Page 61
6.5
A flashing digit will appear at the first digit position. The digit that is flashing can be changed by using the arrow keys. The PARAM DISPLAY key advances the flashing digit and the LAST key backs up the digit. You can change any of the part numbers within the rules stated in paragraph 6.3. Be very careful not to enter an illegal part number.
If you are recovering from the DATA LOST mode be sure to enter the complete part number. When the part number is correct push the PARAM DISPLAY key until the next display appears.
Figure 6-3. Setting the Part Number
SETTING THE DISPLAYED UNITS (ALSO CONVERTING FROM °C TO °F)
The controller will accept any 2 alphanumeric characters for displayed units. The only limitation is that the temperature F or C units MUST be in the right hand position.
UNITS UU The best way to see how units are set is to push the TIME H:m| 2frow key while watching the display. All numbers and : letters are available in both positions. UNITS setting starts with the left hand digit. Push the PARAM DISPLAY key to move to the right hand digit. LAST key will back up right to left if needed. The DOWN key will scroll the digit reverse to the UP key. A blank is available in the sequence for single character units. The left hand position can be a blank. Push PARAM DISPLAY key when units are correct.
IMPORTANT NOTE: Changing units between F and C does not change the numerical values of any set points, alarms, or span limits. Each set point, alarm and span limit must be individually changed to correspond to the new units of measurement. When no units are specified the controller uses the degree C linearization table for thermocouple or RTD input.
56
“ita
Page 62
6.6
6.7
In order to convert from °C (centigrade) to °F (fahrenheit), follow the directions to get into the CAL loop.
1. In the CAL loop when the part number is displayed, press the PARAM CHECK key. 2. Controller then displays UNITS C
TIME H:M
3. The temperature units of measure are two digits long, where the first digit is blank. The first digit is always to be left blank. Press the letter.
PARAM CHECK key to move to the second digit in order to change _
Press the UP arrow three times until F is displayed.
Press the PARM CHECK key until display reads CAL COMPLETE. Press RETURN key.
The CN2000 unit is now converted from °C to °F.
NO 1
SETTING THE TIME BASE
A time base must be selected when a TIMER alarm is included.
UNITS UU You can select Hours:Minutes (H:M) or Minutes: TIME H:M Seconds (M:S) for the time base. Push the NO key to : change the selection. When the time base is correct push the PARAM DISPLAY key to advance to the next display.
SETTING THE SPAN
LO SPAN The next two displays are LO and HI SPAN, SPAN is XXXX UU the LO and HI limits outside of which the system is not to operate. The controller automatically limits all set points and alarms to be within this SPAN.
HI SPAN The controller stores in permanent memory the max- XXXX Uy} imum allowable spans for all listed thermocouple and RTD inputs. Unless ordered otherwise, the maximum span will appear on these displays. You can select any span up to the stored limits for thermocouple and RTD inputs. For certain thermocouples higher limits may be included. Push the UP arrow key to read the maximum programmed limit.
Process type inputs are limited to any span between, 3200 and +3200 units. You can assign any display value to the LO SPAN and H! SPAN within these limits and the controller will automatically linearize all values in between. Use the UP and DOWN arrow keys to change values. Advance from LO to HI SPAN using the PARAM DISPLAY key. The LAST Key will back up from HI! to LO SPAN. Both direct and reverse spans are allowable.
57
Page 63
6.8
6.9
6.10
CONFIGURATION calibration for controllers with thermocouple or RTD input is now complete. If you have this type of controller proceed to paragraph 6.10.
If you have a process input controller, three more displays are available. Push the PARAM DISPLAY key and proceed to paragraph 6.8.
SETTING THE DECIMAL POINT
This display allows the selection of decimal point posi- DECIMAL . - : : we PLACES x|_ tion from zero (no decimal point) to third position from
‘to select decimal point position. When decimal position is correct push the PARAM DISPLAY key to advance to the next display.
SETTING THE DISPLAY RANGE
LO VAL This display is used to program the desired display in- XXXX UU dication at minimum input. For example: LO VAL can be set to indicate O for a 4 mA input level. After setting the desired reading using the arrow keys, press the PARAM key.
HI VAL This display is used to program the desired display in- XXXX UU dication at maximum input. For example: HI VAL can be set to indicate 2000 for a 20 mA input level.
The LO VAL/HI VAL procedure is the electronic equivalent of changing the scale in an analog panel meter. No input reference calibration is required. You can change the displayed range purely through the keypad when a process signal such as 4-20 mA is the input.
REFERENCE CALIBRATION
At this point in the calibration program the CONFIGURATION calibration has been completed. Three situations may exist.
a) You have completed what you need to do and wish to return the controller to use. Push the PARAM DISPLAY key and proceed to paragraph 6.15.
b) The controller will not advance when you push the PARAM DISPLAY key. Proceed with the following instructions. This occurs usually when calibrating after a DATA LOST/PLEASE CAL.
c) You wish to perform a REFERENCE calibration. Proceed with the following instructions.
58
_ the rightfie,, 0.783). Use the UP or DOWN arrow keys...
Page 64
ENTRY INTO THE REFERENCE CALIBRATION ROUTINE WITHOUT PROPER CALIBRATION EQUIPMENT MAY ERASE THE FACTORY CALIBRATION. DO NOT PROCEED WITH THESE INSTRUCTIONS UNTIL YOU ARE PROPERLY PREPARED.
REFERENCE calibration refers to the procedure for calibrating the controller to an external input reference source. Before starting a reference -calibration -you-must-be-at-one of these displays.- - -
HI! SPAN or HI VAL XXX UU XXX UU
If you are not at one of these displays and wish to do a REFERENCE calibration push the PARAM DISPLAY key until ‘‘CAL COMPLETE” appears. Then push the LAST key once.
A security code protects the reference calibration procedures. To enter the reference calibration mode push the two keys indicated in Figure 6-4 simultaneously.
|
Figure 6-4. Entering the Reference Calibration
CAUTION
ALLOW AT LEAST A 20 MINUTE WARMUP BEFORE ANY REFERENCE CALIBRATION IS ATTEMPTED.
There are three stored calibration routines. The controller will automatically display the correct instructions for your application.
6.11. Thermocouple Input Calibration 6.12 RTD Input Calibration 6.13 Process input Calibration
59
Page 65
6.11 THERMOCOUPLE CALIBRATION
All thermocouple input controllers are calibrated in the same manner. A 50.000 +.005 mV source, anda type J thermocouple in an Ice Bath or equivalent simulator are required.
IMPORTANT NOTE: A cold junction compensator resistor is provided at the rear terminals of each thermocouple input controller. Calibration of thermocouple units MUST be done with the specific compensator to be used in the final installation. All therrnocouple input controllers are calibrated with a type J thermocouple.
INPUT | 50.000 mV
J T/C IN ICE BATH
This display indicates:that~a stable, precision distortion-free +50.000 mV DC calibration source be connected to rear case terminals F ( - ) and H (+). Allow a 2 minute interval for the source input to stabilize with the +50.000 mV applied and then push the PARAM DISPLAY key,
Without removing the AC power, change the input to a J T/C in Ice Bath or to its equivalent from a calibration device. Allow a 2 minute interval for the input to stabilize and then push the PARAM DISPLAY key. Proceed to paragraph 6.15.
6.12 RTD CALIBRATION
INPUT 100 OHMS
INPUT 300 OHMS
RTD input controllers should be calibrated using a Precision decade resistance box. Be sure to use short, low resistance leads and good tight connections. Three wire connections to the input are required to minimize lead resistance errors. All wires must be the Same gauge and length.
This display is the first step for RTD calibration. Connect the RTD calibrator and set for 100.00 +.05 ohms. Allow a 2 minute interval for the source to stabilize and then push the PARAM DISPLAY key.
Set the RTD calibrator for 300.00 +.05 ohms. Allow a 2 minute interval for the source to stabilize and then push the PARAM DISPLAY key. For controllers with 0.1 RTD resolution, different inputs may be specified. Follow the instructions provided on the display. Push PARAM DISPLAY key and proceed to paragraph 6.15,
60
Page 66
6.13
6.14
PROCESS CALIBRATION
An appropriate voltage or current source is required for process input calibration.
INPUT LO CAL
INPUT HI CAL
This display is the first step for process input calibration. Connect the calibrator and set its output to the LO calibration value. With a 4-20 mA input the LO CAL would be 4 mA. Allow a 2 minute interval for the source to stabilize and then push the PARAM DISPLAY key.
Adjust the calibrator to output the HI calibration value.
With a 4-20 mA input the HI CAL would be 20 mA. Allow a 2 minute interval for the source to stabilize and then push the PARAM DISPLAY key. Proceed to paragraph 6.15.
REMOTE SETPOINT CALIBRATION
REMOTE SETPOINT Input can be used in any controller that has been provided with this option. Perform all other calibrations proceeding with this calibration.
To calibrate the REMOTE SETPOINT Input enter the reference calibration program as described in paragraph 6.10 and advance to the following using the PARAM DISPLAY key.
INPUT LO REMSP
Connect the remote voltage or current source to terminals B (+) and F ( - ) or use the internal + 2.45 VDC across terminals C and F to power aremote 10K ohm potentiometer with arm connected to terminal B.
Set the input source to the LO INPUT value that is to correspond to the LO SPAN value previously established. Wait 2 minutes for the system to stabilize and then push the PARAM DISPLAY key.
INPUT
Hi REMSP
Set the input source to the HI INPUT value that is to correspond to the HI SPAN value previously established. Wait 2 minutes for the system to stabilize and then push the PARAM DISPLAY key. Proceed to paragraph 6.15.
61 re
Page 67
6.15
CALIBRATION COMPLETE
CAL This is the final display in the calibration program.
When at this display you must push the RETURN key
COMPLETE to enter and store all calibration data. THIS STEP IS
CRITICAL. All the changes and references calibration are not valid until this step is completed. When you push the RETURN key the controller returns to the OPERATOR mode and the CAL indicator goes out.
