Page 58
Chapter 5 Configuration Menus
Menu 6: Diagnostics Menu Parameters (cont’d)
Pressing <ENTER> will transmit the following test pattern through the communications port to the Host computer (single 80 column line): 0123456789 ––<The quick brown fox jumped over the lazy dog.–– 9876543210 <carriage return> [<line feed>] The line feed is optional and is sent only if the Aux Comm CRLF parameter has been enabled (in the Comm Port Menu). The bottom line of the display continues to show:
DTR:
ON
CD:
ON
The pattern is sent continuously until the <EXIT> key is pressed. Pressing <EXIT> will terminate the test and display 8–Comm Transmit Test.
9–Aux Comm Receive Test When Enter is pressed while 9–Aux Comm Receive Test (Aux Rx Test) is showing on the display, the following prompt appears on the display:
DTR:
ON
CD:
ON
DTR cannot be toggled OFF. If another workstation has been set to run Diagnostic 7–Comm Transmit Test, the following test pattern will be received through the communications port (single 80 column line); 0123456789 ––<The quick brown fox jumped over the lazy dog.–– 9876543210 <carriage return> [<line feed>] While operating this test, characters received will be echoed to the top line of the display. The bottom line continues to display:
DTR:
ON
CD:
ON
Pressing <EXIT> will terminate the test and re-display 9–Aux Rx Test.
5–17
Page 59
Chapter 5 Configuration Menus
Menu 6: Diagnostics Menu Parameters (cont’d)
A–Aux Comm Loopback Test When Enter is pressed while A–AUX Loop Test is showing on the display, the following prompt appears on the display:
DTR:
ON
CD:
ON
DTR cannot be toggled OFF. The Aux Comm Loopback Test is used to verify proper operation of the communications line. The same pattern used by the transmit test is sent, and the test expects to receive this pattern from the comm line. In order to use this test, a LOOPBACK PLUG must be made or acquired. To make an RS-232 loopback plug, use a 9-pin female D connector: Jumper pin 2 to 3 (TxD to RxD) To make an RS-422 loopback plug, use a 9-pin female D connector: Jumper pin 3 to 2 (TxD + to RxD +) through a 1K ohm resistor Jumper pin 1 to 4 (RxD– to TxD–) through a 1K ohm resistor The 1,000 ohm resistor is placed in-line between each Receive and Transmit pin to simulate a 1,000 ft. length of cable. Install the loopback connector into the communications port of the workstation BEFORE starting this test. Once this test is started, the upper line of the display should show the transmit pattern flashing past. If a character is lost, then the display will freeze. This indicates a test failure. If a character is substituted, a beep will sound and the display will pause for 3 seconds. Losing characters is indicative of a hardware error occurring in the workstation. The keys 1 through 9, <ENTER>, <CLEAR>, <RIGHT ARROW>, <IN> and <OUT> will be transmitted to the comm line. Pressing <EXIT> will terminate the test and display A–Aux Comm Loopback Test.
5–18
Page 60
Chapter 5 Configuration Menus
Menu 6: Diagnostics Menu Parameters (cont’d)
B–RS485 Block Receive This RS485 Block Receive Test is used in conjunction with diagnostic test C–RS485 Block Transmit to test the cabling integrity of the network. When this test is enabled, the following appears on the display: Rx=nnnnn
ERRS=nnnnn
–––contents of a block–––––
The Rx indicates the number of blocks received by this workstation, the ERRS indicates the number of errors encountered. If the Rx count does not change on the display, then the cable is probably not connected, is shorted or has a break. If the Rx Error count is more than 1% of the received blocks (Rx count), then there are cabling problems present which must be corrected for proper operation of the network. See Chapter 2. This test is terminated by pressing <EXIT>.
C–RS485 Block Transmit This RS485 Block Transmit Test is used in conjunction with diagnostic test B–RS485 Block Receive to test the cabling integrity of the network. It causes a continuous stream of test records to be transmitted out the RS-485 port of the workstation on which it is running. Other workstations may be placed in RS485 Block Receive mode in order to verify that the cabling between the workstations in test are properly wired, connected and are functioning. When this test is enabled, the following appears on the display: Tx=nnnnn
ERRS=nnnnn –––contents of transmitted block–––––
The Tx indicates the number of blocks transmitted by this workstation, the ERRS indicates the number of ERRS encountered.
