Page 31

9.4 Expanding the configuration This section shows you how you can expand your configuration to adapt it to your specific requirements. You can add sensors and monitoring areas and work with additional monitoring cases. You can also change the inputs and outputs and edit the settings for the address, the application variant and the restart behaviour. Note on the following subsections: There are two basic means of expanding the standard application, depending on the user category under which you are logged on: – If you are logged on as an “Authorised Client” you are automatically guided through all the steps, as when creating a new configuration (see section 9.3). – If you are logged on as “SICK Service”, you can only call up and alter specific individual settings. The following subsections describe these options. This means you do not need to read the entire section, but can go straight to the passages which are relevant to your application.

Logging on additional sensors

• • • • •

From the menu choose LSI – Configuration – Edit . Or choose the “Edit Configuration” button from the toolbar. From the “LSI Configuration” dialogue box select the “Sensors” tab. Click on “Add”. Log on all the sensors connected to your LSI one after the other and name them as you wish. You can log on up to four sensors.

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

31

Page 32

Defining additional monitoring areas

• • • • • •

From the menu choose LSI – Configuration – Edit . Or choose the “Edit Configuration” button from the toolbar. From the “LSI Configuration” dialogue box select the “Monitoring areas” tab. Click on “Add”. Log on all the monitoring areas you need one after the other and name them as you wish. Define the size and shape of the protective and warning fields for your application as described in the example in section 9.3.

Defining additional monitoring cases

•

From the menu choose LSI – Monitoring Cases – Edit .

The following dialogue box appears: View list of all monitoring cases: Click on “Overview”. You get a list of all defined monitoring cases, their input and output definitions and the active sensors and monitoring areas. Here you can keep a running check on your settings.

•

Check plausibility: Click on “Check”. During configuration you check here that the monitoring cases with their current settings are plausible. This can help you to detect any conflicts or errors.

•

To generate a new monitoring case: Click on “Add”. A series of dialogue boxes appears in which you can enter your settings as described in section 9.3. (You can alter any of the settings later).

•

To delete a monitoring case: Select the monitoring case you want to delete from the list and click on “Remove”.

•

To change a monitoring case: Select the monitoring case you want to change from the list and click on “Edit”. You can then make the change you want on the various tabs as described below:

•

32

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

Page 33

“Links” tab: This is where you define which monitoring area (comprising a protective field and a warning field) is to be monitored on which sensor.

“I/O Definitions” tab: This is where you set the input information on which you want activation of the monitoring case to be based: X = low or high, 0 = low, 1 = high. Also select the output to be switched in the event of an intrusion into the protective field. Note: Each input consists of two signals of which the states must always be inverted, e.g. for input A signals A1 and A2: – Input A low: A1 = 1 and A2 = 0 – Input A high: A1 = 0 and A2 = 1 The value set in the dialogue box always corresponds to the signal level of the assigned input A2, or B2, C2, D2. (For the wiring of the inputs see section 8.2.)

“Evaluation” tab: This is where you set how often (that is, in how many consecutive scans) the sensor must detect an object in the protective field before the configured outputs are shut off (between 2 and 16 scans are possible). This sets the response time of the LSI. Note: If you are using the LSI together with PLS type 101-316 for vehicle protection, the response time of the LSI is fixed at 270 ms.

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

33

Page 34

“Order” tab: Here you can set the order in which the monitoring cases are to be activated. – Any: After the current monitoring case, any other case may be activated. – Specific: After the current monitoring case, only the case you selected from the list below can be activated. – Alternative: After the current monitoring case, only one of the two cases you selected from the lists below can be activated. Note on specific and alternative order of activation: When programming the order, make sure only one input at a time changes state when switching monitoring cases. Order example: A B 1. 0 0 2. 1 0 3. 1 1 4. 0 1

Changing inputs and outputs

• • • • • •

34

From the menu choose LSI – Configuration – Edit . Or choose the “Edit Configuration” button from the toolbar. From the “LSI Configuration” dialogue box select the “I/O Definition” tab. Check the checkbox to indicate if you have connected incremental encoders. You can use incremental encoders if you are operating the LSI on a vehicle (see section 9.7). Select which inputs and outputs you are using by placing a check against them. Check the checkbox to indicate if external device monitoring (EDM) is to be actice for the outputs you are using.

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

Page 35

Changing address You can define whether the LSI is addressed by way of a universal address or single address.

