CN-2000 Series Programmable Temperature Controllers Operator's Manual, pages 31 to 40
Pages 31 to 40 of 75
The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omega CN2001
Page 31
4.21
This controller is unique in that it not only automatically calculates the PID values but it will also show you those values on its alphanumeric display. You can use the calculated PID values or you can manually change any of them as circumstances require. For example: in a flow application you may want to turn the RATE action OFF,
NOTE This SELF TUNE program ONLY applies to a primary HEAT acting output (OUT 1} and its PID values. For Time Proportional Control (TPR) you must first select the CYCLETIME before self-tuning. If your controller has a secondary output (OUT2), you must also tune that output manually. Primary COOL-acting., ~ - control also must be manuallytuned.-
This section provides complete details on all Tuning procedures.
The Tune Loop and Keypad Security
Access to the TUNE loop requires that a special key code be entered before any Tuning can be done. Press the keys TUNE-LASTYES in sequence to enter the TUNE loop.
A yellow TUN indicator will illuminate on the display when the code is entered correctly. If the TUN indicator does not come ON, push the RETURN key and then push the code again. The PARAM DISPLAY key will advance the displays in the TUNE loop and the LAST key will back up the displays. A flow chart of the TUNE loop is shown in Figure 4-2 that shows all displays in the loop.
Additional security is available (on units shipped after Jan 1, 1989) to prevent unauthorized controller adjustments.
NO KEYS OW REY er With these displays you can disable the UP/DOWN arrow keys used to change set points when in the operator mode. ALL OPERATOR displays can still be viewed but no values can be changed while the arrow keys are turned off. The key codes do still function.
YES YES
When optional Alarm or Timer
ALARM 1 TIMER 1 relay(s) are provided, one or two of
XXX UU XX:XX these displays will appear in se-or quence. Set in the desired Alarm or
ALARM 2 TIMER 2 Timer values using the arrow keys.
XXX:XX XXX:XX Push the PARAM DISPLAY key to - a advance to next display.
26
Se,
Page 32
END OF TUNE
PD ARROW LNOfaRRow
LEGEND
= Numer“cal Value = Displayed Units = PARAM Display Key x
U
PD
@ = Internal decision based on part number, ALAR TL pe - XXX UU PD PD Pr BANDI ’ XXX 4% ray [AtarM 2 TIMER 2 RESET 1 XXX UU XX XX XX.XXR/M PD PD 4 RATE 1 XXX M No [TUNE ? +# - - - JJ outputs PD , YES < - > YCTIME 1 AUX DB) pp XX SEC XXX y rz NO $ - |
TUNE? >
CYCTIME2 XX SEC
PD _f PR BAND2 XXX id
PD, _ START NO , RESET 2 XX.XXR/M
+, e SELF RATE 2 TUNING [ X.XX M
4 y
Figure 4-2. TUNE Loop for CN2000 Controllers, with Self Tune (AT) Option.
27
Page 33
4.2.2
If setting the alarm relay(s) is the only function you wish to perform in the TUNE loop, push PARAM DISPLAY until END OF TUNE appears and then push the RETURN key to return to normal operation.
For actual Tuning, proceed by pushing the PARAM DISPLAY key.
TUNE ? Push the YES key at this display to access all the Tuning programs. Tuning is required on all initial OUTPUTS installations.
CYCTIME 1] _ This display appears ONLY when the primary outputis....
XX SEC, -Specified as Time Proportional Gontrot {FPR-Any CYC- ~~
TIME from 1 to 60 seconds can be set using the arrow keys. The controller is shipped with a factory set value of 15 seconds.
You must establish the correct CYCT IME for your application. The SELF TUNE program DOES NOT include determination of CYCTIME. When CYCTIME is set, push the PARAM DISPLAY key.
Self Tune Program SELF This is the first display in the SELF TUNE program. Push TUNE ? YES key for SELF TUNE. Push NO key if manual tuning : of the primary output is desired and proceed to Section
4.2.3.
You must next choose the desired closed loop response of the system: FAST or SLOW. Different tuning rules are applied by SELF TUNE according to your choice.
FAST ? NO SLOW ? Indicate whether you : RESPON want your system to be a RESPONSE SE | FAST or SLOW respon.
ding system. Push the NO key to switch between YES YES these two displays. Push the YES key to select the desired response.
