Attended Workstations (Catalog Nos. 2708-DH5B2L & -DH5B4L) (Series B) User Manual: 6 - Operating Procedures

Pages 64 to 70 of 186, from Attended Workstations (Catalog Nos. 2708-DH5B2L & -DH5B4L) (Series B) User Manual

The original document is the PDF (513 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 2708

Page 64

Chapter

A–B

6

Operating Procedures Chapter Objectives

This chapter describes most of the operations normally used in the set-up and maintenance of a network. It also includes descriptions of some methods used in discerning correct operation. Some of these are:

• verifying proper operation • removal of a Master or Submaster from the network • changing a workstation into a Master • removal of a Normal workstation from the network • adding a Normal workstation to the network Default Configuration – The major factory default settings are: Parameter

Value

Configuration Menu

Terminal Number: . . . 0 . . . . . . . . . . . . . . . . . . Network Host Port: . . . . . . . . . . COM . . . . . . . . . . . . . . Network Terminal Type: . . . . . . Normal . . . . . . . . . . . . Network Lower Poll Address . . 1 . . . . . . . . . . . . . . . . . . Network Upper Poll Address . . 99 . . . . . . . . . . . . . . . . . Network Offline Cycle . . . . . . . 40 . . . . . . . . . . . . . . . . . Network Max Net Retries . . . . . 10 . . . . . . . . . . . . . . . . . Network Comm Port Mode: . . . Polled . . . . . . . . . . . . . Network Comm Baud Rate: . . . 9600 . . . . . . . . . . . . . . . Comm Port Comm Data Bits: . . . . 7 . . . . . . . . . . . . . . . . . . Comm Port Comm Parity: . . . . . . Even . . . . . . . . . . . . . . Comm Port Comm Stop Bits: . . . . One . . . . . . . . . . . . . . . Comm Port Comm CRLF: . . . . . . Disabled . . . . . . . . . . . Comm Port Comm Echo: . . . . . . . Disabled . . . . . . . . . . . Comm Port Sync Count: . . . . . . . . 0 (Remains 0 always) . Comm Port Aux Baud Rate: . . . . . 9600 . . . . . . . . . . . . . . . Comm Port Aux Parity: . . . . . . . . Even . . . . . . . . . . . . . . Comm Port Aux CRLF: . . . . . . . . Disabled . . . . . . . . . . . Comm Port Aux Echo: . . . . . . . . . Disabled . . . . . . . . . . . Comm Port Comm Menu Char.: . . None . . . . . . . . . . . . . . Comm Port Menu Password . . . . . 0 . . . . . . . . . . . . . . . . . . System Clock Mode . . . . . . . . 7 . . . . . . . . . . . . . . . . . . System File Block Size . . . . . . 256 . . . . . . . . . . . . . . . . System Bar Code Symbology . . Code 3 of 9 Enabled . . . Bar Code all others Disabled The workstation will be reset to these settings when Option H – Reset to Factory Defaults is selected from the Diagnostics Menu (Menu 6) 6–1

Page 65

Chapter 6 Operating Procedures

Verifying Proper Network Operation

Each workstation is capable of displaying information which can be used to ascertain if it is operating correctly. The Network Status display for workstations that are online are: Normal workstation cc–nn ONLINE

READY cc–nn ONLINE

READY [M]

Master workstation cc–nn ONLINE

READY [SM]

Submaster workstation cc–nn ONLINE

READY [A]

Alternate Master cc–nn ONLINE

READY [AM]

Alternate Submaster cc–nn ONLINE

READY [C]

Concentrator normal operating display normal operating display normal operating display normal operating display normal operating display normal operating display

00 READY TERMINAL

Workstation standalone mode cc–nn ONLINE

Gateway

READY [G] normal operating display normal operating display

Note: Since the program has complete control of the display, the status message will only be present when no program is active or if ENTER/OUT has been invoked. Note: On the displays shown in this manual: cc = Master or Submaster I.D. number nn = Workstation I.D. number

6–2

Page 66

Chapter 6 Operating Procedures

Removing a Master

If the Master is physically removed from the network, fails to function, or the Host stops communicating, then a Master is considered removed from the network. No data can be received by the Host until the problem is remedied. If the problem is that the Host has stopped communication, there is a possibility that the problem lies with the Host. If that is indeed the case, the solution of the problem is also with the Host, and should be addressed there. In some cases, the Host will stop communicating due to a problem with the Master, even though to outward appearances, the Master is fine. Substitution of another workstation to act as Master will usually show whether the problem is with the Master Workstation or the Host. See the section on Instituting a New Workstation as Master. Alternate Master in Place – If an Alternate Master has already been selected and established as an Alternate Master on the network, then it will begin operation at any time from 90 to 120 seconds after the original designated Master became inoperable. When the alternate Master begins operating as the new Master, it will briefly display: cc–nn ONLINE

READY [M] where cc is the Master number if this workstation is a Submaster, and nn is the workstation ID. Notice that all of the workstations attached to this Master (or Submaster) will change their Concentrator or Master number to correspond to the new configuration. Host/Alternate Master – The Host computer must be ready to accept data from the Alternate Master or else the workstations on the network will continue to accept transactions only until their memory is filled. They will then stop functioning. No Alternate Available – If no alternate Master is available to take over the role of Master, then the group of workstations attached to the offline Master will also go offline after about a minute. When that occurs, each of the workstations will display: nn READY OFFLINE

6–3

Page 67

Chapter 6 Operating Procedures

Instituting a New Workstation as Master

If the network is not operating, then adding a new Master to the system involves the following steps: 1. Disconnect the cables from the ‘old’ Master 2. Remove the ‘old’ Master 3. Attach cables to the new workstation 4. Configure the new workstation as a Master (see Configuration Menu) 5. Set the communications parameters from the list in your site parameter list for a Master (see Communications Menu) Before becoming active, the new Master will wait for a moment to make sure that no other workstation is currently acting as Master. During this time, when 1–Network Status is entered, the Master will display: nn READY OFFLINE [M] As soon as the new Master comes online, it’s display will change to: cc–nn ONLINE

READY [M] where cc is the Concentrator or Master number, and nn is this workstation’s number. Note: Under polled mode the Master Workstation will not actually go online until it receives a poll from the Host.

