Page 21
3.4 THE KEYPAD
The six key membrane type keypad on the front face of the controller requires only touch pressure to activate. All control and tuning can be performed through the keypad in conjunction with the alphanumeric display. Some keys are multifunction but they are non-ambiguous because for any specific display, each key has only one function (see Figures 3-2a & 3-2b and Table 3-2),, _ Gm Ca IE
Figure 3-2a. Standard CN-2000 Keypad
=
Fal ICI
Figure 3-2b. Model CN-2000 with Auto Manual (Am) AM option
TABLE 3-2 KEYPAD CONTROL KEYS ITEM KEY FUNCTION 1 PARAM/DISPLAY Advances the displayed information key one step at a tirne. 2 UP arrow key When pressed will increase the {also YES key) numeric value of the parameter that is on the display. Holding the key in will increase the rate of change of the parameter.
3 DOWN arrow key When pressed will decrease the (also NO key) numeric value of the parameter that is on the display. Holding the key in will increase the rate of change of the parameter.
16 tg
Page 22
3.5
TABLE 3-2 (cont'd)
ITEM KEY FUNCTION (see items YES and NO keys Allow the operator to answer 2 and 3) displayed questions. 4 TUNE/RETURN key The TUNE key is used as part of the security code to enter the TUNE mode.
The RETURN key is used to return, - . ....... the-controller-to-the OPERATOR...
mode from any other mode.
5 START/STOP key Turns the output(s) on or off. This key is not a power switch. The MAN indicator will flash when the out- put(s) are off.
6 AUTO/MANUAL key The AUTO/MANUAL mode (units with AM option only) transfers con- trol of the outputs to and from automatic control. The MAN in- dicator light is ON when the con- troller is in the manual mode.
7 LAST key Allows the operator to recall the previous display at any time.
ALARM/TIMER OPTIONS There are two alarm types available on the CN-2000 Controllers:
A PROCESS alarm is an absolute value alarm that is independent of the set point and does not shift when the set point is changed. It can be either HI or LO acting.
A DEVIATION alarm is slaved to the controlling set point, and can be set as a plus or minus value above, equal to, or below the set point. A deviation alarm shifts when the set point is changed. It can be HI or LO acting. Units are differentia! degrees shown on the display as DF or DC.
DEVIATION BAND alarm is slaved to the set point, and is set plus and minus around the set point. Units are differential degrees for temperature.
The HI ACTING alarm activates (relay de-energized) when the measurement is equal to or above the alarm set point.
The LO ACTING alarm activates (relay de-energized) when the measurement is equal to or below the alarm set point.
7
Page 23
3.6
ON TIMER relay is OFF during the timing period and goes ON at the completion of the pericd. The ALM lamp will light at the end of the period.
OFF TIMER relay is ON during the timing period and goes OFF at the completion of the period. The ALM lamp will be ON during the period and goes OFF at the end of the period.
The alarm/timer relays are energized when ALM indicator is OFF and de-energized when the ALM indicator is ON.
In any critical application where failure could cause expensive product loss or endanger personal safety, a second redundant limit controller is recommended.
OPERATOR LOOP
The OPERATOR loop is available to the operator at all times allowing the operator to read all operating parameters. Since the OPERATOR mode is the standard operating mode, there is no OPERATOR indicator light. See Figure 3-3, OPERATOR loop flow chart.
The PARAM/DISPLAY key is used to advance the displays within the loop. The LAST key may be used to review the previous display at any time. Pushing the PARAM/DISPLAY key will continuously repeat this loop.
The numerical value of any displayed value can be changed by pressing either the UP or DOWN arrow key. All possible displays are shown below. Your controller will only show displays appropriate to your application.
XXU This display shows measurement value with units and the set point value. The set point can be changed us-
SP XXX ing the zrrow keys. XX U This display shows measurement value and the UTI XX% primary output in % power output. Manual control U (CN2009 units with Auto/Manual (Am) option only) of primary output is accomplished with this display. XXU This display shows measurement value and the DUT2 XX% secondary output in % power output, if included.
Manual Control of the secondary output is accomplished with this display.
This display shows the auxiliary set point (AUX SP} AUX SP | when OUTPUT 2 is on ON/OFF output. Units are dif- X DF ferential (DF or DC) between the primary and secondary set point.
18
Page 24
3.7
3.8
T 5 This display allows the operator to take manual control IMER ? | of TIMER 1 or TIMER 2 when they are included. Push OVERRIDE | YES key to activate next two displays when TIMER 1 and/or TIMER 2 are provided.
TIMER 1 ON/OFF These displays allow the operator te turn the TIMER relay(s) ON or OFF using the arrow keys when Timers TIMER 2 are specified and enabled above. The ALM 1 and ALM
2 indicators will come ON when the TIMER relays are ON/OFF ON.
REMOTE This display allows the operator to enable or disable the Remote Set Point option when provided, using the
SETPOINT Yes/No keys. The REM indicator will come ON when Remote Set Point is active. ENABLE? This display allows the operator to enable or disable the
Digital Communications option when provided, using COM LINK | _ the Yes/No keys. For complete details on the Digital Communications option, see Section 4. The REM indicator will flash when Digital Communications is active.
