Laser Scanner Interface LSI 101 Technical Description, pages 61 to 70

Pages 61 to 70 of 82

The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Sick LSI-101

Page 61

11.2 LSI fault table

11.3 SICK Service/Hotline

This table enables you to find out what the SICK diagnosis fault codes mean, and whether you can rectify the fault yourself. How to execute the SICK diagnosis is described in section 9.15.

If you have any further questions please refer to your local office or contact the SICK Service Hotline.

Fault codes not listed in this table are internal faults. Please contact SICK Service.

Fault code:

Cause / corrective action:

11 – 21

Communication failure between PLS and LSI: Check the communication cable. Switch the power off and back on again.

41

Sensor fault: Switch the power off and back on again. Replace the PLS, or contact SICK Service.

43

Sensor has no default password: Contact SICK Service to have the default password configured.

44

Wrong sensor address: Check the wiring between the LSI and the sensors. Reconfigure the LSI.

56

Configuration error: Check the wiring between the LSI and the sensors.

57

Maximum input voltage at the inputs exceeded: Check the voltage level of the LSI inputs

59

Initialisation error in channel 1: Contact SICK Service.

60

Initialisation error in channel 2: Contact SICK Service.

61, 63

OSSD fault: Check the output load. Switch the power off and back on again. Replace the LSI, or contact SICK Service.

110

Measurement telegram error, sensor 1: Check the wiring between the LSI and sensor 1. Interrogate the sensor fault memory (see section 9.15), or contact SICK Service.

111

Measurement telegram error, sensor 2: Check the wiring between the LSI and sensor 2. Interrogate the sensor fault memory (see section 9.15), or contact SICK Service.

112

Measurement telegram error, sensor 3: Check the wiring between the LSI and sensor 3. Interrogate the sensor fault memory (see section 9.15), or contact SICK Service.

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

61

Page 62

Fault code:

Cause / corrective action:

113

Measurement telegram error, sensor 4: Check the wiring between the LSI and sensor 4. Interrogate the sensor fault memory (see section 9.15), or contact SICK Service.

114

Initialisation error, sensor 1: Check the wiring between the LSI and sensor 1. Check that the connected sensor type matches the configured type. Reconfigure the LSI, or contact SICK Service.

115

Initialisation error, sensor 2: Check the wiring between the LSI and sensor 2. Check that the connected sensor type matches the configured type. Reconfigure the LSI, or contact SICK Service.

116

Initialisation error, sensor 3: Check the wiring between the LSI and sensor 3. Check that the connected sensor type matches the configured type. Reconfigure the LSI, or contact SICK Service.

117

Initialisation error, sensor 4: Check the wiring between the LSI and sensor 4. Check that the connected sensor type matches the configured type. Reconfigure the LSI, or contact SICK Service.

118

Protective field configured too large: Adapt the size of the protective field to the sensor variant.

120

Contamination on sensor 1: Check and clean the front screen of the sensor.

121

Contamination on sensor 2: Check and clean the front screen of the sensor.

122

Contamination on sensor 3: Check and clean the front screen of the sensor.

123

Contamination on sensor 4: Check and clean the front screen of the sensor.

144

Initialisation error in channel 1: Contact SICK Service.

145

Initialisation error in channel 2: Contact SICK Service.

161

Configured measurement tolerance of incremental encoders exceeded: Check the connections of the incremental encoders.

162

Directional values of incremental encoders different: Check the connections of the incremental encoders.

163

Undefined input combination: Check the configuration of the input conditions.

165

Incorrect monitoring case switching sequence: Check the sequence setting in the configuration (see section 9.4).

62

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

Page 63

Fault code:

Cause / corrective action:

180

Fault in sensor 1: Switch the power off and back on again. Interrogate the sensor fault memory (see section 9.15). Replace the sensor, or contact SICK Service.

181

Fault in sensor 2: Switch the power off and back on again. Interrogate the sensor fault memory (see section 9.15). Replace the sensor, or contact SICK Service.

