Manual · Omega
CN-2000 Series Programmable Temperature Controllers Operator's Manual
Manual75 pagesPDF 2.2 MB
Operator's manual for the OMEGA CN-2000 series programmable temperature controllers, including the CN2001 and CN2002: wiring, tuning, setup.
Covers · 1 model
The models it covers
Summary
What is in it
Operator's manual (a scanned copy) for the OMEGA CN-2000 series programmable temperature controllers, covering the CN2001 and CN2002 models and their alarm versions. It explains unpacking, panel mounting, noise suppression and wiring of power, inputs and outputs, then operation from the keypad, alarms and timers, PID tuning and self tune, the digital communications option (RS-232, RS-422, 20 mA loop), calibration, service, remote start/stop and specifications.
Its parts
- Introduction
- Installation
- Operation
- Tuning
- Digital Communications Option
- Calibration
- Service Information
- Remote Start/Stop Option
- Specifications
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Operator's manual for the OMEGA CN-2000 Series programmable temperature controllers, covering the CN2001 and CN2002 with their input, output, alarm and communication options. It explains panel mounting, noise suppression and wiring, the display and keypad, tuning, digital communications and calibration. Its last sections give diagnostic displays, a troubleshooting table, the remote start/stop option and specifications.
- Device
- Microprocessor-based programmable controller for temperature or other process variables, ON/OFF or PID control p. 6
- Inputs
- Thermocouple, three-wire RTD, voltage or current; input codes include 4 to 20 mA and 0 to 5 VDC p. 6, 7
- Factory setting
- Thermocouple models ship set for Type J thermocouple, °F scaling; reprogrammed by changing the configuration code p. 6
- Output
- CN2001: one output, 1 A solid state relay (opto-isolated triac), PID; SSR load up to 240 V ac p. 6, 14
- Alarms
- Alarm models (-A): two independent process or deviation alarms on relays with NO and NC contacts p. 6, 19
- Display
- Multicolor vacuum fluorescent, two rows of eight alphanumeric characters p. 18
- Power
- Normally wired for 120 V ac; maximum input current 115 mA ac at 120 V ac, 50/60 Hz; terminals 6, 7 and 8 p. 13
- Communications
- Options for RS-232-C or RS-422-C (isolated or non-isolated) and an isolated 20 mA loop p. 7
- Remote start/stop
- Option D7 (terminals B and C) or D7DE (terminals D and E); dry circuit contact closed at least 100 milliseconds p. 70
- Panel cutout
- 3.620 in (92 mm) square; U-shaped bracket; 4.5 in minimum horizontal spacing on center p. 9
- Sensor wiring
- Thermocouple loop resistance up to 100 ohms; RTD extension lead resistance up to 10 ohms p. 13, 14
- Diagnostic displays
- INPUT OPEN, POWER FAILURE, RTC FAILURE, RAM FAILURE, DATA LOST PLEASE CAL p. 67, 68
- Noise kit
- OMEGA P/N 1821-101: capacitor, resistors, R-C snubber and an MOV rated up to 130 VAC at 35 joules p. 11
What this manual walks you through
- Choosing input, output, alarm and communication options by ordering code p. 6, 7
- Mounting the controller in a panel cutout p. 9, 10
- Suppressing electrical noise with snubbers and MOVs p. 10, 11, 12
- Wiring power and the thermocouple, RTD or DC input p. 13, 14
- Wiring solid state relay outputs p. 14
- Reading the display and its alarm, output and mode indicators p. 18, 19, 20
- Understanding diagnostic displays and troubleshooting control problems p. 67, 68, 69
- Wiring and operating the remote start/stop option p. 70
Good to know
- Applying 240 V ac to a unit not rated for that voltage damages the controller. p. 13
- Output options cannot be added or changed in the field. p. 14
- Allow at least five minutes of warm-up before starting operation. p. 18
- The remote analog set point option (D1) disables alarm 2 and is not available with the 2001A and 2002A. p. 7
- If RTC FAILURE or RAM FAILURE stays after switching power off and on, the controller needs service by authorized personnel. p. 68
Questions this manual answers
What sensors can the Omega CN2001 controller use?
Thermocouple, three-wire RTD, or voltage or current signals. Thermocouple models ship set for Type J and °F. p. 6
The CN2001 display shows input open. What should I check?
The thermocouple or input circuit is open; check the thermocouple and extension wire for open circuits. p. 69
What panel cutout does the CN-2000 need?
A 3.620 in (92 mm) square cutout, held by the U-shaped mounting bracket supplied with each unit. p. 9
What line power does the CN-2000 controller take?
It is normally wired for 120 V ac, drawing at most 115 mA ac at 50/60 Hz, connected to rear terminals 6, 7 and 8. p. 13