Select FAST RESPONSE for systems where a possible overshoot will not present a hazard. Select SLOW RESPONSE where potential overshoot is not acceptable. Your decision can be changed at any later time without retuning by returning to these displays in the TUNE loop and selecting the other response.
28
Page 34
4.2.3
4.2.4
START Push the NO key if you don’t want to start the SELF TUNE? TUNE procedure. The PID constants will then be
: calculated according to the last process model and your choice of response. This allows you to change your choice of FAST or SLOW tuning without repeating the self tuning program.
Push the YES key to initiate the SELF TUNE program.
SELF The yellow TUN light will flash, and the display in- TUNING dicates that you are in SELF TUNE mode. After a short troller will start to analyze the system. Self Tune From A Cold Start
When you start your machine or process from a cold start, the SELF TUNE program begins with 100% output power until the temperature reaches approximately one-half way to set point (Figure 4-3). The set point must be at least 30 degrees F (17 degrees C) above ambient. If itisn’t, the controller automatically goes to manual tuning displays. At the half-way point, the controller shuts off the output and monitors the process as it responds to the loss of heat. The controiler calculates appropriate PID values and returns output power to quickly bring the temperature to set point under three mode control.
sp
PV
TIME - Figure 4-3. Self Tune From a Cold Start
Self Tune For Hot Restart and During Operation
NOTE Controllers with analog inputs can only use SELF TUNE from acold start. SELF TUNE from a hot start will yield erroneous results.
Anytime during operation, or after a pause in operation, the SELF TUNE program can be used when a thermocouple or RTD input is being used. If the process or machine is at or close to operating temperature, the controller will shut off the output to allow an approximate 20% drop in temperature (set point to ambient) while it calculates new PID values. The output is then turned ON to return the temperature to set point.
29
‘detay (15 secs}, Output 1 will turn ON, and thecon: ~ ~~~
Page 35
4.2.5
The 50% point for cold start and the 20% drop for hot retune are factory set but can be changed if either of these values causes process dif-ficulties. Contact the factory for instruction on changing either value.
While the SELF TUNE is active, the yellow TUN indicator will flash and all keys but two are disabled. The RETURN key is active to allow you to observe the OPERATOR loop displays using the POINTER technique explained in paragraph 4.3. The STOP/START or AUTO/MANUAL (option AM) key is also active to allow you to stop the SELF TUNE program if required.
The SELF TUNE program will select the most appropriate PID values shown below.
SELF TUNING MANUAL TUNING Proportional Band 1-50% 1-200% RESET 0-10 R/M 0-20 R/M RATE 0-3M 0-5M
When the SELF TUNE program is completed, the display automatically advances to show you the Proportional Band selected.
Manual Tuning
The following tuning displays are always available in the TUNE loop. When SELF TUNE is used, the first three displays will show the PID values selected by the SELF TUNE program. You can change these values if necessary. These same displays are used if you want to manually tune the primary output. Refer to Section 4.5 for a suggested tuning method.
PRBAND1| SetaProportional Band of 1 to 200% using arrow keys. XXX% Factory preset value is 5%. Push PARAM DISPLAY key ° to advance to the next display.
RESET Set a RESET of 00.00 to 20.00 Repeats per Minute. XX:XXR/M Factory preset value is 0.25 R/M. Setting RESET to : 00:00 turns RESET OFF.
RATE 1 Set a RATE of 0.00 to 5.00 Minutes. Factory preset
XXX M vue is 1.00 Minutes. Setting RATE to 0.00 turns
When a secondary (COOLING) output is included in your controller, a second set of displays follows for manual tuning of this output.
AUX DB For ON/OFF secondary. Select a Deadband from 0.25, XX % 0.50 and 1.00% of Span using the arrow keys. Factory set at 0.25% of Span.
30
Page 36
4.3
CYCTIME 2| For Time Proportional secondary. Select a CYCTIME of XXX SEC 1 to 60 seconds. Factory preset at 15 seconds.
PRBAND2| Seta Proportional Band 2 of 1 to 200%. Factory preset XXX% at 5%. ‘0
RESET 2 Set a RESET 2 of 00.00 to 20.00 Repeats per Minute. . Factory preset at 0.25 R/M. Setting RESET 2 at 00.00 XX:XX R/M] turns RESET 2 OFF,
“T RATE 2 | Seta RATE2 of 0.00 to5.00 Minutes: Factory preset value is 1.00 Minutes. Setting RATE to 0.00 turns RATE
X.XX M OFF.