STOP/START CONTROL
The STOP/START key allows you to turn the control outputs ON and OFF. This is not a power switch. The controller electronic circuitry remains powered when the control outputs are turnec! OFF by this key.
The yellow MAN indicator will flash when the outputs are turned OFF.
AUTO/MANUAL CONTROL (Model CN2000 with AM option only)
The AUTO/MANUAL key allows you to take control and manually set the outputs from the keypad.
The OPERATOR loop includes two displays for manual control. These are OUT1 and OUT2 and show output as a % from C to 100% power.
With ON/OFF control the output is either fully ON or fully OFF. With time proportional control and analog control output, the cutput can be any value from O to 100% and can be adjusted to a particular value when in manual control. To prevent severe process transients when switching between manual and automatic control, an internal program is provided that starts the automatic control at the manual set point. This means that time proportional and analog controllers will drive to the correct output power at a controlled rate, not instantaneously. This action is called bumpless transfer and protects the process from severe transients during control transfer.
19
Page 25
3.9
3.10
REMOTE SETPOINT
Asecond digit 1 (B for CN2000 units with Self Tune (AT) option) in the part number (refer to paragraph 6.2) indicates that the controller has been specified and manufactured to accept an analog remote set point from an externally mounted potentiometer or remote voltage or current source.
REMOTE? | To enable this external input advance the display in the SETPOINT OPERATOR loop until this display appears. See Figure i}. 3-3 OPERATOR loop flow chart.
Push the YES key to enable the remote set point input. The REM indicator will iluminate to confirm that control has been transferred from the internal set point to the external remote set point.
To disable this option, return to the REMOTE SETPOINT display, and push the NO key.
DIGITAL COMMUNICATIONS
Asecond digit 2 thru 6 (C thru G for CN2000 units with Self Tune (AT) option) in the part number (refer to paragraph 6.2) indicates that the controller has Digital Communications option.
ENABLE? | 10 enable Digital Communications, push the YES key COM LINK at this display. See Figure 3-3 Operator Loop Flow
Chart. To disable Digital Communications, push the NO key at this display.
The host cannot enable digital communications. This can only be accomplished by a key press on the front keypad of the controller. Even after communications is enabled, local control is still allowable.
During host-controlled operation, the front keypad remains active so that you can override the host and can take control if necessary.
The REM indicator light will flash when the communications is enabled. The REM indicator light will continue to flash until communications is disabled via the keypad. The host can also turn the REM indicator full on as part of the STATUS INPUT (PSW) command to inform you that the host is in control. Included in the host command structure is manual control of the controller output(s).
20
Page 26
UU
XXXX SP XXKX
XXXX UU
OUT1 XX%
PD
ON/OFF CONTROL,
AUX SP
TIMERS q
?
‘0
YES
NO.
| TIMER rI1* OVERRIDE
TIMER 1 ON/OFF
+
TIMER 2 DP oon/orr y"
REMOTE ?
SETPOINT
XXX_DU
PD
DIGITAL COMM.
NG
YE.
* A YES or NO response is required at each of these displays.
PARAM DISPLAY key to advance. LAST key to recall last display.
ENABLE ? COM LINK
Figure 3-3. OPERATOR Loop Flow Chart
21
X =NUMERICAL VALUE U =DISPLAY UNITS PD=PARAM DISPLAY
ACTUAL DISPLAY
INTERNAL DECISION
Push
Push ore
Page 27
SECTION 4 TUNING
4.1
CONTROLLER TUNING FOR CN2000 CONTROLLERS WITHOUT SELF TUNE (AT) OPTION
This controller has been configured at the factory with input, output and alarm functions to meet your specific application. Arbitrary alarm and tuning values were used at the factory to allow complete controller checkout. It is necessary for you to TUNE this controller to your specific Process or machine before going to automatic control. In the TUNE program the PARAM DISPLAY key advances the displays. The LAST key
_May be used to review the previous display-at-any time. - --- -----
This section provides complete details on all tuning procedures.
TUNE Loop
The TUNE loop requires that a special tuning code be entered on the keyboard before any tuning information can be accessed. Press the following keys in Sequence to enter the TUNE made.
TUNE - LAST - YES
The yellow TUN indicator will illuminate on the display when the code is entered Correctly. If the TUN indicator does not come ON, push the RETURN key and then push the code again. The PARAM/DISPLAY key advances the displays in the TUNE loop and the LAST key will back up the displays.
The TUNE displays shown below indicate all possible combinations. No Specific application uses all of these displays. Your controller will only display those items appropriate to the part number of your controller. See Figure 4-1, TUNE Loop Flow Chart.
These two displays will appear
ALARM 1 TIMER 1 when alarms or timers have XXX UU XXX:XX | been included. ALARMS can be or process (F or C units) or devia-
ALARM 2 TIMER 2 tion (DF or DC units). The UP or . DOWN arrow keys are used to
XXX UU XXX:XX set in the desired alarm or timer values. Push the PARAM DISPLAY key to advance to the next display.
