CN-2000 Series Programmable Temperature Controllers Operator's Manual, pages 1 to 10

Pages 1 to 10 of 75

The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omega CN2001

Page 1 read from a scan by OCR; it may hold reading errors

fe! rs No ° =) und Q

3

Q. a a No ° © N

Programmable Temperature Controllers

®

[CE OMEGA) Operator’s Manual

An OMEGA Technologies Company rm

Page 2 read from a scan by OCR; it may hold reading errors

(CQ OMEGA Am OMEGA Techaclogies Company: Servicing USA and Canada: Call OMEGA Toll Free

USA Canada One Omega Drive, Box 4047 976 Bergar Stamford, CT 06907-0047 Laval (Quebec) H7L 5A1 Felephone: (203) 359-1660 Telephone: (514) 85¢:-6928 FAX: (203) 359-7700 FAX (514) 856-6886 €

Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA™ Customer Service: 1-800-622-2378 / 1-800-622-BEST™ Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN™ iat viet

Servicing Europe: United Kingdom Sales and Distribution Center 25 Swannington Road, Broughton Astley, Leicestershire LE9 6TU, England Telephone: 44 (1455) 285520 FAX: 44 (1455) 283912

The OMEGA Complete Measurement and Control Handbooks & Encyclopedias

Temperature Data Acquisition Systems Pressure, Strain & Force Electric Heaters

™ Flow and Level Environmental Monitoring pH and Conductivity and Control

Call for Your FREE Handbook Request Form Today: (203) 359-RUSH

DFM1294GFE7B

Page 3 read from a scan by OCR; it may hold reading errors

CN-2000 SERIES PROGRAMMABLE TEMPERATURE CONTROLLERS SECTION PAGE SECTION 1 INTRODUCT. ION... eee eee 1 11 General Description... 2.0.02... 0000.00.00... 1 1.2 Features oe 1, - 13 Available Models -s-r5 sessop pt 17

SECTION 2 INSTALLATION......................... 3 2.1 Unpacking... 2... eee, 3 2.2 Identification... 2... 3 2.3 Mounting... 0.2... 4 2.4 Wiring... 2... 5 2.5 Noise Suppression ..............0..........00000, 5 2.6 Power Circuit Wiring ......0..00..000........000000 8 2.7 Input Circuit Wiring... 2... 8 2.7.1 Thermocouple Input ..............0....0.00.000000 8 2.7.2 RTDInput........2......0 9 2.7.3. DC Voltage and DC Current Input 2. 9 2.8 Output Circuit Wiring... 9 2.8.1 Solid State Relay, Primary and/or

Secondary Output ...........0.00000000.00000..... 9 2.8.2 Analog Output - Primary and/or

Secondary Output .......0..0.0000.0...0......... 10 2.8.3 Alarm/Timer Wiring (Option) .................-.- 11 2.9 Remote Set Point Input......................00.000, 3 2.10 Digital Communications Wiring... 0... eee. 12 SECTION 3 OPERATION........................... 13 3.1 Initial Power Up... eee eee ee. 13 3.2 Modes of Operation.............................., 13 3.3 Display Indications ...........0..0..............., 13 3.4 The Keypad... 0... 16 3.5 Alarm/Timer Options ..........................0.., 17 3.6 Operator Loop...... 2.0... 18 3.7 Stop/Start Control... 2... 19 3.8 Auto/Manual Control (Model CN2000 With

AM Option) ... 2... 2.0... e eee, 19 3.9 Remote Set Point ..........................000... 20 3.10 Digital Communications ............................ 20

TABLE OF CONTENTS

Page 4 read from a scan by OCR; it may hold reading errors

TABLE OF CONTENTS (Cont'd)

SECTION PAGE SECTION 4 TUNING ............................, 22 41 Controller Tuning for CN2000 Controllers Without

Self Tune (AT) Option... 0... 000. ee cee eee eee. 22 41.1 TUNE Loop .... 2... eee cence eee, 22 4.2 Controller Tuning for CN2000 Controllers With Self Tune

(AT) Option 2... cee cece ee. 25 4.2.1 The Tune Loop and Keypad Security. See eee eee eee 26 o.1 A.2.2., Self Tune Program 3. sso Wie. errr. veer 28

