option, it must be configured to use the ULTRAc protocol so that it will pass all messages received from RTUs through to the Communications And I/O Test program. When connected to the Model 1732 RTU, you will be able to test only the I/O points on that particular RTU. All functions of the program are accessed through the menus. The center of the main window is where messages received from the controller and/or RTUs are displayed. The bottom of the window shows the currently selected device type and address, and the communications port settings. SETTING OPTIONS Selecting Options from the main menu brings up the dialog shown in Figure 10. In the Address field, put the address of the Controller or RTU that you want to test. The Device field should specify the type of device you are testing. The choices include: 1730, 1732, 1708, and 1716.

Figure 10. The Options Dialog Box The Comm port, Baud rate and Format fields select and configure the RS232 communications port used to communicate with the device under test. You must select a port that is not in use by any other program. The Acknowledge exceptions field should be checked if you want the test program to acknowledge exceptions reports received from the Model 1730 Controller and/or RTUs. If not acknowledged, the sender of the exception will keep sending the report, and eventually go into its communications fail state. The Show exceptions field controls whether or not exception reports are shown on the screen. When this box is checked, exceptions reports received from any device will be displayed.

60

025-9209

Page 71

Appendix B THE POLL MENU The Poll selection in the main menu is used to poll the Controller or RTU for current I/O status, logic register values (Model 1732 RTU only) or hardware information.

Figure 11. The Poll Menu For menu items that end in an ellipsis (...), additional information such as the module or register number must be entered the before poll is sent. Examples of the dialogs for this are shown in Figure 12.

Figure 12. Entering Additional Polling Information

025-9209

61

Page 72

Appendix B THE SET MENU The Set option in the main menu is used to control outputs and change logic registers.

Figure 13. The Set Menu When one of the Set menu items is selected, a dialog box always pops up requesting additional information such as the module number, output number and output value.

Figure 14. Entering Output Control Information For setting logic registers, the register number, register type and new value are requested as shown in Figure 15.

Figure 15. Setting a Logic Register

62

025-9209

Page 73

Appendix B THE CLEAR MENU The Clear menu provides options for clearing the message window and for clearing counters, runtimes and accumulators.

Figure 16. The Clear Menu On the Model 1730 Controller and Model 1732 RTU, you can select one or more counters, runtimes or accumulators to clear at the same time. Figure 17 shows how this is done for counters.

Figure 17. Specifying Which Counters to Clear

025-9209

63

Page 74 read from a scan by OCR; it may hold reading errors

(ZETRON),

Appendix B

64 025-9209