NOTE If setting the alarm or timer relay(s) is the only function the operator wishes to perform in the TUNE Loop, push PARAM DISPLAY until END OF TUNE appears; then push the RETURN key to return to normal operation.
22
Page 28
SET PT XXXX_UU PO
OFF TIMER 1 TIMER 1 ALARM 1 ALARM 1 RESET 1 XXX:XX XXX:XX XXXX DU XXXX UU XX.XXB/M PD PD PD PD
OFF
DEV ALARM 2 XXXX DU
PD
TIMER 2 TIMER 2 XXX:XX XXX: XX
TUNE ? LYES
OUTPUTS J
NO mi
DISPLAY
LEGEND PD = PARAM DISPLAY KEY X = NUMERICAL VALUE U_ = DISPLAY UNITS
PR BAND2
D RESET 2 XX. XXE/M
FD
OPERATOR LOOP
RATE : XXX M ?D
Figure 4-1. TUNE Loop Flow Chart (For CN2000 Units Without Self Tune (AT)
Option)
23
Page 29
TUNE ? OUTPUTS pene BD1
PR BAND1 XXX %
RESET 1 X.XX R/M
RATE 1 X.XX M
AUX SP XXX DF
At this display the Operator must decide if he wishes to tune the outputs. A YES or NO answer using the appropriate key will allow the operator to tune each OUT. PUT Separately or to bypass this section. When a YES answer is entered, the outputs may be tuned using the following sequence of displays:
This display appears when the primary output is specified as ON/OFF control. A deadband of 0.25, 0.50 or 1.00% of span can be selected. Factory preset value is 0.25%. Push PARAM DISPLAY to advance,
This display appears when the prirnary output is specified as time proportioning control in the part .
number. A cycle time from 1 to 60 seconds can be selected. Factory preset is 15 seconds. Push PARAM DISPLAY to advance.
The following 3 displays appear when the PRIMARY OUTPUT is specified as time proportioning or voltage Of Current control. Set a proportional band (gain) of 1 to 200 percent using arrow keys. Factory preset value is 5%. Push PARAM DISPLAY key to advance to next display.
RESET display indicates the RESET (integral) action. Reset from 0.01 to 20.00 repeats per minute (R/M) can be selected. Factory preset value is 0.25 R/M. A reset value of 0.00 turns the reset action off.
This display indicates the RATE (derivative) action. RATE from 0.01 to 5.00 minutes (M) can be selected. Factory preset value is 1.00 minutes. A rate value of 0.00 turns rate action off.
This display appears only whena secondary output is provided. Auxiliary set point (AUX SP} defines the value of the secondary set point with respect to the primary Set point. The units are differential degrees DF or DC. This set point can be set above (plus), equal to or below (minus) the primary set point using the arrow keys.
24
Page 30
4.2
When a secondary COOLING or ON/OFF HEATING output is included in the controller, a second set of displays follows for tuning of this output.
This display appears only when a secondary output is AUX DB provided and is specified as ON/OFF control. A dead-
XX % band of 0.25, 0.50 or 1.00% of spar can be selected. Factory preset at 0.25% of span.
This display appears only when a secondary output is
CYCTIME2 provided and is specified as TPR control in the part
-| XXX SEG-} -number - A-cycletime-from - t-to-6G-seconds-can-be - - selected. Factory preset at 15 seconds.
PR BAND2| PROPORTIONAL BAND (gain) from 1 to 200% of span XXX % can be selected. Refer to paragraphs 4.4 through 4.5 for instructions on proper tuning. Factory preset at 5%.
RESET 2 RESET (integral) action from 0.01 to 20.00 repeats per KX.XX R/M minute (R/M) can be selected. Factory preset at 0.25 : R/M. A reset value of 00.00 turns the RESET 2 OFF.
RATE 2 RATE (derivative) action from 0.01 to 5.00 minutes (M) XXX M can be selected. Factory preset value is 1.00 minutes. . A RATE value of 0.00 turns the RATE action off.
This display is the final step in the TUNE loop. The LAST END OF key will back up the display one step at a time within
TUNE the TUNE loop. PARAM/DISPLAY key will repeat the TUNE loop from the top.
RETURN key will exit the TUNE mode and return the display to the primary OPERATOR loop. This is the only display from which the TUNE Loop can be exited.
CONTROLLER TUNING FOR CN2000 CONTROLLERS WITH SELF TUNE (AT) OPTION
This controller has been configured at the factory with input, output and alarm functions to meet your specific application. Arbitrary alarm and tuning values were used at the factory to allow complete controller checkout. It is necessary for you to TUNE this controller to your specific process or machine before going to automatic control.
In this controller, a special program can automatically calculate the appropriate PID values during start-up and even during normal operation thereby eliminating the need for manual tuning. You initiate this SELF TUNE program from the front keypad by responding to a sequence of displayed questions. There are no internal switches, ;0ts or jumpers to set or adjust. All tuning is accomplished through keypad inputs.
25