Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeEnglishEspañolContact

The text of a manual · part 5 of 8

CN-2000 Series Programmable Temperature Controllers Operator's Manual, pages 41 to 50

Pages 41 to 50 of 75

The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omega CN2001

Page 41 read from a scan by OCR; it may hold reading errors

12. If overshoot occurred, it can be eliminated by decreasing the RESET time. When changes are made in the RESET value, a cor-responding change should also be made in the RATE adjustment so that the RATE value is equal to:

RATE = 1 : ie, if reset = 2 R/M, the 6 x Reset Value RATE = 0.08 min.

13. Several set point changes and consequent RESET and RATE time adjustments may be required to obtain the proper balance between ‘‘RESPONSE TIME" toa system upset and ‘SETTLING TIME"’. In general, fast response is accompanied by larger over-

~~. Shootand consequently shorter time for the process to “SETTLE

“OUT”. Corversely, if the response is slower, the process tends to slide into the final value with little or no overshoot. The requirements of the system dictate which action is desired.

14. When satisfactory tuning has been achieved, the cycle time should be increased to save contactor life (applies to units with time proportioning outputs only (TPRI)). Increase the cycle time as much as possible without causing oscillations in the measurement due to load cycling.

15. Proceed to Paragraph 4.4.3.

4.4.2 Tuning Procedure When No Oscillations Are Observed

1. Measure the steady-state deviation, or droop, between set point and actual temperature with minimum PB setting.

2. Increase the PB setting until the temperature deviation (droop) increases 65%. Nomogram | (see Figure 4-'7) provides a convenient method of calculating the desired final temperature deviation.

3. SettheRESET 1toa high value (10 R/M). Set the RATE 1 to acor-responding value (0.02 MIN). At this point, the measurement should stabilize at the set point temperature due to reset action.

4. Since we were not able to determine a critical oscillation time, oe the optimum settings of the reset and rate adjustments must be determined by trial and error. After the temperature has stabilized at set point, increase the set point temperature setting by 10 degrees. Observe the overshoot associated with the rise in actual temperature. Then return the set point setting to its original value and again observe the overshoot associated with the actual temperature change.

Excessive overshoot implies that the RESET and/or RATE value are set too high. Overdamped response (no overshoot) implies that the RESET and/or RATE value are set too low. Refer to Figure 4-10. Where improved performance is required, change one tuning parameter at a time and observe its effect on performance when the set point is changed. Make incremental changes in the parameters until the performance is optimized.

36

Page 42 read from a scan by OCR; it may hold reading errors

RESET OR RATE TOO HIGH

4.4.3

4.5

When satisfactory tuning has been achieved, the cycle time should be increased to save contactor life (applies to units with time proportioning outputs only (TPRI)). increase the cycle time as much as possible without causing oscillations in the measurement due to load cycling.

RESET OR RATE TOO LOW.

Figure 4-10. Setting RESET and/or RATE

Tuning the Primary Output for Cooling Control

The same procedure is used as defined for heating. The process should be run at a set point that requires cooling control before the temperature will stabilize.

SIMPLIFIED TUNING PROCEDURE FOR PID CONTROLLERS

The following procedure is a graphical technique of analyzing a process response curve to a step input. It is much easier with a strip chart recorder reading the process variable (PV).

1.

Starting from a cold start (PV at ambient), apply full power to the process without the controller in the loop, i.e., open loop. Record this starting time.

After some delay (for heat to reach the sensor), the PV will start to rise. After more of a delay, the PV will reach a maximum rate of change (slope). Record the time that this maximum slope occurs, and the PV at which it occurs. Record the maximum slope in degrees per minute. Turn off system power.

Draw aline from the point of maximum slope back to the ambient temperature axis to obtain the lumped system time delay Td (see Figure 4-11). The time delay may also be obtained by the equation:

Td = time to max. slope - (PV at max. slope - Ambient)/max. slope

Apply the following equations to yield the PID parameters:

Pr. Band = Td x max. slope x 100/span = % of span Reset = 0.4/Td = resets/minute Rate = 0.4 x Td = minutes

37 a)

Page 43 read from a scan by OCR; it may hold reading errors

5. Restart the system and bring the process to set point with the controller in the loop and observe response. If the response has too much overshoot, or is oscillating, then the PID parameters can be changed (slightly, one at a time, and observing process response) in the following directions:

Widen the proportional band, lower the Reset value, and increase the Rate value.

