Manual · Datalogic
CM52 Remote I/O Interface Module Operator's Manual
Manual116 pagesPDF 886 KB
Operator's manual for the Escort Memory Systems CM52 Remote I/O interface module linking Allen-Bradley Remote I/O to RFID equipment.
Covers · 1 model
The models it covers
Summary
What is in it
Operator's manual for the CM52 Remote I/O interface module from Escort Memory Systems (a Datalogic Group company), which connects an Allen-Bradley Remote I/O network to EMS RFID antennas, reader/writers, serial devices and bar code scanners. It covers dimensions, connectors and pinouts, internal switches and jumpers, LED indicators, device addressing, PLC memory mapping, the command protocol and every command by opcode, with specifications in an appendix.
Its parts
- Introduction
- Installation
- Remote I/O Interface
From the manual
Key facts from this manual
Each line names its page in the PDF.
Operator's manual for the Escort Memory Systems CM52 Remote I/O Interface Module, which links Allen-Bradley PLCs on the Remote I/O network to RFID antennas, RFID reader/writers, serial devices and bar code scanners. It covers mounting, wiring, cables and bus termination, DIP switches and jumpers, LED indicators, Remote I/O addressing and the command set, with specifications in an appendix.
- Device
- Programmable interface between the Allen-Bradley Remote I/O network and EMS RFID equipment or third party products; a Remote I/O slave device p. 7
- Connects to
- Two HS/HL500-Series antennas, two HMS8xx series antennas, two serial ports, and up to 32 HMS-Series reader/writers, RS-Series read only antennas or bar code scanners on an RS485 MUX32 line p. 7
- Power
- 24 VDC (+/-15%) from an external supply; 350 mA module only, 900 mA with antennas p. 7, 113
- Serial ports
- COM1 RS232 on a DB9 (pin 2 TX, pin 3 RX, pin 5 signal ground); COM2 RS232/RS422/RS485 (MUX32), selected with jumper J7 p. 11, 19, 113
- Inputs and outputs
- Two industrial-level inputs, 10-30 Vdc; two industrial-level outputs, 5-30 Vdc (400 mA, sinking) p. 113
- Remote I/O speed
- 57.6K, 115.2K or 230.4K bits per second, set with DIP switches p. 7, 16
- Processors
- Node adapter chip, RF coprocessor and 386EX main processor; up to four tasks at once; 16K buffer per task p. 8
- Tag transfer
- 3000 bytes per second to or from HS-Series tags; up to 20 inches antenna to tag with long range HS tags p. 8
- Size and weight
- 2.00 x 7.50 x 6.00 inches (L x W x H); 2.0 lb. (0.9 kg); EMI shielded ABS shell p. 113
- Temperature
- Operating +32 to 122 degrees F (0 to 50 degrees C); storage -4 to 158 degrees F (-20 to 70 degrees C); 90% non-condensing humidity p. 113
- Enclosure and mounting
- NEMA 2 (IP31); DIN rail mountable with optional clips (00-1096) p. 7, 113
- Remote I/O cable
- 1770-CD (Belden 9463); daisy chain up to 3,048 m (10,000 ft) at 57.6 kbps, 1,524 m (5,000 ft) at 115.2 kbps, 762 m (2,500 ft) at 230.4 kbps p. 13
- Factory switch settings
- All switches off: rack address 0, group address 0, 57.6 Kbps, not last rack, quarter rack, no banner p. 18
- Serial defaults
- COM2 RS232, 9600, n, 8, 1; COM1 RS232, typically 9600 baud p. 43
What this manual walks you through
- Mounting dimensions and the DIN rail clip p. 9, 10
- Wiring the Remote I/O connector and the COM1 DB9 p. 11
- Opening the module to reach the internal terminal blocks p. 12
- Remote I/O cable lengths and terminating the bus p. 13
- Setting rack address, starting quarter, baud rate, last rack, rack size and banner switches p. 14, 15, 16, 17
- Setting jumper J7 for RS232, RS485/MUX32 or RS422 on COM2 p. 19
- Reading the LED indicators and the Bus Active LED p. 20, 21
- Remote I/O addressing by rack and group p. 22, 23
- Command timeouts and the Done and Error flags p. 29
- Command opcode quick reference p. 111, 112
Good to know
- Turn off power and follow ESD procedures before opening the module. p. 12
- The first slot cannot hold input or output data in CM52 racks. p. 35
- A half-rack CM52 cannot start at the fourth quarter; it moves to the third quarter. p. 16
- Missing or wrong terminating resistors cause frequent bus retries, especially above 57.6 Kbps. p. 21
- A MUX32 Write carries at most 58 data bytes in one block transfer. p. 35
Questions this manual answers
Why is the Bus Active LED off on my CM52?
The bus processor is not initialized, no valid frames arrive, or communications timed out. Check for reversed Line 1 and Line 2 wires, a wrong data rate or a wrong link address. p. 21
What are the CM52 factory switch settings?
All switches off: rack address 0, group address 0, 57.6 Kbps, not the last rack, quarter rack and no banner display. p. 18
How long can the CM52 Remote I/O cable be?
With 1770-CD (Belden 9463) cable in a daisy chain: 3,048 m (10,000 ft) at 57.6 kbps, 1,524 m (5,000 ft) at 115.2 kbps, 762 m (2,500 ft) at 230.4 kbps. p. 13
What does the Error bit mean on the CM52?
The CM52 found an incorrect parameter or command format; it also sets the Done bit. p. 29
How do I switch CM52 COM2 to RS485 or RS422?
Set jumper J7 on the controller board as the manual shows; the default is RS232. Serial parameters and wiring must match too. p. 19
The whole text · 12 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file