Page 71
Restart after intrusion into the protective field You have the following options, programmable in the PLS/LSI user software (see section 9.3): – Without delay – Delayed by n seconds – With restart button Restart “without delay”: As soon as the active protective field is free, the LSI enables the output after the pre-set response time (multiple scans). The red LED at the configured output (OSSD A or B) goes out and the green LED lights up.
Red Yellow
Red
Green Yellow Green
RES
OSSD WEAK/
A
Yellow
OSSD
RES
B
ERROR
Restart “delayed by x seconds”: The LSI starts up when the preset time has expired after the protective field has become free. At the end of this time, the red LED at the configured output goes out and the green LED lights up. The output is then free.
After x seconds:
Red Yellow
Red
Green Yellow Green
RES
OSSD WEAK/
A
Yellow
OSSD
RES
B
ERROR
Restart “with restart button”: The yellow “RES” LED at the configured output flashes. You must then press the restart button. Only then is the output enabled.
Red Yellow
Red
Green Yellow Green
Yellow
Note: When mounting the restart buttons, make sure the button is mounted such that the danger zone is in full view when the button is pressed. The system is then ready for operation.
RES
OSSD WEAK/
A
ERROR
OSSD
RES
B
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
71
Page 72
12.3 Technical data Here you will find the key technical data of the LSI. Notes: Also refer to the technical data of the PLS contained in the PLS Technical Description. The requirements for the cables to be used are set out in section 8 of this Technical Description and in the LSI Operating Instructions, section 4.3, “Cable requirements”.
Properties
Specifications typ. max.
Comments min. 16.8 V
24 V
28.8 V
Protected against polarity reversal by a safety isolating transformer to EN 60742
Permissible residual ripple
500 mV
The upper and lower voltage limits must not be infringed.
Cable length
50 m
Cable cross-section
2.5 mm2
Permissible cable resistance
2.5 Ohm
Power supply connection (Uv)
Response time (adjustable) at 2 scan rate
190 ms
Formula for multiple scans (n = 2 to 16)
110 ms + ( n x 40 ms ) Exception: PLS 101-316 with LSI in vehicle protection applications, where the response time is 270 ms, non-adjustable
Power-up time On power-on
9 sec.
Power consumption without PLS and no load
15 W with 1 PLS and max. load
63 W with 2 PLS and max. load
80 W with 3 PLS and max. load
97 W with 4 PLS and max. load
114 W See PLS technical data Connect only PLS units of the same types
PLS connection RES A, RES B (Reset/Restart input) Quantity
One input per OSSD pair
Input resistance at HIGH
3.8 kOhm
Voltage for HIGH
15 V
28.8 V
Voltage for LOW
0V
1V
Start pulse current (where t = 100 µs)
15 mA
32 mA
Static input current
3.5 mA
9 mA
Current consumption
72
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
Page 73
Properties min.
Specifications typ. max.
Comments
Time response of reset/restart button LOW level before actuation
160 ms
HIGH level during actuation
240 ms
LOW level after actuation
160 ms
5s
Cable length
50 m
Cable cross-section
2.5 mm2
Permissible cable resistance
2.5 Ohm
EDM input (external device monitoring) Quantity
One input per OSSD pair
Input resistance at HIGH
3.8 kOhm
Voltage for HIGH
15 V
28.8 V
Voltage for LOW
0V
1V
Start pulse current (where t = 100 µs)
15 mA
32 mA
Static input current
3.5 mA
9 mA
Current consumption
Time response of EDM input High level after OSSD activation
200 ms
Low level on OSSD deactivation
200 ms
Cyclic monitoring of the rest and operating positions
5s
Cable length
50 m
Cable cross-section
2.5 mm2
Permissible cable resistance
2.5 Ohm
Inputs A, B (2-channel: A1, A2/B1, B2 antivalent), static binary Input resistance at HIGH
3.8 kOhm
Voltage for HIGH
15 V
28.8 V
Voltage for LOW
0V
1V
Start pulse current (where t = 100 µs)
15 mA
32 mA
Static input current
3.5 mA
9 mA
Current consumption
Port inconsistency Time window for valid switchover ... (at 2 scan rate)
80 ms
Cable length
50 m
Cable cross-section
2.5 mm2
Permissible cable resistance
2.5 Ohm
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
73
Page 74
Properties min.