Example:

The chart recording in Figure 4-11 was obtained by applying full power to anoven. The chart scales are 10°F/cm, and 5 minécm, The controller ~ range is 100, GOO°F, or a span Of 5000 Fr Maximum slope = 18°F/5 minutes = 3. 6°F/minutes.

Time delay = Td = approximately 7 minutes.

Proportional Band = 7 minutes x 3.6°F/minutes x 100/500°F = 5%.

Reset = 0.4/7 minutes = 0.06 resets/minute Rate = 0.4 x 7 minutes = 2.8 minute

PV

18°F

5 mins jl

Tg TIME

Figure 4-11. System Time Delay

38

Page 44 read from a scan by OCR; it may hold reading errors

SECTION 5 DIGITAL COMMUNICATIONS OPTION

5.1

The host cannot initiate communications enable. This can only be accomplished by a key press on the front keypad cf the controller. See paragraph 3.8. Even after communications is enabled, local control is allowable.

During host-controlled operation, the front keypad is still active so that the operator can override the host and can take direct control if necessary.

The REM indicator light will flash when the communications is enabled. The host can also turn the REM indicator full on as part of © the STATUS INPUT (PSW) command to inform the operator that the host is in control.

INSTRUMENT IDENTIFICATION

The specific type of digital communications circuitry provided in a Model CN-2000 Controller is indicated by the PART NUMBER.

DO = No digital communications

D1 = Analog remote set point (disables alarm #2) D2 = Non-isolated RS232C communications

D3 = Isolated RS232C communications

D4 = Non-isolated RS422 communications

D5 = tsolated RS422 communications

D6 = Isolated 20 mA current loop communications

For for CN2000 Controllers With Self Tune (AT) Option: EA No communications EB = Remote analog set point EC = RS232C non-isolated ED = RS232C isolated EE = RS422non-isolated EF = RS422 isolated EG = 20mAcurrent (isolated)

"

The communications circuitry is located on the middle circuit board of the electronic assembly. This board plugs into the front bezel assembly and connects to the rear ‘‘D'’ connector by means of a flexible flat ribbon cable that plugs into the bottom edge of the communications circuit board.

39

Page 45 read from a scan by OCR; it may hold reading errors

5.2

COMMUNICATIONS WIRING

The ‘‘D’’ Type (DB25S) 25-PIN digital communications connector located at the rear of the CN-2000 case is a standard Electronic Industries Associates (EIA) interface for RS232C. RS422 and 20mA current loop use the same connector.

Wiring to the Model CN-2000 is identical to that for any Data Terminal. Table 5-1 identifies each PIN by function. Sections 5.4, 5.5 and 5.6 provide the specific wiring for the three available interfaces.

- __ TABLE 5-1 CONNECTOR PIN DESIGNATIONS.

PIN MNEMONIC SIGNAL DESCRIPTION 1 GWG Protective In the RS232C environment this line pro- Ground vides a ground connection between devices. Although not required, may also be used for RS422 and 20 mA current loop configurations for the same purpose.

T™ Send Data Transmits data within RS232C voltage levels (+12 V and - - 12 V) or RS422 voltage levels (O and 5 V differential). Also used by the 2C mA current loop as 20 mA input (user supplied) for the transmit loop.

RX Receive Data Accepts data within RS232C or RS422 voltage levels or used by the 20 mA cur- rent loop as 20 mA input (user supplied) for the receive loop.

RTS Request to This line is normally held inactive by the Send CN-2000 until a message is ready to be sent. Then the line is switched active and the CN-2000 waits for the Clear To Send.

CTS Clearto Send This line must be made active by the host in order for the CN-2000 to send data unless handshake lines are inactive (see switch settings, paragraph 5.7).

DSR Data Set Ready Since the CN-2000 is a respond only device and does not initiate cor- respondence, the CN-2000 assumes that the host is ready to receive if the Clear To Send line is active, and does not monitor this line.

SG Signal Ground, This line provides a common signal connection for the RS232C environment. It is also used as a ground reference for the power supplied by user.

40

Page 46 read from a scan by OCR; it may hold reading errors

TABLE 5-1 (cont'd) CONNECTOR PIN DESIGNATIONS

PIN MNEMONIC SIGNAL DESCRIPTION 8 DTR DTR Return Return line for Data Terminal Ready signal (PIN 20) used with RS422 with hand- shake only. 9 +V Positive Voltage User must supply +12 V dc on this PIN if

1

14

16

18

20

25

CTS

TX - RTS - RX-

DTR

DSR using RS232C isolated configuration or

- +5 -V.de-if-using RS422 isolated con-- - - .

figuration. No connection otherwise.

Negative User must supply, 12 V dc on this PIN if Voltage using RS232C isolated configuration. No connection otherwise.

CTS Return Return line for Clear To Send signal (PIN

5) used with RS422. Also 20 mA current Loop return line for transmit loop.

Send Data Return line for Send Data signal (PIN 2)

Return used with RS422, Also 20 mA current loop return line for transmit loop.

Request to Return for Request To Send signal (PIN 4)

Send Return used only with RS422 with handshake.

Receive Data Return line for Receive Data signal (PIN 3) Return used with RS422 or 20 mA current loop on receive loop. Internally tied to Signal Ground (PIN 7) for RS232C operatons.

Data (Terminal) When handshake lines are used, this line Ready is always active telling the host to send data at any time. This line is in an undeter-mined state when handshake is not used.

Data Set Return line used for Data Set Ready Ready Return _ signal (PIN 6) used with RS422 with handshake only. NOTES

. All signals are named with respect to the originating unit.

. All undesignated PINS are to be left open.

. User must supply +12 Vde @ 125 mA on PIN 9, -12 Vdc @ 50 mA on PIN 10 referenced to ground on PIN 7 for isolatec| RS232C operation. For isolated RS422 operation, the user must supply +5 Vdc @ 150 mA on PIN 9 referenced to ground on PIN 7.

41

Page 47 read from a scan by OCR; it may hold reading errors

5.3 HANDSHAKE OPTION

The Model CN-2000 digital communications includes provision for the full handshake selection for use in RS232C and R'5422 interfaces. To enable handshake for these interfaces, set the S2 switch number 4 “ON”. (Refer to paragraph 5.7.) Four signal leads are used.

PIN 4 RTS PIN 5 CTS PIN6 DSR PIN20 DTR “The RS422 also requires return tines. PINiI6 RTS PIN 12 CTS PIN25 OSR PIN8 DTR

Request to Send

Clear to Send

Data Set Ready Data (Terminal) Ready

Request to Send Return Clear to Send Return

Data Set Ready Return

Data (Terminal) Ready Return

Interface diagrams (Sections 5.5 and 5.6) shown are suggestion only. There are several alternate wiring configurations depending on the host. It is essential to compare the host or modem requirements with the CN-2000 pin designations (Section 5.3) before connecting the system.

If handshake is not required or if these signals are not compatible with the host computer, the $2 switch number 4 MUST be ‘‘OFF’’. Hand-shaking cannot be used for any 20 mA Current Loop interface or for Drop Line RS422 configurations.

5.4 RS232C INTERFACE (See Figures 5-1 and 5-2)

Ground

Send Data Receive Data Signal Ground

Ground

Send Data Receive Data Signal Ground

Figure 5-1. RS232C Half/Fult Duplex Without Handshake

Ground

Send Data Receive Data Request to Send Clear to Send Data Set Ready Data Ready Signal Ground

2000

1 2 3 4 5 6 20 7

HOST wevevevervewe

Ground Send Data Receive Data

Determined by host requirements

Signal “round

Figure 5-2. RS232C Half/Full Duplex With Handshake

42

Page 48 read from a scan by OCR; it may hold reading errors

5

Request to Send

Send Data

Receive Data

Send Data Return Receive Data Return

RS422 INTERFACE (See Figures 5-3 and 5-4.)

Send Data

Receive Data

Send Data Return Receive Data Return

Figure 5-3. RS422 Half/Full Duplex Without Handshake

Send Data Receive Data

Clear to Send

Data Set Ready

Data Ready

Send Data Return Receive Data Return Request to Send Return Clear to Send Return Data Set Ready Return

Data Ready Return

2000 HOST 2 mal ) Send Data 3 () Receive Data 4 2 Ao Cee cn 5 > air ) Determined by 6 r> a () host requirements 20 () 14 () Send Data Return 18 Par ) Receive Data Return 16 > ar ) 11 t ) Determined by 25 > a host requirements e () LJ UL)

Figure 5-4. RS422 Half/Full Duplex With Handshake

The RS422 driver is shown in Figure 5-5. Be sure the host RS422 driver conforms or it will be necessary to swap connections between all signals and their respective return lines to correct polarity, i.e., Pins

2 and 14, Pins 3 and 18, etc.

+ Signal

- Return

Figure 5-5. RS422 Driver

RS422 may be drop line configured to enable the host to talk to several CN-2000 units through one port as shown in Figure 5-6.

HOST

NOTE:

2000

Send Data 2 Receive Data

Send Return 14 Receive Return 18 Send Data 2 Receive Data 3 Send Return 14 Receive Return 18 Send Data 2 Receive Data 3 Send Return 14 Receive Return 18

() () () ( )

Send Data (TX +)

Receive Data (RX +)

Send Data Return (TX -) Receive Data Return (RX -)

HANDSHAKE LINE SWITCH MUST BE OFF

Figure 5-6. Several CN-2000 Units in Conjunction With One Host

43

See

Page 49 read from a scan by OCR; it may hold reading errors

5.6 20 mA CURRENT LOOP INTERFACE (See Figures 5-7 through 5-10}

2000 HOST 2000 HOST oh t@= mye Transmit * 14 ( ) Transmit * "i ( ) =r ; qe . +13 () ive +13 () Receive, 18 () Receive lie 6) I

Figure 5-7. Full Duplex 4-Wire Figure 5-8. Half Duplex 2-Wire Connections Connections

- 2000 “HOST.

Se ye BOO OST re Thm Tr] Or Transmit * ve C) ® 3 Transmit * i, 3 A 3 FL oF 2@s ve +3 + ttOR Receive ly, ( ) __ Receive - [28] ‘cue La 2000 2000 .. +{ 2 t atl? Ee Transmit _ 14 a ransmit 14-5 Receive +] 3 Receive 3 -[8 "] 28] | 4

Figure 5-9. Half Duplex 2-Wire Chaining Figure 5-10. Full Duplex 4-Wire Chaining of Several CN-2000 Controllers of Several CN-2000 Controllers

NOTES

1. Symbol A indicates 20 mA current source provided by others.

2. Less than 2.3 V (Transmit) and 1.0 V (Receive) drop across contacts while marking.

3. Maximum voltage that can be applied across Transmitter or Receiver Terminals is 24 V. Maximum current is 30 mA.

5.7 FORMAT SELECTION SWITCHES

Format selector switches mounted on the communications circuit board inside the Model CN-2000 Controller allow the user to select Parity, Baud Rate and Unit Address to fit the application (see Figure 5-11). The switch options are: PARITY: Even, odd or no parity (factory set at NO PARITY) BAUD RATE: 300, 600, 1200 or 2400 (factory set at 1200) UNIT ADDRESS: Oto 63 (factory set at ADDRESS 00) HANDSHAKE: YES or NO (factory set at NO HANDSHAKE)

44

Page 50 read from a scan by OCR; it may hold reading errors

To access these switches, turn power to the Mode! CN-2000 Controller OFF. Press in the tabs on each side of the front bezel and pull the electronic assembly forward enough to expose the switches. DO NOT REMOVE the assembly from the case.

Carefully note the type of switch action. Rocker switch action is push in to activate. Slider switch action is slid up or down to activate. Follow the markings on the switch for the correct switch position for ON (CLOSED, HI, 1) or OFF (OPEN, LO, 0). Use a pencil or pen tip to set desired switch position. Each unused switch MUST be in the OFF position.

eTiLTTITE) LETTE TT |»

COMMUNICATIONS Ul BOARD

1234567 8 1 23 4 5 6 7 8

| aa PARITY HANDSHAK§ BAUD RATE UNIT ADDRESS sz] 2 | 3 s2| 4 s2} 5 }6]7]8 $1 ]3 4445 16} 748 NONE | OFF |OFF NO | OFF 300 | ON | ON JOFF OFF] {VALUE |32}1618 |4 | 211 ODD | ON jOFF YES| ON 600 | OFF [OFF | OFF | ON EVEN | ON | ON 1200 | OFF |OFF} ON | OFF 2400 | ON [OFF | OFF | ON ALL UNUSED SWITCHES MUST BE SET ‘‘OFF’’ Figure 5-11. Format Selection Switches 5.8 PROGRAMMING 5.8.1. Asynchronous Serial Data Format

The DATA WORD consists of one ASCII character, i.e., two hexadecimal characters plus one start bit and two stop bits. The number of incoming stop bits is not critical. The CN-2000 can accept any number of stop bits. The CN-2000 will always respond with two stop bits. The MSB of the data bits is the parity bit. When parity is not used the MSB must be OFF. (See Figure 5-12.)

45.