Interface Units
An optional DC-to-DC converter provides isolated DC power for photoeyes and a tachometer. Isolated +12 and +5 volts DC and ground terminals are available on terminal block TB5. Using these voltages and the opto-isolated inputs will provide total isolation.
Programmable Interface Controller Inputs Standard inputs 4-8 are used for height sensing. When used, the least significant height is connected to input 4 of the Interface Unit(s).
Optional Input Relay Modules As many as eight optional solid-state input relay modules can be used to accommodate AC input signals. Refer to “Relays in the Interface Units” on page 3-14 for more information.
Control Output Connections Eight solid-state open-collector control outputs are available at terminal block TB1 on the main printed circuit board, to operate relays, alarms, diverters, etc. Connector assignments are listed in Table 3–2, “Interface Unit I/O Connections - TB1,” on page 3-17. Refer to Figure 3–8, “Typical Solid State Output Circuit” on page 3-10. By default, three of the outputs are assigned to output NO READ, MATCH and NO MATCH signals, as specified Table 3–2, “Interface Unit I/O Connections - TB1,” on page 3-17. The assignments are shown in parentheses in the table. A custom C program or the Setup parameters may be used to override the default assignments. As many as seven optional solid-state output relay modules, and one form C (SPDT) electromechanical relay, are available to switch AC voltages. Refer to “Relays in the Interface Units” on page 3-14 for more information.
Special Inputs & Outputs Laser Control A digital low or switch closure to ground on this input will turn the laser On or Off, depending upon how a jumper inside the scanner was configured at the factory. The default position of jumper JH2 is between pins 1 and 2. This is referred to as a normal laser control. With no connection, or logical high on the input laser control, the laser will be On. A ground or logical low on laser control input causes the laser to turn Off. Moving the jumper to position 2 to 3 causes this function to be reversed and referred to as an inverted laser control.
Rev F, February 2002
CiMAX 75xxA/76xx Scanner Technical Reference Manual
3-9
3
Controls, Connectors, & Indicators
Up to seven additional low-voltage DC inputs are available at terminal block J2 on an optional Programmable Interface Controller, as shown in Figure 3–12, “Programmable Interface Controller Board” on page 3-14. The inzone photoeye is connected to input 8 of the Programmable Interface Controller. The extra height photoeyes are connected to inputs 1 - 7 of the Programmable Interface Controller, with lowest input connected to input 1 of the Programmable Interface Controller. On the leading edge of inzone, the peak-detected state of the 7 inputs, the highest number of photoeyes blocked since the last inzone, are sent serially to the scanner. They permit additional height sensing, for better resolution of height and corresponding better accuracy for x, y positioning to allow smaller gaps between boxes.
Page 50
Chapter
3
Controls, Connectors, & Indicators
Beeper The Beeper output is an open collector output providing an audio tone to signal the operator each time that the scanner has read a label. By default, Output 4 is used to drive the beeper. Jumper JH6 in the Standard Interface Unit is used to connect Output 4 to the beeper. For beeper operation, position JH6 across pins 2 and 3. Refer to Figure 3–10, “Standard Interface Unit Circuit Board” on page 3-12 which shows the location of JH6. To use Output 4 as a general purpose output: 1.
Place the JH6 jumper across pins 1 and 2.
2.
Set parameter 003 IOMODE to +16 to disable the beeper. Refer to the Scanner Parameters Reference Guide for more information.
Communications Inputs & Outputs Host and SETUP port connections are available on terminal block TB1. Terminal assignments for these ports are shown in Table 3–2, “Interface Unit I/O Connections - TB1,” on page 3-17.
DC Power Outputs Terminal block TB1 also provides several non-isolated low voltage DC outputs for powering external sensors, as well as associated ground connections. The ratings of the DC outputs are shown in Table 3–2, “Interface Unit I/O Connections - TB1,” on page 3-17.
Solid State Input & Output Circuits Figure 3–8 and Figure 3–9 show typical Solid State Input and Output Circuits. FIGURE 3–8. Typical Solid State Output Circuit
3-10
CiMAX 75xxA/76xx Scanner Technical Reference Manual
Rev F, February 2002
Page 51
Interface Units
FIGURE 3–9. Typical Solid State Input Circuit
+12 VDC
10K Ohms Scanner input active low when input < 1.0 volts
Rev F, February 2002
3
0.1 µf
CiMAX 75xxA/76xx Scanner Technical Reference Manual
Controls, Connectors, & Indicators
Maximum input voltage 30 VDC, 27 VDC continuous
ULN2003
3-11
Page 52
Chapter
3
Controls, Connectors, & Indicators
Standard Interface Unit Circuit Board FIGURE 3–10. Standard Interface Unit Circuit Board
3-12
CiMAX 75xxA/76xx Scanner Technical Reference Manual
Rev F, February 2002
Page 53
Interface Units
Hex Interface Unit Circuit Board FIGURE 3–11. Hex Interface Unit Circuit Board
Controls, Connectors, & Indicators
3
Rev F, February 2002
CiMAX 75xxA/76xx Scanner Technical Reference Manual
3-13
Page 54
Chapter
3
Controls, Connectors, & Indicators
Programmable Interface Controller Board FIGURE 3–12. Programmable Interface Controller Board
Relays in the Interface Units Standard Interface Unit Optional output relay modules can be plugged into locations K1 through K7. Standard Opto-22 style solid state output relay modules with several different AC and DC voltage and power ratings can be provided to fit your application. You can use these relays to operate divert gates, for example. Optional input relay modules can be plugged in to locations K1 through K5. Relay modules with several different AC and DC voltage and power ratings can be provided to fit your application. Position the jumpers associated with relay modules JH1-JH5 to: •
IN when an input relay is used, as shown in Figure 3–13
•
OUT when an output relay is used, as shown in Figure 3–14
•
OUT when no module is used
FIGURE 3–13. JH1-5 Jumper Setting for Input Relays
JHX OUT ____ IN
3-14
CiMAX 75xxA/76xx Scanner Technical Reference Manual
Rev F, February 2002
Page 55
Interface Units
FIGURE 3–14. JH1-5 Jumper Setting for Output Relays
JHX OUT ____ IN
Hex Interface Unit JH18 through JH22 are used to isolate inputs 4 - 8 from the three scanners attached to the top three positions (D-F) of the Hex Interface Unit. Normal operation requires that these shunts be installed in the 1-2 position. This will insure that these inputs are connected to all six scanners the same way. If this interface box is used side scanning, then the inputs 4 - 8 will be connected to proximity sensors that detect which side of the conveyor a box may be positioned. Three scanners will be connected to the lower three positions (A - C) and the scanners on the other side of the conveyor will be connected to the top three positions (D - F). The proximity information should be in reverse order from the lower three scanners. This is accomplished by moving shunts JH18 through JH22 to the 2 - 3 position. For example, if five proximity sensors are used, install 22 AWG wire between TB1 AND TB11 (IN4-IN8A, IN5-IN7A, IN6-IN6A, IN7-IN5A, IN8-IN4A).
Typical Relay Wiring Examples FIGURE 3–15. Open Collector Output Operating an External Relay +V to match coil requirements (supplied by user) 1N4003 or similar diode TB1
Output 1
Relay contacts to switch load
NOTE: A separate supply is required for relay coils with voltage ratings other than 12V.
To user ground GND
Scanner
Rev F, February 2002
Interface Unit
CiMAX 75xxA/76xx Scanner Technical Reference Manual
3-15
3
Controls, Connectors, & Indicators
K8 is an electro-mechanical relay containing one set of normally open (NO) and normally closed (NC) contacts. You can use K8 to accomplish logic functions with AC line voltage. For example, relays in series can be used to implement the AND logic function. This relay provides contacts that remain open, and contacts that remain closed, when the power is OFF.
Page 56
Chapter
3
Controls, Connectors, & Indicators
FIGURE 3–16. Solid State Output Relay +12 VDC
TB2 Line
4.7K
Solid state Output relay module (OAC12)
K1
Hot
K1 IN
Divert Gate Power
K1 OUT
Load Divert Gate
Neutral
Interface Unit
Scanner
FIGURE 3–17. K-8 Electro-Mechanical Relay Connection
TB2
TB1 +12V
+24 VDC K8 to Scanner
K8-NO
24 VDC ground
LOAD K8-COM screw 15
K8-NC
C-NO: Normally open contact C-NC: Normally closed contact
Interface Unit FIGURE 3–18. Solid State Input Relay Module
TB1
TB2
Divert Control Relay
K1 to Scanner Input
K1 IN
Input
Divert Gate
Solid state input relay module (IAC15)
Divert Gate Power
K1 OUT
Interface Unit
3-16
CiMAX 75xxA/76xx Scanner Technical Reference Manual
Rev F, February 2002