182

Fault in sensor 3: Switch the power off and back on again. Interrogate the sensor fault memory (see section 9.15). Replace the sensor, or contact SICK Service.

183

Fault in sensor 4: Switch the power off and back on again. Interrogate the sensor fault memory (see section 9.15). Replace the sensor, or contact SICK Service.

200

Same level at input A: Check input levels at A1 and A2. The levels must be mutually inverted.

201

Same level at input B: Check input levels at B1 and B2. The levels must be mutually inverted.

202

Same level at input C: Check input levels at C1 and C2. The levels must be mutually inverted.

203

Same level at input D: Check input levels at D1 and D2. The levels must be mutually inverted.

204

Faulty actuation of inputs: Check the actuation.

206

Incorrect actuation of RES A: Check the levels and the time response at RES A.

208

Incorrect actuation of RES B: Check the levels and the time response at RES B.

209

Maximum input frequency of incremental encoder inputs exceeded: Check the configuration of the incremental encoders.

240

External device monitor EDM A still open: Check EDM A.

242

EDM A closed when output active: Check EDM A. Switch the power off and back on again. Replace the LSI, or contact SICK Service.

243

EDM A open when output inactive: Check EDM A. Switch the power off and back on again. Replace the LSI, or contact SICK Service.

244

External device monitor EDM B still open: Check EDM B.

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

63

Page 64

Fault code:

Cause / corrective action:

246

EDM B closed when output active: Check EDM B. Switch the power off and back on again. Replace the LSI, or contact SICK Service.

247

EDM B open when output inactive: Check EDM B. Switch the power off and back on again. Replace the LSI, or contact SICK Service.

248

Object in protective field: Check the ambient conditions. Adapt the configuration of the LSI to the ambient conditions.

249

Object in warning field: Check the ambient conditions. Adapt the configuration of the LSI to the ambient conditions.

64

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

Page 65

12 Appendix 12.1 Application examples Refer also to the instructions for the PLS given in the PLS Technical Description. The application examples presented on the following pages are intended only as guides. You may need to incorporate additional protection measures. Remember that there may already be someone in the protective field when the switch is made to a different monitoring case. Safe protection can only be guaranteed by prompt switching (that is, before the danger to the person arises at the location concerned). General note on the wiring diagrams: Use only relays with positively guided contacts. The switching elements connected in parallel with the contactors provide arc suppression (varistors for maximum alternating operating voltage VRMS = 25 V). 1) Output circuits. These contacts must be integrated into the control system such that the hazardous state is eliminated when the output circuit is open. For categories 3 and 4 to EN 954-1 they must be integrated in a two-channel configuration (x, y paths).

WF2

PF2

W

F1

W F3

PF

1

PF 3

For area protection

PLS

1. Example: Machining centre with three loading stations The LSI system is configured as follows: – One PLS sensor connected – Three monitoring areas defined (the protective and warning fields are shown in the diagram) – One OSSD output and one warning field output configured – Three monitoring cases configured, activated via the binary inputs – Alternative order of monitoring cases hazardous area

1. Application example: Machining centre with three loading stations

X1. 3 1

+ 24 V DC 0V

PLS

8 7 4 3 2 1

Si

X2.

-

+

+

X15

-

X3

+

-

1

X14

X13

2

X4

3

4

RES B

A2

B1

X12

X5

INPUT B2

3

4

2

SENSOR 2

INPUT A1

2

1

SENSOR 1

B

A EDM B

WZ B

B OSSDA2

OSSDA1

WZ A

+

POWER OUT POWER OUT

A ERROR

-

RES A

POWER IN

X2

-

EDM A

-

OSSDB2

X1

OSSDB1

+

C1

C2

D1

X11

X8 3

5

COM

SPEED INPUT SPEED INPUT

(C)

D2

1

3

6

X10

7

1

3

6

7

X9

1)