Specifications typ. max.
Comments
Inputs C, D (2-channel: C1, C2/D1, D2 antivalent), static binary Input resistance at HIGH
2.6 kOhm
Voltage for HIGH
15 V
28.8 V
Voltage for LOW
0V
1V
Start pulse current (where t = 0.5 µs)
15 mA
32 mA
Static input current
5 mA
13 mA
Current consumption
Port inconsistency Time window for valid switchover (at 2 scan rate)
80 ms
Cable length
50 m
Cable cross-section
2.5 mm2
Permissible cable resistance
2.5 Ohm
Inputs C, D (only for incremental encoder 0°/90°), dynamic Input resistance at HIGH
2.6 kOhm
Voltage for HIGH
15 V
28.8 V
Voltage for LOW
0V
1V
Start pulse current (where t = 0.5 µs)
15 mA
32 mA
Static input current
5 mA
13 mA
Current consumption
Duty factor g (Ti/T)
0.5
Input frequency
100 kHz
Min. number of pulses per cm
50
Evaluable speed range
±10 cm/s
±2000 cm/s
Tolerance time for differing directional information or signal failure of an incremental encoder
0.4 s
³ 10 cm/s
Exceeding of speed tolerance where incremental encoders in same direction
20 s 60 s
< 30 cm/s
Cable length
50 m
Cable cross-section
2.5 mm2
Permissible line impedance
2.5 Ohm
³ 30 cm/s
Warning field output A/B (PNP), HIGH-active Quantity
One output per OSSD pair
Switching voltage HIGH-active at 50 mA
Uv -1 V
Uv
Switching voltage HIGH-active at 100 mA
Uv -0.5 V
Uv
Switching current (referred to EXT_GND)
74
100 mA
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
Page 75
Properties min. Current limitation ( t = 5 ms, 25 degrees Celsius)
Specifications typ. max.
600 mA
920 mA
Pure load inductance
2H
Switching sequence
6 1/s
Response time ( n = 2 to 16 ; n = scan rate)
Comments
150 ms + ( n x 40 ms )
Cable length
50 m
Cable cross-section
2.5 mm2
Permissible cable resistance
2.5 Ohm
Error output (PNP), HIGH-active Quantity
One output
Switching voltage HIGH-active at 50 mA
Uv -1 V
Uv
Switching voltage HIGH-active at 100 mA
Uv -0,5 V
Uv
Switching current (referred to EXT_GND) Current limitation ( t = 5 ms, 25 degrees Celsius)
100 mA 600 mA
920 mA
Pure load inductance
2H » 4 /s 1
Switching sequence Cable length
50 m
Cable cross-section
2.5 mm2
Permissible cable resistance
2.5 Ohm
Safety outputs (OSSD A, OSSD B), dynamic, High-active Quantity
Two 2-channel outputs
Switching voltage High-active (Ueff)
Uv -3,4 V
Uv
Voltage for LOW
0V
2.5 V
Switching current (reference to EXT_GND) 2 mA Short-circuit protected
250 mA by monitoring of outputs
In case of fault: Leakage current
1.1 mA
Pure load capacity
100 nF
Pure load inductance
2H
Switching sequence (without switchover and without simultaneous monitoring)
6 1/s
Response time at double speed
190 ms
Cable length
50 m
Break in GND cable. The downstream switching element must detect this state as Low.
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
75
Page 76
Properties min.
Specifications typ. max.
