Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeEnglishEspañolContact
Page 1 of DP2000-P, DP9000-P Process Indicators

Manual · Omega

DP2000-P, DP9000-P Process Indicators

Manual60 pagesPDF 1.9 MB

User manual for the Omega DP2000-P and DP9000-P process indicator panel meters and their BSCP process signal conditioner.

Download the PDF1.9 MB

Covers · 1 model

The models it covers

Summary

What is in it

The user manual for the Omega DP2000-P and DP9000-P process indicators, 1/8 DIN digital panel meters with LED or LCD displays. It gives safety notes, specifications, panel mounting, power and signal connections, configuration procedures and charts, tests and diagnostics for the DP2000 and DP9000 main assemblies, then the BSCP signal conditioner that scales process current and voltage inputs, with its calibration and installation instructions. The text was read from a scan.

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

This OMEGA manual covers the DP2000 and DP9000 digital panel meter main assemblies together with the BSCP process signal conditioner (DP2000-P and DP9000-P). It gives specifications, panel mounting, power and signal wiring, jumper settings for the decimal point and input ranges, connector pin assignments and calibration steps.

Read for this summary: pages 1 to 18, 34 to 38, 52 and 56 to 57 of 60.

Device
Digital panel meter in a 1/8 DIN case: main assembly, signal conditioner and optional interface boards p. 5
LED models
DP20, DP22, DP24, DP26, DP28 p. 5
LCD models
DP21, DP23, DP25, DP27, DP29 p. 5
Power versions
120 Vac, 240 Vac, 9-32 Vdc and 24 Vac main assemblies p. 5
Process input
BSCP conditioner: current spans 1 to 50 mA FS, voltage spans 0.5 to 20 V FS p. 34
Readout range
DP2000-P: -1999 to +1999 p. 35
Voltage ranges
0.5, 1.0, 2.0, 5.0, 10.0 and 20.0 V full scale; 250 Vp maximum p. 35
Current ranges
1.0, 2.0, 5.0, 10.0, 20.0 and 50.0 mA full scale, 0.5 V drop at full scale p. 35
Input type
Single-ended, bipolar, meter ground common to input LO p. 34
Warmup
Less than 10 minutes to rated accuracy p. 35
Signal terminals
TB1 terminal 5 signal LO, terminal 6 signal HI, terminal 4 no connection p. 36
Power terminals
Terminals 1, 2 and 3 of TB1; AC wires black (HI), white (neutral), green (ground) p. 9, 37
Panel cutout
3.622 x 1.772 in; panel up to .25 in thick p. 15
Internal power
50 mA maximum available from all internal sources p. 14

What this manual walks you through

  • Mounting the meter in a panel cutout p. 8, 56
  • Wiring power and signal input terminals p. 9
  • Setting the decimal point with jumpers or the J1 connector p. 11
  • Setting the interface board signal bypass jumper p. 12
  • Main board connector J1 pin assignments p. 14
  • Panel cutout and case dimensions p. 15
  • Selecting BSCP voltmeter and current ranges p. 38
  • Functional test after configuration p. 37
  • Calibrating zero and span on a DP2000-P p. 52

Good to know

  • The meter has no power switch; an external switch or circuit breaker must be fitted in the building wiring. p. 4
  • Do not operate the meter in flammable or explosive atmospheres or expose it to rain or moisture. p. 4
  • Overtightening the slide clamps can break them. p. 8
  • The BSCP has a restricted common-mode range; the BSCS strain gauge conditioner is advised for large common-mode signals. p. 34
  • A main assembly cannot be tested alone; it needs a signal conditioner board. p. 13

Questions this manual answers

What is the difference between a DP20 and a DP21?

The DP20 main assembly has an LED display and the DP21 has an LCD display. p. 5

What panel cutout does the Omega DP2000 need?

The cutout is 3.622 by 1.772 inches, in a panel up to .25 inch thick. p. 15

What input ranges does the DP2000-P accept?

With the BSCP conditioner it takes current spans of 1 to 50 mA or voltage spans of 0.5 to 20 V full scale, set by push-on jumpers. p. 34

How do I set the decimal point on a DP2000?

Fit the push-on jumper for the wanted position, or connect the matching J1 pin to J1-6. p. 11

How do I calibrate a DP2000-P?

Short the input and set the zero pot (R1), then apply the full input and set the span pot (R2), repeating until within one count. p. 52

The whole text · 6 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60

The file

Revision and size

Revision10288ML-98 Rev. B, 1998
PublisherOMEGA Engineering, Inc.
Pages60
PDF1.9 MB
TextThe pages are scans; their text was read by OCR, which may hold reading errors.

The first pages · 3 of 60

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 60
Page 2
Page 2of 60
Page 3
Page 3of 60

More documents · 1

For the same models