K1 x k1

K6

K1

K2

K2

LSI

(D)

y k2 x y

S1A

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

65

Page 66

2. Example: Pipe bending machine The LSI system is configured as follows: – One PLS sensor connected – Two protective fields (simultaneously) and one warning field defined – Two OSSD outputs and one warning field output configured – Three monitoring cases configured, activated via the binary inputs – Any order of monitoring cases

WF1

PF1

PF2 (simultaneous)

2. Application example: Pipe bending machine

X1. 3 1

+ 24 V DC 0V

PLS

8 7 4 3 2 1

Si

X2. X1

X2 -

+

X15

+

-

+

A

X4 -

2

1

X14

3

X5 4

1

SENSOR 1

B

A1

A2

X13

B1

X12

2

3

2

C1

C2

D1

X11

3

5

COM

(C)

D2

1

3

6

(D)

7

1

3

X10

6 x1 k1

K1

K2

K3

K4

K2

66 y1 k2 x1

K6

7

X9

1)

K1

LSI

SPEED INPUT SPEED INPUT

INPUT B2

X8 4

SENSOR 2

INPUT RES B

EDM B

EDM A

WZ B

B OSSDA2

OSSDA1

WZ A

X3 -

POWER OUT POWER OUT

A ERROR

+

RES A

POWER IN

-

OSSDB2

-

OSSDB1

+ x2 k3 y1 y2 k4 x2 y2

K3 S1A

K4

S1B

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

Page 67

For on-board vehicle use 3. Example: Automated guided vehicle (AGV), forward and reverse, with incremental encoders Calculate the number of pulses your encoders deliver per centimetre travel of your vehicle.

Frictional wheel Æ 3.5 cm with incremental encoder

The result depends on the number of pulses the incremental encoder delivers per revolution, and on the transmission ratio between the vehicle‘s running wheel and the friction wheel to which the incremental encoder is fitted. How to calculate the number of pulses per centimetre:

Forklift wheel Æ 35 cm

The running wheel of a forklift truck has a diameter of 35 cm. The friction wheel to which the incremental encoder is fitted has a diameter of 3.5 cm. Distance covered by vehicle

The incremental encoder in use delivers 1000 pulses per revolution.

Calculation of pulses per centimetre Circumference of forklift wheel = d × p = 35 cm × p = 109.96 cm One revolution of the forklift wheel corresponds to 10 revolutions of the friction wheel, and thus to 10,000 pulses of the incremental encoder. The number of pulses of the incremental encoder per centimetre travel of the vehicle is calculated as:

WF3

Pulses per cm = 10,000 : 109.96 = 90.94 Consequently, when configuring the incremental encoders in the PLS/LSI user software you need to enter the rounded value “91” under “Pulses per centimetre”. From that figure, the user software calculates the maximum permissible speed of the vehicle. (How to configure the incremental encoders in the PLS/LSI user software is described in section 9.7.)

The LSI system is configured as follows: – Two PLS sensors connected – Six monitoring areas defined (the protective and warning fields are configured in stages, as shown in the diagram) – Two incremental encoders connected and configured – Two OSSD outputs and two warning field outputs configured – Six monitoring cases (three for forward running, three for reverse) – Any order of monitoring cases

PF3

WF2 PF2 protective fields for forward movement protective fields for reverse movement

WF1 PF1

PF4 WF4

(The circuit diagram for this example is on the next page.)

PF5 WF5 PF6

WF6

3. Application example: Automated guided vehicle (AGV), forward and reverse

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

67

Page 68

X1.

3 1

+ 24 V DC 0V

Si

X2 +

X15

K6

K1

K2

1

3

K3

8 7 4 3 2 1

X2.

X2.