END OF Tuning has been completed. At this display you have TUNE several key options.
LAST key will back up displays to review or change settings. PARAM DISPLAY key will repeat TUNE loop from the top. RETURN key will exit TUNE loop and return to Operator displays.
NOTE You can only extinguish the TUN indicator by pushing the RETURN key while at the END OF TUNE display.
TUNING POINTERS
To simplify tuning of the Model CN-2000 Controller, special logic called POINTERS has been included that allows tuning persorinel to jump back and forth between TUNE displays and OPERATOR displays quickly and efficiently.
To operate the tuning pointers, the controller must be in the TUNE mode, ie., TUN indicator ON. Pushing the RETURN key once, and then the PARAM DISPLAY, will allow the operator to review all of the OPERATOR loop displays. Push the RETURN key again to return to the TUNE loop displays. The PARAM DISPLAY key will now scroll through the TUNE displays. The operator can switch between loops simply by pushing the RETURN key.
NOTE The TUN indicator can only be turned off and the TUNE Loop can only be terminated when at the ‘END OF TUNE” display. Pushing the RETURN key when at this display cancels the TUNE program and turns TUN off.
31
Se
Page 37
For example: In the TUNE mode (TUN indicator ON) the display can be advanced to RESET 1 using the PARAM/DISPLAY key. Then, after pressing the RETURN key to call up the OPERATOR Loop, the display can be advanced to OUT 1 using the PARAM/DISPLAY key. Push RETURN to see and set RESET 1 and then push RETURN again to observe OUT 1 response to that change. The operator can go back and forth between these two displays at the touch of a key for quick and efficient tuning. _
TUNING A PID (THREE MODE) CONTROLLER
The Series CN-2000 Controller is capable of exceptional control
~ Stability when properly tuned and used. The operator can achieve the- - fastest response time and smallest overshoot by following these instructions carefully. The information for tuning this three mode controller may be different from other controller tuning procedures. Normally the SELF TUNE feature (units with AT option) will eliminate the necessity to use this manual tuning procedure for the primary output, however, adjustments to the SELF TUNE values may be made if desired.
After the controller is installed and wired:
a. Apply power to the controller.
b. Disable the control outputs by pressing the STOP key. (The MAN indicator will flash when the output(s) have been disabled.) With CN2000 units with AM (Auto/Manual) option, the operator must go to manual control, push MANUAL key, and turn the outputs OFF using the DOWN arrow key.
c. Enter the TUNE loop by pushing TUNE-LAST-YES keys in sequence. (The TUN indicator will illuminate).
d. Press PARAM/DISPLAY key to advance the TUNE program to TUNE OUTPUTS e. Press YES key. For time proportional primary output, CYCTIME 1 will appear. Enter the following value:
CYC TIME 1, - - S5SEC (Only appears if output is TPR output, a smaller cycle time may be re- quired for systems with an ex- tremely fast response time).
32
Page 38
4.41
Press PARAM DISPLAY and sequentially enter the following values. (For CN2000 with the SELF TUNE (AT) option, press PARAM DISPLAY and answer NO to the SELF TUNE display. Then press PARAM DISPLAY again and sequentially enter the following values.)
PRBAND 1, - - ~ - - 5% (PB) RESET 1, - - - - OR/M (TURNS OFF RESET FUNCTION) RESET 2, - - - OR/M RATE 1 | = - - - _OMIN (TURNS OFF RATE FUNCTION) RATE2, - - - OMIN
NOTE
On units with dual three mode outputs the primary and secondary tuning parameters are independently set and must be tuned separately. The procedure used in this section is for a HEATING primary output. A similar procedure may be used for a primary COOLING output or a secondary COOLING output.
Tuning Outputs for Heating Control
1.
Press the RETURN key so that the measurement appears on the screen. Itis not necessary to return to OPERATOR mode while tuning the controller (POINTERS).
Press START key (or AUTO key, for CN2000 with AM option) to enable the OUTPUT(S) and start the process.
. The process should be run at a set point that will allow the temperature to stabilize with heat input required.
. With RATE and RESET turned OFF, the temperature will stabilize with a steady state deviation, or droop, between the set point and the actual temperature. Carefully note whether or not there are regular cycles or oscillations in this temperature by observing the measurement on the display. (An oscillation may be as long as 30 minutes).
The tuning procedure is easier to follow if you use a recorder to monitor the process temperature.