4.2.3 Self Tuné From a Cold Start Lene eee cece eee aes 29 4.2.4 Self Tune For Hot Restart and During Operation ............ 29 4.2.5 ManualTuning ... 2.2.0.0... 0000 cece eee ee. 30 4.3 Tuning Pointers... 2... cece eee eee. 31 4.4 Tuning a PID (Three Mode) Controller................... 32 4.41 Tuning the Primary Output for Heating Control............. 33 4.4.2 Tuning Procedure When No Oscillations Are Observed ....... 36 4.4.3 Tuning the Primary and/or Secondary Output for

Cooling Control... 0.0... cece eee ee eee. 37 4.5 Simplifed Tuning Procedure for PID Controllers............. 37 SECTION 5 DIGITAL COMMUNICATIONS OPTION......... 39 51 Instrument Identification .....0...000. 000. ee. 39 5.2 Communications Wiring... 2.000000. 0c eee eee eee ee 40 5.3 Handshake Option .........00 0.0.00 cece eee eeeee 42 5.4 RS232C Interface... eee een 42 5.5 RS422 Interface... 0... eee cece eae 43 5.6 20 mA Current Loop Interface... 0... 0. eee ce eee 44 5.7 Format Selection Switches ........00 00.000 cee ee cueee. 44 5.8 Programming 2.0.0.0... 000 cece cece eee eveeneus 45 5.8.1 Asynchronous Serial Data Format ..................... 45 5.8.2 DataProtocol......... 0.0... e eee eeen 46 5.8.3 Data Protocol Definitions .........0 00.0.0 cee cece eee 47 5.8.4 Parameter Designations ...................0 00-0000. 48 5.8.5 Control Commands, Process Status (PSW) .............. 49 5.8.6 Control Commands - Control Status (CSW) .............. 49 5.8.7 Status Response...... 0.0.0.0... 0. ccc eee cee eee eeue 49 5.8.8 Protocol Example - Read .........0. 00.0 ccc cece eee eee 50 5.8.9 Protocol Example - Write .. 0.00.00... cee eee eee 51 5.8.10 ASCH Table 0.0.0.0... 0... ccc cece eee 51 SECTION 6 CALIBRATION ...................000 eee 52 6.1 Entering Calibration Program... 2... ee ee 52 6.2 PartNumber.........0..00 00000000. cece eee eee eee 54 6.3 Part Number Changes ........... 0.0000 cece e eee ees 55

Page 5 read from a scan by OCR; it may hold reading errors

TABLE OF CONTENTS (Cont'd) SECTION PAGE

6.4 Setting the Part Number............................ 55 6.5 Setting the Displayed Units (Also Converting from °C to °F) ...56

6.6 Setting the Time Base ............................. 57 6.7 Setting the Span. 22... 57 6.8 Setting the Decimal Point... ........................ 58 6.9 Setting the Display Range ................0....0.... 58 6.10 Reference Calibration ............................. 58 ~ - - 644- - -- Thermocouple Catibration-~; => TTT tee eens .. 60 6.12 RTD Calibration... 2... 60 6.13 Process Calibration ............................... 61 6.14 Remote Set Point Calibration......................... 61 6.15 Calibration Complete... ............0........00.00, 62 SECTION 7 SERVICE INFORMATION .................. 62 74 Maintenance ... 6... eee ee eee. 62 7.2 Diagnostic Displays.............................., 62 7.3 Troubleshooting .........000. 0000 0000000-....0.., 63 SECTION 8 REMOTE START/STOP OPTION.............. 65 8.1 Wiring... 2... cee eee 65 8.2 Operation... 20... 65 SECTION 9 SPECIFICATIONS ....................... 66

Page 6 read from a scan by OCR; it may hold reading errors

IMPORTANT

All CN2001 & 2 thermocouple models are shipped factory programmed to operate with Type ”J” therm-couple, °F scaling. Users can re-program/re-scale these controllers to operate with other sensors by changing several digits in it’s configuation code. Section 6 in this manual outlines how to implement this change.