X3 4

+

INPUT A1

A2

X13

K4

-

X5 +

-

1

POWER OUT

B

X12

K1

K3

K2

K4

B1

C1

C2

X11

D1

3

X8 4

2

SENSOR 2

3

5

COM

SPEED INPUT SPEED INPUT

INPUT B2

2

(C)

D2

1

3

(D)

6

7

1

3

6

LSI

7

X10

X9

+ - 0¡ 90¡

+ - 0¡ 90¡

1/f

1/f B1

68

PLS

8 7 4 3 2 1

SENSOR 1

X14

K7

2

A EDM A

WZ B

B OSSDA2 x2 y2

OSSDA1 x1 y1

A

3 1

PLS

X4 -

POWER OUT OSSDB2 x2 y2 WZ A x1 y1 k1 k2 k3 k4

ERROR

1)

+

RES A

POWER IN

-

EDM B

-

OSSDB1

-

RES B

X1 +

X1.

B2

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

Page 69

4. Example: Automated guided vehicle (AGV), forward only, with incremental encoders WF2

Calculate the number of pulses your encoders deliver per centimetre travel of your vehicle, as described in the third example, and enter the resultant values in the user software under “Pulses per centimetre”. (How to configure the incremental encoders in the PLS/LSI user software is described in section 9.7.)

PF2

WF3

WF4 PF4

PF3 WF1 PF1

The LSI system is configured as follows: – One PLS sensor connected – Four monitoring areas defined (the protective and warning fields are shown in the diagram) – One OSSD output and one warning field output configured – Four monitoring cases configured (e.g. slow, fast, left, right) – Two incremental encoders connected and configured – The “slow” and “fast” monitoring cases are activated by way of the incremental encoders; the “left” and “right” cases via the binary inputs. – Any order of monitoring cases

4. Application example: Automated guided vehicle (AGV), forward only

X1. 3 1

+ 24 V DC 0V

8 7 4 3 2 1

Si

1)

PLS x k1 y k2 x y

X2. X1

X2 -

+

+

X15

-

X4 +

A

X14

-

1

X13

2

3

X5 4

1

SENSOR 1

B

A1

A2

X12

B1

2

INPUT B2

X8 3

4

2

SENSOR 2

INPUT RES B

EDM B

EDM A

WZ B

B OSSDA2

OSSDA1

WZ A

+

POWER OUT POWER OUT

A ERROR

X3 -

RES A

POWER IN

-

OSSDB2

-

OSSDB1

+

C1

C2

X11

D1

SPEED INPUT

(C)

D2

1

3

5

COM

3

6

7

SPEED INPUT

(D)

1

3

6

X10

X9

+ - 0¡ 90¡

+ - 0¡ 90¡

1/f

1/f

LSI

7

K1

K6

K1

K2

K2

B1

B2

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

69

Page 70

12.2 Start-up testing and restarting Performing start-up testing You can set in the PLS/LSI user software whether you want to carry out a start-up test when your LSI system has powered up. You can use the start-up test to check whether the protective field evaluation you stored in the LSI is working correctly. In doing so, you test only the sensor which is active during power-up and the monitoring area assigned to it. Consequently, the question of which sensor and which monitoring area is tested depends on which monitoring case is activated first on power-up. Since two monitoring cases may be activated simultaneously, in start-up testing you must test either one or two sensors. Only after start-up testing are the configured outputs enabled, and the system is ready for operation. How to programme start-up testing in the PLS/LSI user software is described in section 9.3. How to perform start-up testing:

•

Red Yellow Green

Switch on the LSI. (It takes a few seconds to warm up.)

The green LED on the active sensor (possibly two sensors) lights up: The protective field which is active on power-up on the sensor is free. The red LEDs at both outputs (OSSD A and OSSD B) light up on the LSI: The outputs are deactivated.

Red Yellow

RES

OSSD WEAK/

A

• • •

Red

Green Yellow Green

Yellow

OSS

ERROR

RES

B

Intrude into the protective field of the active sensor to make the red LED on the sensor light up. Red Yellow Green

Move out of the protective field again. Also intrude into the protective field of the second active sensor where appropriate and then move out of it again.

Depending on the restart response you programmed in the PLS/ LSI user software, the configured output (or, where appropriate, both outputs) is/are enabled. More detailed information on the restart response is given in the following subsection.

70