5–19
Page 61
Chapter 5 Configuration Menus
Menu 6: Diagnostics Menu Parameters (cont’d)
The following is a cable verification procedure: Place the workstation at the Master’s location into RS485 Block Transmit test mode (Diagnostic Test C). As you install each workstation, place it into RS485 Block Receive mode (diagnostic test B). If the receiving workstation does not show the test block, it is indicative of a cable fault. Correct any cable faults before proceeding. Always work your way out from the Master workstation, installing workstations further and further away as you progress. After all workstations on the network are in place, verify that every one is receiving the test message. Place the Master workstation into RS485 Block Receive test mode (diagnostic test B), and place the workstation at the most remote position in the network into RS485 Block Transmit mode (diagnostic test C). Once again, verify that all workstations are receiving the test block. Remember that only one workstation on the network can ever be in Block Transmit mode. Pressing <EXIT> will exit the Block Transmit mode. Note: This test must never be performed on a network operating in an actual application. All other network activity must cease while this test is being run.
D–RS232 Block Receive This test, and its counterpart, the RS232 Block Transmit must be used only with asynchronous modem lines. It is used for testing the Concentrator to Submaster connection ONLY. When this test is enabled, the following appears on the display: Rx=nnnnn
ERRS=nnnnn
–––contents of a block–––––
The Rx indicates the number of blocks received by this workstation, the ERRS indicates the number of errors encountered. If the Rx count does not change on the display, then the cable is probably not connected, is shorted, wired incorrectly or has a break. If the Rx Error count is more than 1% of the received blocks (Rx count), then there are cabling problems present which must be corrected for proper operation of the Concentrator to Submaster link. See Chapter 2. This test is terminated by pressing <EXIT>.
5–20
Page 62
Chapter 5 Configuration Menus
Menu 6: Diagnostics Menu Parameters (cont’d)
E–RS232 Block Transmit This test and its counterpart, the RS232 Block Receive must be used only with asynchronous modem lines. It is used for testing the Concentrator Submaster connection ONLY. This test causes a continuous stream of test records to be transmitted out the RS-232 port of the workstation on which it is running. The workstation at the other end of the Concentrator/Submaster connection must be placed in RS232 Block Receive mode in order to verify that the cabling between the workstations in this test is properly wired, connected and is functioning. When this test is enabled, the following appears on the display: Tx=nnnnn
ERRS=nnnnn –––contents of transmitted block–––––
The Tx indicates the number of blocks transmitted by this workstation, ERRS indicates the number of errors encountered. What follows is a cable verification procedure: Place the workstation at the Concentrator’s location into RS232 Block Transmit test mode (Diagnostic Test E). Place the Submaster workstation attached to the Concentrator into RS232 Block Receive mode (Diagnostic Test D). The Submaster should show the test block being received. If the block does not display the count of received blocks, it is indicative of a cable fault. Correct any cable faults before proceeding. Place the Submaster workstation into RS232 Block Transmit mode. Now place the Concentrator into RS232 Block Receive test mode. The Concentrator workstation should show the test block being received. If the count of received blocks is not displayed, it is indicative of a cable fault. Correct any cable faults. Pressing <EXIT> will exit the Block Transmit mode. Note: This test must never be performed on a network operating in an actual application. All other network activity must cease while this test is being run.
5–21
Page 63
Chapter 5 Configuration Menus
Menu 6: Diagnostics Menu Parameters (cont’d)
F–Lamp Test If this test is selected, it will turn on, one by one, each of the keypad LEDs. After all the lights are on, the workstation will return to the G–Lamp Test Menu and the LEDs will return to off.
G–Reset Powerup When the Reset Powerup Test is entered, it reboots the workstation, causing the workstation to go through the entire power-up sequence exactly as if power had been removed, then re-applied.
H–Reset Unit to Factory Defaults When <ENTER> is pressed while Reset Unit to Factory Defaults is on the display, it causes all of the workstation parameters, those described in the Network, Comm and Bar Code menus, to be reset to the way they were set when the workstation left the factory. This is particularly helpful when attempting to track other problems, as the factory defaults are a known starting place from which to work. Refer to Chapter 6 for default values.
5–22