For the Sick LSI-101
Page 41
This dialogue box appears. You now have three options: – You can reject the taught-in protective field. – You can edit it as a segmented field. – Or you can check it and then activate it in the LSI. Reject protective field: • Click on “Cancel”. The taught-in protective field is rejected and the old field retained. Edit protective field: Click on “Edit”. You can then edit the taught-in protective field like a segmented field and then transfer it to the LSI.
•
Check protective field: Click on “Check”.
•
The taught-in protective field is shown on-screen. The space contour of the sensor is displayed for comparison purposes.
•
Infringe the contour of the protective field intentionally until you have reached all 361 points and measuring rays. It is important to do this in a corridor no more than approximately 70 cm from the inner edge of the protective field.
The status bar indicates the number of checked points.
As soon as you have checked all points, this dialogue box automatically appears. To abort the check before all points have been checked:
•
•
From the menu choose Monitoring area – Teach-in, or deactivate the “Teach-in Monitoring area” button on the toolbar. The same dialogue box appears.
Click on “Yes” to transfer the monitoring area into the LSI and confirm with “OK”.
The taught-in protective field is now active in the LSI.
Note: You can also edit the taught-in protective field subsequently and then transfer it as a segmented protective field to the LSI.
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
41
Page 42
9.7 Adapting protective fields to speed If you are using the LSI on a vehicle, you can switch between protective fields of different size and shape depending on the speed of the vehicle. In this way you can adapt the monitoring area flexibly to the surroundings and speed of the vehicle. For this, you must have connected incremental encoders to the LSI. The LSI receives the speed data from the incremental encoders and switches to a different monitoring case as necessary.
•
• •
Calculate the number of pulses your encoders deliver per centimetre travel of your vehicle (min. 50 pulses per cm). (A calculation example for a typical application is given in section 12.1. in the appendix). To be able to transfer the configuration to the LSI subsequently, log on as an “Authorised Client” by way of the LSI – User Category menu function. Choose File – New from the menu and create an LSI configuration with the following settings in the dialogue boxes:
– Application variant: Vehicle protection – Pixel suppression activated: This is the recommended setting to prevent unintended shutdowns and enhance the availability of the system.
– Use incremental encoders: As a result inputs C and D are occupied and so are no longer available to you. – Activate inputs and outputs and external device monitoring (EDM) according to your requirements. (In the example, no other input is configured apart from the incremental encoders. In this case OSSD A is connected to the vehicle’s braking system.)
42
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
Page 43
– Number of pulses of the encoders per centimetre travel of your vehicle: Enter the values calculated for your application here. (A calculation example for a typical application is given in section 12.1. in the appendix). Note: The maximum possible speed of the vehicle is displayed in the box. The minimum recordable speed is ±10 cm/s. For technical reasons, and for the sake of greater availability, lower speeds are ignored and interpreted as 0 cm/s.
– Speed difference between the two incremental encoders: The recommended setting is 25 %. The values of the two incremental encoders may only differ by up to this amount. Note: The speed difference entered here may be exceeded for max. 20 seconds, e.g. for cornering. Activation of the protective field in such cases is always based on the higher of the two speed values. This ensures maximum safety.
– Set the restart behaviour for the outputs according to your requirements. (In this example, delayed restart after two seconds is selected for the configured output OSSD A.) – Start-up testing off: This is the recommended setting.
– Log on and name sensors. (In the example, the two sensors in use are named according to their position on the vehicle: one sensor is mounted at the front and one at the rear, to monitor the forward and reverse movement of the vehicle.)
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
43
Page 44
– Enter and name monitoring areas. (In the example, three monitoring areas are used, named according to their size.)
– Define monitoring cases: Click on “Add” and make the settings you need for your application. Name each monitoring case and assign sensors and monitoring areas as described in section 9.3 for the getting started example. (In the example, five monitoring cases are defined: three for forward and two for reverse.)
– Use speed range: Activate this option and enter the speed range in which you want the monitoring case to be active. Notes: In order to avoid errors, make sure a monitoring case is defined for every speed at which the vehicle may run. For technical reasons, speeds between –10 cm/s and +10 cm/s are interpreted as 0 cm/s. Consequently, you can only enter values less than –10 cm/s or greater than +10 cm/s. To cover the range ±10 cm/s, enter speed ranges as follows, for example: – For forward running: from –10 cm/s to +150 cm/s – For reverse: from –300cm/s to +10 cm/s The more negative value is always at the left. When defining the speed ranges, note that a maximum of two monitoring cases can be active at any one time (simultaneous monitoring cases).
44
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
Page 45
– Click on “Overview” to check your settings. The monitoring cases are listed with the associated sensors, fields and speed ranges. (In the example, five monitoring cases are defined: three for forward running at different speeds and two for reverse. The “forward1” and “reverse1” monitoring cases are active together (simultaneous monitoring cases) and protect the vehicle in both directions at low speeds.
– Edit monitoring areas: Define the size and shape of the various protective and warning fields for your application as described in sections 9.3 and 9.5. Additional hints and tips: Section 12.1 presents a number of examples offering additional possibilities for implementing your application on a vehicle in a configuration with incremental encoders. Section 9.8 describes how you can simulate monitoring cases on PC in order to check the linking of sensors and fields at different speeds. Section 9.10 presents information on the “I/O Monitor” menu function, with which you can receive and log the switching states of the inputs and outputs and the incremental encoders from the LSI in operation.