You can now remove the calibrator and return the controller to its nor-matinstallation.---
SECTION 7 SERVICE INFORMATION & TROUBLESHOOTING
7A
7.2
MAINTENANCE Some simple preventative steps will help assure optimum performance:
© Keep controller fairly clean and protected from ciirt, oil and corrosion. * Periodically recheck all electrical connections. ¢ Allow at least 5 minutes for warm-up before starting operation.
© Clean keypad and display with a soft, damp cloth. Solvents or chem-cal cleaners should not be used.
If you experience difficulty with a controller, first check all wiring. Also pull the electronic assembly foward out of the case enough to check that all circuit boards and plug-in components are snugly-in their connectors.
Check that the correct key sequence has been used and that the set points and tuning values set into the controller are appropriate to the application.
DIAGNOSTIC DISPLAYS
The controller contains several self-diagnosis programs that will display an appropriate warning when necessary. When any of these displays appear the control output(s) go OFF and the alarm(s) go ON.
INPUT This display indicates that the input is an open circuit OPEN and must be corrected before proceeding.
POWER This display will appear if the AC voltage to the con- FAILURE troller drops below specification to a low voltage level.
Check the AC voltage level and correct if necessary.
62 ta,
Page 68
RTC FAILURE If either of these displays appear, try switching the AC power ON or OFF to the controller. If the indication RAM stays the same, the controller must be serviced by FAILURE authorized personnel. DATA This flashing display indicates that for some reason the LOST controller calibration has been lost. This is an error alarm that prevents the controller from continuing to PLEASE operate after an error is detected in its internal memory. CAL When this display appears the controller shuts down: ~~ Recalibration is a quick and easy procedure which is fully explained in Section 6. 7.3 TROUBLESHOOTING
The troubleshooting information in Table 7-1 is included to serve as a guide to enable equipment repair. It is a guide only, and cannot cover all possible contingencies that may occur.
SYMPTOM
1. Power applied, display does not light and controlier does not operate.
No power to load. Measurement in- dicates temperature below set point. Output indicator is on continuously.
. Erratic control.
TABLE 7-1
TROUBLESHOOTING GUIDE PROBABLE CAUSE CORRECTIVE ACTION
No power applied to controller.
Check power wiring and fusing.
Check if controller is properly engaged in housing.
Controller not engaged properly in housing.
Open connection to load.
Check load wiring, fuses, and connections.
Cycle time is too long. Reduce cycle time. When. using elec- tromechanical relay or contactor, set cycle time at value just below point where load cy- cling occurs.
Proportional band is too narrow.
Widen P.B. adjustment until load cycling is eliminated.
63
Page 69
SYMPTOM
4. Controller operating but temperature not at set point and call- ing for 100% power.
TABLE 7-1 (cont’d)
PROBABLE CAUSE
Rate time is too short.
Controller not warmed up.
Improper sizing of heater to load.
5. Display shows input open.
6. Inability to tune con- troller properly.
7. Slow response to set point or load change with tuned controller.
8. Large overshoot on SP or load change.
9. Stepwise response to set point or load changes.
Thermocouple or input Circuit open.
On controllers with dual three mode outputs, resets and rates for both outputs must be set to zero before beginning the tuning procedure.
Cycle time is set too long.
Reset time is too short.
Reset time is set too long.
Rate time is set too long.
64
CORRECTIVE ACTION
Increase rate time adjustment.
Wait five minutes for controller to stabilize.
Higher wattage heaters
__.are required,
Check thermocouple and extension wire for open circuits.
In tuning procedure outlined previously, the rate and reset ad- justments are set to zero (turned off).
Reduce cycle time.
Increase the resets/minute (R/M) and recheck response by making a small set point change.
Decrease the reset (R/M) and recheck response by making a small set point change.
Decrease rate time set- ting and recheck response by making a small set point change.
Page 70
SECTION 8 REMOTE START/STOP
81
8.2
The following information pertains to the Remote Start/Stop option for the CN2000 Series Controller. This option is available in two (2) formats: D7 (using terminals B and C, and disables alarm 2) or D7DE (using terminals D and E, and disables output 2).
The remote/start option provides for start/stop control of the unit from a remote location. The start/stop key pad on the CN2000 Series unit remains active and this function may be controlled either from the front panel or the remote location. Units may be alternatively configured for remote actuation from a dry circuit contact closure.
WIRING
The connections for remote start/stop are through terminals D & E or B & C on the rear terminal strip. Refer to Figure 2-6. Polarity is not important for dry circuit contact closure. The dry circuit contacts are assumed to either a normally open push button or a normaily open relay contact suitable for low voltage operation.
OPERATION
Operation of the remote start/stop circuit is actuated by a contact closure as shown in Figure 8-1. A momentary contact across Terminals Band C (for option D7) or D and E (for option D7DE) is all that is required. The contact must remain closed for a minimum duration of 100 milliseconds to ensure that the controller will recognize the input signal to change state between start and stop.
MOMENTARY CONTACT
=O
©
Figure 8-1. Remote Start/Stop Wiring Diagram
65