. If there are no regular oscillations in the temperature, divide the
PB by 2 (see Figure 4-4). Allow the process to stabilize and check for temperature oscillations. If there are still no oscillations, divide the PB by 2 again. Repeat until cycles or oscillations are obtained. Proceed to Step 5.
If oscillations are observed immediately, multiply the PB by 2. Observe the resulting temperature for several minutes. If the oscillations continue, increase the PB by factors of 2 until the oscillations stop.
33
Page 39
TEMP.
PRIMARY
PRIMARY PRIMARY SET POINT
A SET POINT A SET POINT ee
TEMP.
=
TIME v
~~ -, TIME TIME
Divide PB by 2is This is close to Multiply PB by 2 if you observe this. perfect tuning. you observe this.
Figure 4-4. Temperature Oscillations
The PBis row very near its critical setting. Carefully increase or decrease the PB setting until cycles or oscillations just appear in the temperature recording.
If no oscillations occur in the process temperature even at the minimum PB setting of 1%, skip Steps 6 through 11 below and proceed to paragraph 4.4.2.
Read the steady-state deviation, or droop, between set point and actual temperature with the “‘critical” PB setting you have achieved. (Because the temperature is cycling a bit, use the average temperature.)
Measure the oscillation time, in minutes, between neighboring peaks or valleys (see Figure 4-5). This is most easily accomplished with a chart recorder, but ameasurement canbe read at one minute intervals to obtain the timing.
PRIMARY SET POINT Y
TEMP.
MEASURE THIS TEMP. INCREASE A 4
DECREASE BcRiticaL }“at- MEASURE THIS PB PB TIME
TEMP.
STARTUP, TIME
Figure 4-5. Oscillation Time
Now, increase the PB setting until the temperature deviation, or droop, increases 65%.
The desired final temperature deviation can be calculated by multiplying the initial temperature deviation achieved with the CRITICAL PB setting by 1.65 (see Figure 4-6) or by use of the convenient Nomogram | (see Figure 4-7). Try several trial-and-error settings of the PB control until the desired final temperature deviation is achieved.
PRIMARY SET POINT Y y
CRITICAL PB, DEVIATION A 1.65 ~« TEMP TIME WITH PB, TEMP WITH PB. =DEVIATION WITH
G, STARTUP
_
TIME
Figure 4-6. Calculating Final Temperature Deviation
34
Page 40
TEMPERATURE DEVIATION WITH a | CRITICAL PB, SETTING tn 1 2 345 10 18 20 304050 70 100 PB. -SET PB TO L | | | | ji il | { | | | | Lit] OBTAIN 5° FINAL T T TUT TT TUT TTY T DEVIATION 2 3 5 10 15 20 30 4050 100 150
| 4 FINAL TEMPERATURE DEVIATION = 1.65
DEVIATION WITH CRITICAL PB, SETTING. NOMOGRAPH | Figure 4-7. Nomogram |
__... 9. You have now completed all the necessary measurements to_ obtain optimum performance from the CN-2000 Controller. Only two more adjustments are required, RATE and RESET.
10. Using the oscillation time measured in Step 7, calculate the value for RESET in repeats per minutes as follows:
RESET = 8 x 1. Where To = Oscillation Time in Minutes.
5 To; OR Use Nomogram li (See Figure 4-8):
TEMPERATURE CYCLE TIME IN MINUTES
0.1 0.2 0.3 1 2 3 10 20 30 100 wal 4 Lit | (Gua meeeel 1 ie ae Sees t WT rt qT TIT Ti Tt rT qT q Tq Tot 20 10 5 3.2 1 0.50 0.30 0.20 0.10 ¢.05 0.03 0.02
CORRECT RESET SETTING IN REPEATS PER MINUTE Figure 4-8. Nomogram Il
Enter the value for RESET 1.
11. Again using the oscillation time measured in Step 7, calculate the value for RATE in minutes as follows:
RATE = To Where to = Oscillation Time
10; OR Use Nomogram Ill (See Figure 4-9)
TEMPERATURE CYCLE TIME IN MINUTES
4 2 0. 1 2 3 10 20 30 4050 o OF 8 at Leip spins TLL 0.01 0.02 0.03 01 02 03 1 2 3465
CORRECT RATE SETTING IN MINUTES Figure 4-9. Nomogram Ill
Enter this value for Rate 1.
35