Cable cross-section
2.5 mm2
Permissible cable resistance
2.5 Ohm
Comments
Test pulse data (OSSD_Test) Test pulse width
100 µs
Test frequency
Once per scan
Test pulse data (Test_Ub) Test pulse width
100 µs
Test frequency
Twice per scan
Safety category
Single error fail-safe
DIN V 19250
Requirement class 4
EN 954-1
Category 3
IEC/EN 61496-1
Type 3
General data IP 20
Enclosure rating Protection class
3 Safety-low voltage
Humidity class
F to DIN 40040
Vibration resistance
IEC 60068, part 2-6
Frequency range
10 ... 55 Hz
Amplitude
0.35 mm IEC 60068, part 2-29
Shock resistance Continuous shock 1000
10 g / 16 ms
Interference immunity (EMC)
IEC / EN 61496-1 EN 50081-2 DIN 40839-1 and -3
Mass (net)
1.25 kg
Dimensions (W x H x D)
216 mm x 108 mm x 86 mm
Operating temperature in degrees Celsius
0
Storage temperature in degrees Celsius -25
76
Installation in switch cabinet with min. IP 54 specified.
Dimensions excluding terminals and connectors +50 +70
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
Page 77
Properties min.
Specifications typ. max.
Protective fields
1
8
Warning fields
1
8
Protective field output
2 independent, monitored semiconductor outputs, 2-channel, PNP HIGH-active, 24 V/250 mA
Warning field output
2 independent semiconductor outputs, PNP HIGH-active, 24 V/100 mA
Fault output
1 semiconductor output, PNP HIGH-active, 24 V / 100 mA
Reset/restart input
1 input per OSSD pair (to 24 V DC)
Comments
EDM input (external device monitoring) 1 input per OSSD pair (to 24 V DC) Inputs A1, A2, B1, B2, C1, C2, D1, D2
Static binary inputs to 24 V DC
Inputs C, D
Dynamic inputs to 24 V DC
Switchover of monitoring cases (use of inputs A - D)
4 static binary input pairs (x1 and x2 antivalent) A1, A2, B1, B2, C1, C2, D1, D2 or 2 dynamic incremental encoder inputs (C, D) and 2 static binary input pairs (x1 and x2 antivalent) A1, A2, B1, B2 Only for temporary configuration and diagnostic purposes
Interface (PC) Transmission rate RS 232
9600, 19200, 38400 Baud
RS 422
9600, 19200, 38400 Baud
Cable length RS 232
15 m
RS 422
100 m Use of a low-capacitance twisted-pair data cable of type Li2YCY (TP) with a cable cross-section of min. 2 x 2 x 0.25 mm2
Interface (LSI - PLS)
Transmission rate RS 422
500 kB
Cable length RS 422
30 m
Cable cross-section RS 422
0.25 mm2
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
77
Page 78
12.4 Accessories
User documentation
For installation
Technical Description LSI, German, without software discs
Part no. 8 008 309
Technical Description, LSI, English, without software discs
8 008 310
Technical Description, LSI, French, without software discs
8 008 311
Technical Description LSI, Spanish, without software discs
8 009 033
Mounting kit (DIN rail and mounting bracket)
Part no. 2 019 300
LSI variants LSI 101-112 (for connection of max. 2 PLS 101-3xx) LSI 101-114 (for connection of max. 4 PLS 101-3xx)
Part no. 1 016 063 1 016 065
For connection to the control and the PLS Connection set A 1 PLS power plug, 1 PLS interface connector, 1 screw-in interface connector for sensor connection to LSI, without cable
Part no.