SECTION 1 INTRODUCTION

1:1

1.2

1.3

GENERAL DESCRIPTION ;

“The OMEGA® CN-2000 Series Programmable Controllers utilize the latest microprocessor technology to improve reliability, accuracy and control. Inputs can be either thermocouple or three wire RTD temperature sensors, or voltage or current signals from virtually any process variable. Output types are solid state relay, voltage or current signals, with either ON/OFF or proportioning control modes. These controllers provide proportional control of both heaters and coolers for stable automatic control of processes, or dual output control for separate control action.

The versatility of the CN-2000 makes it ideal for both laboratory and industrial use. The precision, fine tuning controls allow easy adjustment for accurate process control, and the bright alphanumeric display provides process variable and set point information from on demand, plus continuous alarm, output and operating mode status.

FEATURES

Thermocouple, RTD, voltage or current inputs Current, voltage or solid state relay outputs ON/OFF or PID control

Two independent process or deviation type alarms Timer option

Remote Set Point available

Digital Communications Options

AVAILABLE MODELS MODEL 1 OUTPUT | 2 OUTPUT NUMBER | DESCRIPTION| AND MODE | AND MODE (2002) CN2001(*) | 1 output 1A SSR, PID | 1A SSR, on/off CN2002(*) | 2 output 1A SSR, PID CN2001(*)-A] 1 output with | 1A, SSR, PID alarms 1A SSR, on/off CN2002(*)-A} 2 output with | 1A, SSR, PID » ONO alarms

* Input Code

Page 7 read from a scan by OCR; it may hold reading errors

INPUT INPUT

CODE TYPE #J Iron Constantan #K Chromega™-Alomega™ #T Copper Constantan #E Chromega-Constantan #R Pt 13% Rh/Pt #S Pt 10% Rh/Pt #B Pt 30% Rh/Pt 6% Rh aN Omegalloy™(Nicrosil-Nisil) #PLN Platinel il #G WIW 26% Re #C W 5% Re/W 26% Re #D W 3% Re/W 25% Re P2 Pt RTD, 1000 MA 4 to 20 mA (from transmitter} MV100 Oto 100mv DC V5 0 to 5 VDC v10 Oto 10 VDC

* refer to Handbook description of differences # For T/C controllers, check that T/C type is correct (see Section 6)

OUTPUT OPTIONS

TYPE FIRST OUTPUT SECOND OUTPUT (HEATING) {COOLING) SPECIFY SPECIFY:

SSR, on/off NF1 STO

SSR, PID STD PID2

4-20 mA && FI F2

0-5VDOC&& DCc1 DC2

Cooling cu STD

Heating STD H28

Auto/Manual AM NIA

Auto Tune AT N/A

§ N/A with PI02, F2 or DC2 && Auto/Manual standard on these units

NOTES: SSR outputs are user configurable (refer to Section 6.2} for on/off and PID control. Output 1 is user configurable for heat/cool.

ALARM OPTIONS DESCRIPTION ALARM 1 ALARM2 SPECIFY: SPECIFY:

High Process All* A2\

Low Process Al2 A22*

High Deviation A13 A23

Low Deviation Al4 A24

On Timer A15 A25

Off Timer Al6 A256

* standard with CN2001A and CN2002A

COMMUNICATION OPTIONS

ORDERING DESCRIPTION

SUFFIX

D1 Remote Analog Setpoint (disables Alarm #2} (N/A with 2001A and 2002A)

D2 RS-232-C non isolated

03 RS-232-C isolated

D4 RS-422-C non isolated

Ds RS-422-C isolated

06 20 mA loop isolated

07 Remote Start/Stop (disables alarm #'2- uses terminals B & C)

D7D0E Remote Start/Stop (disables alarm #'2- uses terminals D & E)

Page 8 read from a scan by OCR; it may hold reading errors

SECTION 2

2.1

2.2

UNPACKING

Remove the Packing List and verify that all equipment has been received. If there are any questions about the shipment, please call

INSTALLATION

OMEGA Customer Service Department.

Upon receipt of shipment, inspect the container and equipment for any signs of damage. Take particular note of any evidence of rough handling ~-_in transit. Immediately report any.damage.to.the shipping agent. =...

The carrier will not honor any claims unless ali shipping material is saved for their examination. After examining and removing contents, save packing material and carton in the

NOTE event reshipment is necessary.

IDENTIFICATION

Refer to case mounted top label on each unit for proper identification of supply voltage, Outputs), Alarm/Timer and Sensor type before proceeding with the wiring.

MICROPROCESSOR BASED CONTROLLER M2: OMEGA SENSOR PRIMARY SECONDARY INPUT OUTPUT OUTPUT O Tc ___, -'|| O ON/OFF SSR O NONE O RTD DO PIDSSR OO ON/OFF SSR O mv O 4-20mA {] PID SSR Ol mA O 0O5VDC O 4-20 mA Ov O O 0-5Vdc

O POWER RELAY 1 COMMUNICATIONS O 120 V AC O NONE (11 NONE O 220V AC O ALARM ___ OO REM.S.F: O 240V AC C] TIMER____ | 0 RS232C

O RS422 50/60 Hz RELAY 2 O 20mA 12 WATTS CO) NONE OO NON ISOL MAXIMUM O ALARM____| (1 ISOLATED

O TIMER O

1200-1450B

Page 9 read from a scan by OCR; it may hold reading errors

2.3

MOUNTING

[CauTION | insure that all power and measuring circuits are disconnected before installation is attempted.

In the normal course of installation and operation, there is no reason to remove the electronic assembly from the case. If the electronic assembly is removed, SPECIAL PRECAUTIONS MUST BE TAKEN IN

- - -HANDLING THE-CMOS INTEGRATED-GIRGUHS 10 PREVENT STATIC. ....- - ~- --

DISCHARGES FROM CAUSING DEVICE FAILURE.

The entire electronic assembly can be removed from the case for servicing without disturbing the rear terminal wiring by pressing in the tabs on each side of the bezel and carefully pulling the assembly out of the case. When digital communications is included, a ribbon cable connector must be pulled from the middle board before the assembly can be removed. When reinstalling the electronics assernbly, make sure that the unit is inserted right side up and that all boards are firmly in their connectors.

The Series CN-2000 Controllers are designed for mounting in a control cabinet or rack where access to the rear terminals is enclosed and where supply and load wiring can be properly terminated and enclosed. Prepare a standard % DIN panel cutout of 3.620” (92 mm) square and insert the instrument into the panel cutout. The U shaped mounting bracket, supplied with each unit, is installed from the rear of the controller and held in place by two threaded studs mounted on the rear of the case. Tighten the bracket with supplied hardware against the panel to insure a snug fit (see Figure 2-1).

Overtightening may cause the rear of the case to bow. To prevent this, a washer of the panel thickness may be used over the stud between the case and the bracket.

The Series CN-2000 Controllers have been designed for panel mounting with natural convection cooling. When installing the unit be sure that the case label and the rear vents are on the top side. Allow adequate clearance for proper air circulation.

NOTE

For panel mounting of two or more units, use a minimum horizontal spacing of 4.5” on center.

Page 10 read from a scan by OCR; it may hold reading errors

4

350 69 mm elie 7! _ MAX. PANEL THICKNESS 7.87 ern SIDE VIEW _, ee eee de 3 620 val H $2 mm j i 3620 ™ 92 mm { 06 - R MAX | 152mm FRONT VIEW PANEL CUTOUT

2.4

2.5

AC SUPPLY

Figure 2-1. Cutout and Mounting Dimensions

WIRING

Successful operation begins with proper installation. Good installation requires not only that good wiring practices be followed but also that reasonable protection be provided against external electrical influences that could interfere with controller operation. In adcition all wiring must conform to applicable local and national codes. The controller should be wired with an external power disconnect and fuse.

NOISE SUPPRESSION (Refer to Figure 2-2)

The primary source of electrical interference (noise) that can impact any digital device is inductors most commonly found as coils and windings in solenoids, relays and transformers. It is important to suppress any potential for electrical noise at its source to ensure reliable controller operation. Specifically this means putting noise suppression devices across the terminals of all inductors in your system.

AC NOISE SUPPRESSOR DC NOISE SUPPRESSOR oe + Dc = R | POWER _ - Figure 2-2. Noise Suppression

5