Removing a Workstation from the Network

When a workstation is removed from the network, or it becomes inoperable for whatever reason, there may be approximately a 2 second pause in network operations. This occurs because the Master makes multiple attempts to get data from the (now) absent workstation before it stops trying. When several workstations are removed from the network at the same time, the pause will be 2 seconds x number of workstations removed.

6–4

Page 68

Chapter 6 Operating Procedures

Adding a Workstation to the Network

When a workstation is first added to the network, it may not immediately be recognized by the Master. This recognition may take up to a minute. During this period, when 1–Network Status is entered, a workstation not yet recognized by the network will display: nn READY OFFLINE As soon as communications are established, the display changes to: cc–nn ONLINE

READY

If the workstation does not come online in approximately 1 minute, the cables should be checked. This can be done quickly by substituting a known working workstation at the questionable position. If the cabling is fine, then check the site parameter list for this workstation. Verify that the parameters are set correctly. Any attempts to load application programs into individual workstations should not be attempted until the ONLINE message has been received from that workstation. Premature attempts at downloading a program can result in nothing being loaded into the workstation. Visual examinatioin of the 7–Program Load Status display should show whether a program has been loaded properly.

Network Problems

Network problems usually fall into one of the following categories: Configuration error . . . . This is usually a duplicate station number, but can be caused by configuring two Masters and starting them at the same time. Cabling error . . . . . . . . . The most common error is caused by switching polarity of the network wires. Other errors include: cold solder joints, improper grounding, excessive induced noise and failure to set the Terminator switch on one AND ONLY ONE of a string of workstations. Workstation malfunction The most likely workstation malfunction which can effect network operation is a workstation which contains an improperly operating RS-485 line driver. Such a workstation can render the entire network inoperable until it is located and removed. 6–5

Page 69

Chapter 6 Operating Procedures

Network Problems (cont’d)

Once the application programs have been loaded into the network workstations, it may not be possible to see the status display, making it even more difficult to recognize and solve network problems. When tracking network problems, liberal use of the ENTER/OUT key combination to cause brief display of the workstation status can be helpful.

Workstation Status

The following is a collection of displays which may be helpful in identifying (and solving) some network problems. cc–nn

WAIT

This workstation is waiting ONLINE to be polled. When this appears on the display, the data memory of the workstation is full and it is trying to send a transaction to the Host, but has not been polled. This should only occur for very short periods of time (less than a second). If waiting occurs for as long as a minute, the workstation will go into offline operation. If waiting occurs on a sporadic basis, then cabling may be the problem. Some intermittent cable problems have been discovered to be the cause of sporadic waiting. Verify that the Terminator has been set on either end of the string in question; check individual cable connectioins to workstations and verify that all workstations are operating. If WAIT appears for more than a few seconds only during your peak usage time, then too many workstations may be trying to send too much data to a single Master. If this problem continues or worsens, consider laying out a network with more than a single backbone (see chapter on Network Design). nn READY OFFLINE

The Master has stopped polling this workstation

This indicates that the station is only able to store information in its local memory, instead of sending data on to the Master. It will do so until either the Master begins communicating again or the memory becomes full. nn FULL OFFLINE

6–6

The memory of this workstation is full and offline

Page 70

Chapter 6 Operating Procedures

Workstation Status (cont’d)

Wait for the Master to come back ONLINE. If it is ONLINE, and all the other workstations are ONLINE, a then check the cables for this workstation. Replace the workstation if no cabling problem can be located. If all other workstations are ONLINE, and the one unit remains OFFLINE, and the cables do not seem to be at fault, the problem could be with the network port. To avoid losing data which may be in the unit, perform the following steps: 1) remove the workstation from the network, 2) connect it to an individual power source and configure it as a Master, 3) establish communications with it through its communications port, and 4) dump its contents via the Host communications. Run the network diagnostics (test D and E) on the workstation to verify that the problem is the network port. nn–nn READY OFFLINE [M]

The Master has not been able to communicate with the Host

The Host has turned off this Master workstation by sending it an XOFF. The workstation will not resume transmitting until it receives an XON. There will be no DSR or poll for at least 10 seconds. If this condition persists, and the Master is ready to receive data, one way to clear this condition is to enter then exit the menu mode (ENTER/IN, the EXIT). If the condition persists, check the cabling. After that, check the Host’s communication (both hardware and software). mm–nn READY OFFLINE [C]

The Concentrator cannot contact its Submaster

Check the cabling to the Submaster. If the cabling is correct, then verify that both the Concentrator and the Submaster are set to the same baud rate. If the problem persists, replace first the Concentrator then the Submaster to identify the failed workstation. nn READY OFFLINE [SM]

The submaster cannot contact its Concentrator

Use the same solution as described above. 00 READY TERMINAL

This workstation has been reset to factory defaults

If this was not specifically caused by changing the workstation’s station number, then there may be something wrong with this workstation. Reconfigure the workstation and let it continue to operate in service. If the workstation resets again, remove it from use and send it back for service. 6–7