2 019 065
Connection set B, as connection set A, with 3 metre cable
2 019 066
12.5 Standards and regulations The following lists the key standards and regulations applicable to the use optoelectronic safety devices. Depending on application, additional regulations may be of importance for you. You can get information on other device-specific standards from local regulatory authorities, or from professional bodies. Regarding the use and installation of safety devices:
Connection set C, as connection set A, with 5 metre cable
2 019 067
Machinery Directive 98/37 EC
Connection set D, as connection set A, with 10 metre cable
2 019 068
Safety of machines – Basic terms, general design guidelines (EN 292)
Connection set E, as connection set A, with 15 metre cable
2 019 069
Safety requirements for automated manufacturing systems (VDI 2854)
Connection set F, as connection set A, with 20 metre cable
2 019 070
Safety of machines – Electrical equipment of machines – Part 1: General requirements (EN 60 204)
Connection set G, as connection set A, with 30 metre cable
2 025 902
Safety of machines – Safety distances to prevent reaching hazardous areas with upper limbs (EN 294)
Terminal strip set, WAGO connector set, 8-part
2 018 946
Safety requirements for robots (EN 775)
SUB–D connector (RS 232/RS 422) with screw-in terminals, EMC protected
6 011 808
Safety rules for electro-sensitive protective equipment on powerdriven machinery (ZH 1 / 597)
SUB–D connector (RS 232/RS 422) with soldered terminals, EMC protected
2 019 097
Safety of machines – Arrangement of safety devices with regard to approach speed of body parts (EN 999) Safety of machines – Risk assessment (EN 1050)
Power supply units Part no. 24 V DC, 2.5 A
6 010 361
Regarding construction and equipping of protective devices:
24 V DC, 4,0 A
6 010 362
24 V DC, 10 A
6 011 156
Safety of machines – Electro-sensitive protective equipment – Part 1: General requirements (IEC/EN 61496-1)
Interface cables RS 232
Part no.
Basic safety observations for instrumentation and control protective devices (DIN V 19 250) Safety of machines – Electrical equipment of machines – Part 1: General requirements (EN 60 204)
Interface cable, 3 m
2 016 401
Interface cable, 5 m
2 016 402
Interface cable, 10 m
2 016 403
Safety of machines – Safety-related components of controls – Part 1: General design guidelines (EN 954)
Interface cable, 3 m
2 019 130
On these subjects please also order our brochure “Safe machines with optoelectronic protection devices”.
Interface cable, 5 m
2 019 131
Interface cable, 10 m
2 019 132
RS 422
78
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
Page 79
OSSD A2
K5 K6 K1 K2
ERROR
A
X15
WZ A
POWER IN
OSSD A1
_ _ + DC 24 V
LSI
B
POWER OUT
+
X14
WZ B
_
OSSD B1
_ _ + _ DC 24 V
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
X13
DC24 24 V DC
K2
K1
A
B
RES
POWER OUT
+
EDM A
DC 24 V
RES A
+
OSSD B2
X3
EDM B
X2
RES B
X1
A
OSSD
OSSD
A1
SENSOR
SENSOR
B1
X12
A2
INPUT B2
ERROR
D1
X11
C1 C2
INPUT
B
2
1
WEAK/
X5
X4
D2
RES
OR
SENSOR
3
X6
RS 422
OR
RS 232
COM
X8
X10
C
X9
D
SPEED INPUT SPEED INPUT
SENSOR
4
X7
12.6 Connection diagram
79
Page 80
12.7 Dimensional drawing min. 75
(all dimensions in mm)
X2 _
24
+
V
POWER IN
_
+
X3 _
_
+
+
X4
X5
X6
X7
X8
1
2
3
4
COM
SENSOR
SENSOR
SENSOR
SENSOR
RS 232
_
D C 24 V
DC 2 4 V
POWER OUT
POWER OUT
LSI
OR
R ES
O SSD
A
X15
B
A
O SSD
R ES
RS 4 2 2
B
B
X14
A
B
X13
RES B
ED M
R ES A
ED M
O SSD B2
O SSD B1
OR
WZ B
O SSD A 2
ERR O R
O SSD A 1
WZ A
A
WEA K/ ER RO R
INPUT A1
A2
B1
INPUT B2
X12
C1
C2
D1
X11
SPEED INPUT D2
SPEED INPUT
C
D
X10
X9
13
86
7
216 min. 75
_ DC
108
X1 +
226
80
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved