Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeEnglishEspañolContact
Page 1 of Application Note: AdaptaScan Reader to a PLC-5 Using RS-232/ASCII Protocol with the 2760-RB Module and the 2760-SFC1 and -SFC2 Protocol Cartridge

Manual · Allen-Bradley

Application Note: AdaptaScan Reader to a PLC-5 Using RS-232/ASCII Protocol with the 2760-RB Module and the 2760-SFC1 and -SFC2 Protocol Cartridge

Manual12 pagesPDF 154 KB

Application note for connecting an Allen-Bradley AdaptaScan 2755-SN3, -SN5 or -SN8 reader to a PLC-5 over RS-232 through a 2760-RB module.

Download the PDF154 KB

Names · 5 models

The models it names

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

An Allen-Bradley application note showing how an AdaptaScan 2755-SN3, -SN5 or -SN8 bar code reader sends data to a PLC-5 by RS-232 dumb terminal protocol, through a 2760-RB interface module with a 2760-SFC1 or -SFC2 protocol cartridge. It lists the hardware, software and related publications, gives PLC-5 compatibility notes, DIP switch settings, the 2760-RB configuration menus, the AdaptaScan reader settings, a sample PLC ladder program, and the two cable diagrams.

Its parts

  1. Overview
  2. Hardware Requirements
  3. Software Requirements
  4. Related Publications
  5. PLC 5 Compatibility
  6. Configuration
  7. Sample PLC Program

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

An Allen-Bradley application note (Publication 2755-2.63, April 1996) on linking an AdaptaScan 2755-SN3, -SN5 or -SN8 bar code reader to a PLC-5 over RS-232 through a 2760-RB interface module with a 2760-SFC1 or -SFC2 protocol cartridge. It gives the DIP switch settings, 2760-RB and reader configuration, a sample PLC-5 program and the two cable diagrams. It does not describe the 2755-DS decoder.

Link
AdaptaScan reader to a PLC-5 over RS-232 dumb terminal protocol, through a 2760-RB module with a 2760-SFC1 or -SFC2 cartridge p. 1
Software needed
Bulletin 6200 PLC-5 software, terminal emulation software, 2755-ASN Windows-based offline reader software p. 2
Serial settings
9600 bits per second, 8 bits no parity, XON/XOFF and modem control disabled, RS232 p. 5
Message end
Messages end in Carriage Return and Line Feed; 2760-RB trailer length 2 (0a, 0d) p. 4, 5
Reader cable
2760-RB Port 1, 25-pin D male: Tx pin 2, Rx pin 3, GND pin 7, to the reader wiring base terminal strip Rx, Tx, GND p. 11
Module placement
2760-RB in slot 0 of the 1771 chassis next to the PLC; the reader uses Port 1 p. 3
Reader ports
RS-232, RS-485 or RS-422 with ASCII, DH-485 or DF1 protocols; Terminal chosen for this link p. 7
Config cable
Terminal to 2760-RB configuration port, 25-pin D: pins 2 and 3 crossed, GND pin 7 to pin 7 p. 11
Config terminal
9600 baud, 8 data bits, 1 stop bit, no parity, no flow control; a break sequence opens the menu p. 5
Remote I/O option
A 1771-ASB module can reach the 2760-RB over the backplane to Remote I/O p. 3
New Generation PLC-5
With a 2760-RB Series A Rev. H or above, add an Immediate Input rung before the Block Transfer Read p. 2, 10
Related manuals
2755-837 AdaptaScan installation, 2755-838 configuration software, 2760-ND001 2760-RB user manual, 2760-2.16 and 2760-2.19 cartridge manuals p. 2

What this manual walks you through

  • Setting the PLC-5, chassis and 2760-RB DIP switches p. 3
  • Configuring the 2760-RB from a terminal p. 5
  • Setting the AdaptaScan serial port and message format in the offline software p. 6, 7, 8
  • Sample PLC-5 block transfer program p. 9
  • Using a 2760-RB Rev. H or above with a New Generation PLC-5 p. 10
  • Building the configuration and reader cables p. 11

Good to know

  • Only the reader settings needed for this link are shown; symbology and trigger setup are outside the note. p. 6
  • With a New Generation PLC-5 in a local rack the PLC may miss the 2760-RB BRR bit without the extra rung. p. 10
  • The Block Transfer Read must come before the Block Transfer Write. p. 10
  • The 2760-RB configuration screens should be entered exactly as shown and then saved. p. 4

Questions this manual answers

How do I connect an AdaptaScan 2755-SN5 reader to a PLC-5?

Through a 2760-RB module in the PLC-5's 1771 rack, fitted with a 2760-SFC1 or -SFC2 cartridge, using RS-232 dumb terminal protocol on Port 1. p. 1, 3

How is the cable from a 2760-RB to an AdaptaScan reader wired?

From a 25-pin D male on 2760-RB Port 1, pin 2 Tx and pin 3 Rx go to the reader terminal strip Rx and Tx, and pin 7 to GND. p. 11

What serial settings does the 2760-RB use for an AdaptaScan reader?

9600 bits per second, 8 bits with no parity, XON/XOFF disabled, with a two-byte trailer of line feed and carriage return. p. 5

What software do I need to set up an AdaptaScan reader?

The 2755-ASN Windows-based offline program software, plus Bulletin 6200 software for the PLC-5 and terminal emulation for the 2760-RB. p. 2

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Overview1
  2. Hardware Requirements1
  3. Software Requirements2
  4. Related Publications2
  5. PLC 5 Compatibility2
  6. Configuration3
  7. Sample PLC Program9
  8. Back Cover12

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 61-6
  2. Pages 7 to 127-12

The file

Revision and size

RevisionPublication 2755-2.63, April 1996
PublisherAllen-Bradley
Pages12
PDF154 KB
TextText from the PDF itself.

The first pages · 3 of 12

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 12
Page 2
Page 2of 12
Page 3
Page 3of 12