Note on turning on the spot: When a vehicle is turning on the spot, the directional information from the two incremental encoders differs. Under normal circumstances this would cause the LSI system to shut down. You can enable turning on the spot by defining a “turnaround” monitoring case as follows: – The “Use speed range” option is deactivated for this monitoring case. The data from the incremental encoder are then not evaluated during turning. Then the full speed range of the vehicle is highlighted in the overview (see diagram). – Apart from the incremental encoders, a further input must be configured exclusively to activate the “turnaround” monitoring case, e.g. input A. In all other monitoring cases this input must be set to “0 = low”.
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
45
Page 46
9.8 Simulating monitoring cases You can check the monitoring case settings by simulating the input conditions of each individual case on your PC. In this way you can also check whether the sensors and fields are correctly assigned in every monitoring case.
• •
From the menu choose LSI – Monitoring Cases – simulate. Or choose the “Simulate monitoring cases” button from the toolbar.
A dialogue box appears displaying the logged-on sensors.
• •
Set the desired state for each input (A, B, C, D): 0– low 1– high If you have connected incremental encoders, activate the “Speed” checkbox and set your desired speed in the list.
The dialogue box displays the monitoring cases active under the given input conditions: The active monitoring area appears in the box of the sensor to which it is assigned for the monitoring case in question. In the example there are two sensors. Under the set input conditions, two monitoring cases are active at one time (simultaneous monitoring cases).
The names of the active monitoring cases are displayed on the status bar at the bottom of the dialogue box.
46
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
Page 47
9.9 Monitoring protective fields You have the option of monitoring the space contour and the defined protective fields in operation, by means of a connected PC.
• •
From the menu choose Monitoring area – Monitor . Or click on the “Monitoring area” button on the toolbar.
The active sensor with the active monitoring case is displayed on-screen. (In the example, two sensors are logged on and two monitoring cases active simultaneously.) The status bar at the bottom of the screen contains a colour key for on-screen display of the protective field and warning field. Saving a defined space contour You can receive and save the defined space contour of a sensor. In this way, when error shutdowns occur you can check at which point the protective field was infringed.
• •
From the menu choose LSI – Tools – Measurements – Record Measurements. Specify the file name under which you want to save the measured values and click on “OK”.
This dialogue box appears.
• • •
Click on “OK”. From the menu choose Monitoring area – Monitor. Or click on the “Monitor Monitoring area” button on the toolbar.
The measurements are recorded. Stop recording:
• •
Deactivate the Monitoring area – Monitor menu option. From the menu choose LSI – Tools – Measurements – Stop recording.
Play back recorded measurements:
• •
From the menu choose LSI – Tools – Measurements – Play Back Measurements. Select the file you want and click on “OK”.
The measurements are played back. Where the space contour protrudes into the protective field it is represented in red. The toolbar contains six additional buttons with which you can control the recording process as on a CD player. Stop playback:
•
Deactivate the LSI – Tools – Measurements – Play Back Measurements menu option.
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
47
Page 48
9.10 Monitoring inputs and outputs You can monitor and log the switching states of the inputs and outputs of the LSI. You can save the retrieved data to an ASCII file for further evaluation.
•
From the menu choose LSI – Tools – I/O Monitor.
This dialogue box appears.
•
Click on “Connect”.
The states of the inputs and outputs and the active monitoring cases are displayed at the top of the box and also logged as ASCII text. If you are using the LSI on a vehicle and have connected incremental encoders, you can read off the speed data and the difference in speed between the encoders and record the data during operation for example.
Stop recording: Click on “Stop”. The connection to the LSI is cut and recording is stopped.
•
Change recording interval: Click on “Options” and set the interval as you wish.
•
Save data: Click on “Save As” and save the retrieved data as an ASCII file for further evaluation.
•
Stop monitoring inputs and outputs: Click on “Close”.
•
48
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
Page 49
9.11 Checking settings You can call up an overview at any time showing all the configuration and monitoring area settings. You can also print out the overview. Note: This page view does not show you the actual configuration active in the LSI, but only the settings you are currently editing on the PC. How to receive the active configuration from the LSI and print it is described in the next section.
•
From the menu choose File – Page View.
Several pages appear listing all the configuration settings in text and diagrams. You can check over your settings any time here. Scroll pages:
•
Click on the “Next” or “Previous” button as appropriate.
Switch view:
•
Click on the “One Page” / “Two Pages” button.
Change size of screen view: You can zoom the screen view in or out in two stages.
• •
Click on the “Zoom In” or “Zoom Out” button. The view is zoomed or unzoomed one stage. Or click on the place you want to zoom into. The view is zoomed one stage at the selected point.
Print page:
•
Click on the “Print” button.
8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved
49
Page 50
9.12 Receiving and saving a configuration Receive configuration from LSI You can receive the configuration data stored in the LSI to print or save it.
•
From the menu choose LSI - Configuration - Configuration Log.
The PC receives the current configuration from the LSI. The screen displays an overview of all the configuration settings stored in the LSI. Scroll pages:
•
Click on the “Next” or “Previous” button as appropriate.
Switch view:
•
Click on the “One Page” / “Two Pages” button.
Change size of screen view: You can zoom the screen view in or out in two stages.
• •
Click on the “Zoom In” or “Zoom Out” button. The view is zoomed or unzoomed one stage. Or click on the place you want to zoom into. The view is zoomed one stage at the selected point.
Print log:
•
Click on the “Print” button.
Save configuration log:
•
Click on the “Save” button.
The following dialogue box appears:
•
Specify the file name under which you want to save the configuration log and click on “OK”.
You can call up the saved file subsequently to edit the settings or transfer them to the LSI.
50