The text of a manual · part 2 of 8

CN-2000 Series Programmable Temperature Controllers Operator's Manual, pages 11 to 20

Pages 11 to 20 of 75

The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omega CN2001

Page 11 read from a scan by OCR; it may hold reading errors

If you do not have the necessary components available, they may be purchased in kit form from OMEGA.

OMEGA P/N DESCRIPTION

1821-101 Noise suppression kit includes one 0.1pF capacitor, one 2200 resistor, one 470 resistor, one R-C snubber and one MOV rated for up to 130 VAC at 35 joules.

The use of twisted and shielded extension wire is recommended for all signal leads. Make sure the shield is grounded ONLY at the controller.

Be sure to protect against ground loops in signal leads, shields and all” other input and output wiring. Never run signal input leads in or near the same bundle as supply or load lines.

SNUBBER FOR NOISE SUPPRESSION

A resistor-capacitor snubber network is used to suppress transient noise generated by arcing across opening contacts or caused by collapsing fields of inductive coils. The noise generated by these may pro-duce an undesirable response in an electronic instrument and the snubber helps to suppress this noise. The parts in this kit may be used across contacts or coils in circuits up to 240 VAC. The parts consist of the following: 1 2200 resistor, 1 472 resistor, 1 0.1pF capacitor, and 1 MOV.

ACROSS COILS

The capacitor is connected in series with the 2200 resistor (red-red-brown-gold) and the network is installed directly across the coil. The second resistor and the MOV in this kit are not used. Refer to Figure 2-3.

7 / C L,, iF oo |

T S ! I AC | SUPPLY \ 1h 220 coILj~ - ~- - - - - Figure 2-3. Coil Hookup

Page 12 read from a scan by OCR; it may hold reading errors

ACROSS CONTACTS

The capacitor is connected in series with the 470 resistor (yellow-violet-black-gold) and the network is installed directly across the contacts. The second resistor and the MOV in this kit are not used. Refer to Figure 2-4.

SUPPLY | i eee

INDUCTIVE COIL

Figure 2-4. Contacts Hookup

MOV FOR NOISE SUPPRESSION

Metal oxide varistors (MOV‘s) are used to suppress transient noise surges that are caused by the collapsing fields of inductive coils. The MOV in this kit is rated at 35 Joules at 130 VAC maximum.

The MOV is connected directly across a coil or winding. Make sure that the voltage rating of the MOV is correct to match the supply voltage of the coil. Higher rated MOV's are available. The capacitor arid resistors in this kit are not used. Refer to Figure 2-5.

oo

LJ ce Mov AC

SUPPLY | COIL

Figure 2-5. MOV Hookup

NOTE

FOR THE MOST EFFECTIVE SUPPRESSION, THE SNUBBER NETWORK OR MOV MUST BE MOUNTED AS CLOSE AS POSSIBLE TO THE CONTACTS OR COIL.

Page 13 read from a scan by OCR; it may hold reading errors

2.6

POWER CIRCUIT WIRING

The CN-2000 is normally wired for 120 V ac operation. Maximum input current at 120 V ac, 50/60 Hzis 115 mA ac. Connect the ac line power to rear terminals 6, 7 and 8 (see Figure 2-6). Terminal 6 is ac high; terminal 7 is ac low; terminal 8 is ground.

CAUTION ; ALM (2; NO @ G) ALM (1) NC Applying 240 Vac supply voltage toa unit | “UM (2!C 6) Ri . vee . _ - See “S$ ~~ not rated for this vottage] Aim ia we Cc) (3) ALM (1) NO will result in damage to OUT (2) HI ©) G) out ant the controller. OUT (2) LO (e) (s) OUT (1)L0 _ -INPUT G)} (6) | Ac HIGH (HoT) ° < OA ON 2 ; Fl 4 G2) }. Ac cow ineutRAL) + + INPUT GROUND VOLTAGE RTD TCINPUT OR INPUT CURRENT INPUT A.coto JuNctION COMPENSATOR FOR T/C UNITS ONLY Figure 2-6. Rear Terminal Connections 2.7 INPUT CIRCUIT WIRING NOTE The use of twisted and shielded extension wire is recommended to minimize noise pick-up. Never run signal input leads in or near the same bundle as supply or load lines. 2.7.1 Thermocouple Input

NOTE

For thermocouple versions of the controller, check that the instrument has been programmed for the correct thermocouple type.

Before attaching the input leads, follow the instructions in Section 6 to check the thermocouple type and perform any reprogramming that may be necessary. The input leads should be clean and tight and the maximum loop resistance should not exceed 100 ohms.

Connect the red ( - ) thermocouple wire or exterision lead to the rear panel terminal F (see Figure 2-6). Connect the color coded thermocouple lead to terminal H (+). No external connection is made to terminal G.

at

Page 14 read from a scan by OCR; it may hold reading errors

2.7.2

2.7.3

2.8

2.8.1

ALM (2) NO ALM 12) ALM 12) NC OUT 12) Hi OUT 12)LO w INPUT JNeTION + INPUT

LOAD

RTD Input

Connect the RTD sensor as shown in Figure 2-6 for a three wire RTD input. If a two wire RTD is used, strap terminals F and G together and connect the RTD between this pair and terminal H.

RTD leads can be extended with copper wire, provicled the leads are of the same lenath and diameter and run in a common conduit. Maximum extension lead resistance should not exceed 10 ohms.

DC Voltage and DC Current Input

__Connect the +dc input to terminal H, and connect the, dc input to terminal F (GND) (see Figure 2-6).

OUTPUT CIRCUIT WIRING

NOTE

Output options can not be added or changed in the field.

Solid State Relay, Primary and/or Secondary Output

Refer to Figure 2-7.

The Solid State Relay Output is a 1 ampere opto-isclated Triac output. Maximum voltage for SSR load is 240 V ac.

NOTE

Current limiting fuses are recommended to protect the 1 amp solid state relay.

6) QJ] aemrunc @) @)] amare = = (C) @ ALM «i NO + - (O} ExTERNAL ©) OUT «1 HI LOAD (@] JUMPER) FE] ours F © AC HIGH HOT, = | @) |_AC tow ineuTRal: o 8) Peron (zovac! = ALM (2) NO ©) @ ALM 11 NC ALM i21C KB) (jy acminc AuMi2inc [cy] EXTERNAL ALM 1) NO KO) jumper {2 ouTiaent [> G)} outa Out i2iL0 fe} @, OUT LO 4 + WPUT F (6) ) AC HIGH HOT) nerd, S @) | actow ineutRat + INPUT H (8) GROUND = uae 1 * Frovag

Figure 2-7a. Solid State Relay, Typical Primary Output Wiring

Figure 2-7b. Solid State Relay, Typical Secondary Output Wiring ae,

Page 15 read from a scan by OCR; it may hold reading errors

NOTE

Power is not internally wired to relays. If the same power source is required to power the controller and the primary output, jumper terminal 6 (AC HI) to terminal 4 (OUT (1) HI). (For secondary output, jumper terminal 6 to terminal D (OUT (2) Hl). Load is connected to terminal 5 (or E for secondary output). Power then goes through the relay to the load, and the other side of load is connected to AC LO to complete the circuit.

APPLICATION NOTE: WHEN USING THE CONTROLLER SOLID STATE

RELAY TO OPERATE AN EXTERNAL SOLID STATE RELAY OR SENSITIVE COIL RELAY TWO SITUATIONS MAY EXIST

1. The leakage current in the 1 amp SSR may be sufficient to cause an external SSR to remain in the conducting state. A 2k ohm 8 watt power resistor across the external SSR will solve this problem.

2. The low power draw of the external SSR may cause the controller SSR to turn OFF due to insufficient holding current. Use of a loading resistor across the external SSR or reiay terminals to increase the current will also solve this problem. Most loads are greater than 1 amp. It is recommended that external solid state relays such as SSR240A10 (nominal rating of 10 amps), SSR240A25 (nominal rating of 20 amps), or SSR240A45 (nominal rating of 35 amps), be used for larger loads.

2.8.2 Analog Output, Primary and/or Secondary Output (4-20 mA DC or 0-5 Vdc Output)

The solid state relay and analog output use the same terminals; therefore, only one type can be provided on each output (see Figure 2-8).

NOTE

Maximum Load Resistance = 1 K for 4-20 mA output. Minimum Load Resistance = 1 K for 0-5 V dc output.

(C + t SECONDARY = OUT (2) HI ¢ - +0) p - - - OUT (1)HI = PRIMARY OUTPUT . _ OUTPUT (ANA2) OUT (2) LO +E), - OUT (1) LO (ANA1)

©) ©) oO ere

REAR VIEW

Figure 2-8. Current or Voltage Output --Primary and/or Secondary Output Wiring

10

Page 16 read from a scan by OCR; it may hold reading errors

2.8.3

Standard controllers with analog output(s) have a common connection between the input and output circuits. Grounding both input and output may cause controller damage and loss of control. Isolated input and/or outputs are available.

Alarm/Timer Wiring (Option)

Two independent alarms or timers (ALM 1 and ALM 2) use electromechanical relays with both NO and NC terminals with one common return (C) for each relay, available at the rear terminals.

The part number will specify if alarms or timers are provided and the

(SUPPLIED BY USER. NOTE USE OF MOV {_ SUPPRESSOR.)

2.9 type and action of alarm (PROCESS or DEVIATION, Hl or LO acting) or ~ timer. Relay contacts are rated 1 amp @ 240 V ac resistive load.

Terminal designations normally refer to the de-energized state, i.e., no power to the relays. To provide reliable alarm indication, the relays in this controller are energized during normal operation of the controller. When wiring to these relays, be sure to keep this in mind. Before power is applied to the controller and when the alarm(s) is ON, the relay terminal designations are as shown in Figure 2-9. During normal operation with no alarms ON, the relays are the reverse of that shown in Figure 2-9.

Special care should be taken, when wiring these relays to inductive devices such as coils and transformers. Noise suppressors as shown in Figure 2-9 are important to prevent electrical noise from being generated. See paragraph 2.5.

EXAMPLE 1 ALM 2 ALM1 EXAMPLE 2

NO L(A) o NC .

t ’ ALARM HORN 1 t ' ‘

4 t t t 2 Cy MOV. to 0) 2 - t t

NC NO Cc eee od 120, VAC O

TRANSFORMER TYPE PANEL ALARM LAMP (SUPPLIED BY USER

\ NOTE USE OF R-C SNUBBER.F

Figure 2-9. Alarm/Timer Wiring

REMOTE SETPOINT INPUT

A controller with REMOTE SETPOINT input option (D1) provides for remote linear analog current or voltage control of the primary set point. Although the standard set point input is calibrated for 0 to 5 Vdc, other voltages through 10 Vdc or currents through 100 mAdc may be supplied on special order. The remote input may be from an isolated stable current or voltage supply or, where the set point can be manually adjusted to the required value; it may use an internal controller supply with a remote potentiometer for a simplified source. All controllers supplied with remote set point input option have a part number whose second digit is a ‘’1’’ (refer to paragraph 6.2).

Ni

Page 17 read from a scan by OCR; it may hold reading errors

2.10

NOTE Controllers with remote Set point input option can not have an ALARM/TIMER 2 option as these terminals are used for the remote set point input.

SPECIAL WIRING: The rear barrier terminal connections are changed as shown in Figure 2-10. All other connections are as described in the other paragraphs of Section 2.

voltage or current source

REAR VIEW Figure 2-10. Remote SetPoint

DIGITAL COMMUNICATIONS WIRING

Controllers with digital communications option are provided with a special Type D (DB25) connector between the rear terminals (see Figure 2-11). Wiring to this connector is discussed in detail in Section 5.

a

LZ REAR VIEW COMMUNICATIONS

CONNECTOR

QBNOANMA OND |

Figure 2-11. Communications Connector

12

Page 18 read from a scan by OCR; it may hold reading errors

SECTION 3 OPERATION

3.1

3.2

3.3

ALOOPis a series of items that appear on the controller display in a fixed sequence. The term MODE is used to define a keyboard setup that is required before a specific loop can be addressed. The CN-2000 is programmed to perform certain LOOPS only when in a specific MODE. For clarity, capital letters are used in this manual to denote names of LOOPS and MODES as well as for key names and functions.

INITIAL POWER UP

Before proceeding, verify that the controller is correctly inserted in the case and not installed upside down. Rear vents should be at the top of the case. Front vents are at the bottom of the case.

After all connections have been made to the rear terminal connections and the correct wiring verified, power may be applied. The display should illuminate as soon as power is applied. If the rnulticolor vacuum fluorescent display does not illuminate immediately, disconnect the power and recheck the wiring. Allow at least five minutes for warm-up before starting operation.

MODES OF OPERATION

The controller can operate in one of two MODES i.e. the OPERATOR mode or the TUNE mode. This distinction is made because different displays appear on the front of the controller for each mode and you can perform different functions in each mode.

The OPERATOR mode is the normal mode of operation. It is explained in detail in paragraph 3.6. The TUNE mode is used for tuning and programming the controller prior to going on-line or during operation. Tuning is explained in detail in Section 4.

A third mode is used for calibration of the controller. This CAL mode is explained in detail in Section 6. The controller cannot operate while in the CAL mode.

Before putting the controller into operation please read the rest of this section, which explains the display and keypad furictions.

DISPLAY INDICATIONS

The multicolor vacuum fluorescent provides all the communications to the operator. The central portion of the display is color coded blue and contains two rows of eight alphanumeric characters that display process measurement and set points, plus provide communications for tuning and operation. The display also has decimal point capability in the upper line of characters. Refer to Figure 3-1 and Table 3-1 for display indications.

13

Page 19 read from a scan by OCR; it may hold reading errors

ITEM 1

2

Figure 3-1. Series CN-2000 Vacuum Fluorescent Display

TABLE 3-1 DISPLAY INDICATIONS ___ - INDICATION FUNCTION ALARM/TIMER The two alarm/timer indicators are indicators color coded red and illuminate ALM

OUTPUT indicators with either a 1 or 2 or both, when one or both alarms or timers are active.

The alarm/timer circuitry is active at all times and continue to function even when the controller is in the TUNE mode.

The two independent alarms/ timers, ALM 1 and ALM 2, consist of electromechanical relays with both NO and NC contacts on the rear terminals. The alarm circuitry is active at all times. The alarms con- tinue to function even when the controller is in the TUNE mode. Timer relay(s) begin tirning when the START key is pushed.

Their normal state is energized and are de-energized when the alarm/ timer indicators turn on signifying alarm/timer output.

The two output indicators in- cluded in the display appear in blue and illuminate the word OUT with either a 1 or 2 or both numbers when either or both outputs are on. (1 = primary output and 2 = secondary output).

With ON/OFF and TPR (time pro- portional) control, the output indicator(s) will cycle on and off as the outputs cycle on and off.

14

Page 20 read from a scan by OCR; it may hold reading errors

iTEM 2

TABLE 3-1 (cont’d)

INDICATION FUNCTION OUTPUT indicators With analog output control, the (cont'd) output indicator(s) will be ON when the output is ON and the measure- ment is outside the selected pro- portional band limits. When the measurement comes within the band limits, the numerical indicator will flash with an ON/OFF ratio pro- woe ~portionat to the analog output: ~ MODE or status Color coded yellow and illuminate indicators to show controller status: TUN The TUN indicator will illuminate when the CN-2000 is in the TUNE mode. In this mode, all tuning parameters can be viewed and set.

TUN (Flashing) The TUN indicator will flash when the SELF TUNE program is in opera- tion (units with Self Tune (AT) op- tion only).

CAL The CAL indicator illuminates when the controller is in the CALIBRA- TION mode. All control functions are inactive while in the CAL mode.

REM (Steady) The REM indicator illuminates when the REMOTE SETPOINT op- tion is included and in use. See paragraph 3.9. Also ON by com- puter command.

REM (Flashing) The REM indicator will flash when a Digital Communications option is included and in use. See paragraph 3.10.

MAN (Steady) The MAN indicator will illuminate when the controller outputs are under manual control. (CN2000 with Auto Manual (AM) option only)

MAN (Flashing) The MAN indicator will flash when the control outputs are OFF as a warning that no action is taking place.

15