• • • •

From the menu choose LSI – Configuration – Edit . Or choose the “Edit Configuration” button from the toolbar. From the “LSI Configuration” dialogue box select the “Address” tab. Select whether you want to use a universal or single address. Universal address (zero, recommended setting): If you set “Universal address”, the stored configuration can be transferred at a later time to any other LSI. Single address (between 5 and 126): If you set “Single address” you assign the LSI the address specified here for transferring the configuration. It is then only possible to reload a configuration at a later time if the address specified here and the one stored in the LSI match. This makes sense when you want to ensure that a configuration saved as a file can only be transmitted to a specific LSI unit.

Changing application variant You can also change the area of application of the LSI system at a later time.

• • • • •

From the menu choose LSI – Configuration – Edit . Or choose the “Edit Configuration” button from the toolbar. From the “LSI Configuration” dialogue box select the “Variant” tab. Select whether you want to use the LSI for area protection or for protection on a vehicle (e.g. an automated guided vehicle – AGV). Select which evaluation you want to use. Standard: This is the standard evaluation. Pixel suppression: In this setting, objects detected only by a single pixel per scan are ignored. This can be useful in preventing unintended shutdowns.

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

35

Page 36

Changing the restart behaviour You can change the settings for the restart behaviour and the start-up testing.

• • • •

From the menu choose LSI – Configuration – Edit. Or choose the “Edit Configuration” button from the toolbar. From the “LSI Configuration” dialogue box select the “Restart” tab. For the configured outputs OSSD A and B, select how the LSI is to restart after a protective field infringement. With restart inhibit: The system only restarts after a protective field infringement or a reset when the protective field is free and the restart button is pressed. Without delay (without restart inhibit): The system restarts as soon as the protective field is free after the preset response time (multiple scans). Restart delayed by n seconds: The system only restarts when the time set here has elapsed after the protective field has become free again. Use start-up testing: If you select this option, you must intentionally interrupt the protective field one time after switching on the system. Only then is the system ready for operation. (How to perform start-up testing is described in section 12.2).

Configuring incremental encoders If you want to evaluate the speed of a vehicle in vehicle protection mode, enter the data from the incremental encoders here. The “Incremental encoders available” checkbox on the “I/ O Definition” tab must be checked for this. (For detailed information on evaluation of the speed data of a vehicle refer to section 9.7.)

• • • • •

From the menu choose LSI – Configuration – Edit . Or choose the “Edit Configuration” button from the toolbar. From the “LSI Configuration” dialogue box select the “Incremental Encoders” tab. Enter the number of pulses per cm of travel for the incremental encoders C and D being used. Enter the maximum speed difference between incremental encoders C and D as a percentage.

Note: The maximum possible speed of the vehicle is displayed in the box. The minimum recordable speed is ±10 cm/s. For technical reasons, and for the sake of greater availability, lower speeds are ignored and interpreted as 0 cm/s.

36

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

Page 37

9.5 Editing/dimensioning fields Section 9.3 describes the basic way to edit a protective field or warning field. You can use rectangular, semi-circular or multiple segmented fields. You can draw the fields using the mouse or type in their co-ordinates. This section describes additional options of defining the size and shape of the protective and warning fields for your application. Various edit functions will assist you in drawing up the fields. The status bar at the bottom of the screen contains a colour key for on-screen display of the protective field and warning field. Notes: Protective fields require additional allowances, to cover the measurement error of the PLS for example. There are also specific dimensioning rules to follow, such as for use of the system on materials handling equipment in narrow aisles. Refer to the Technical Description of the PLS. After programming, check on the plant or vehicle that all monitoring areas are the correct size and shape! You can do this by intruding intentionally into the monitoring areas. Only start up the plant or vehicle when you are sure all monitoring areas are operating effectively!

Converting fields You can convert a field into a different shape – for example, a rectangular field into a segmented field.

•

From the menu choose Edit – Convert to .

These field shapes are available to choose from: – Segmented field: You can select various resolutions. The more segments a field has, the higher is its resolution. You can define the co-ordinates for each segment individually. – Rectangle: This is the default. Newly defined fields are always this shape, unless you select a different setting. You can adjust the height of the rectangle and the width at the right and left. – Semi-circle: Here you define the radius. – Segmented rectangle / Segmented semi-circle: You define a rectangle or a semi-circle and select the desired resolution (number of segments). The field is automatically converted into a segmented field with the appropriate dimensions. Note: Warning fields are always segmented fields. If you have defined a warning field as a rectangle or semi-circle, it is automatically converted into a segmented field with the appropriate dimensions.

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

37

Page 38

Changing the scale of a segmented field When you have defined a segmented field you can enlarge or reduce it in scale.

• •

From the menu choose Edit – Select All to select all the points in the field. Pick up one of the points with the mouse and drag the field to the size you want.

Each point is dragged on a measuring ray of the sensor away from or towards the zero as appropriate.

Copying and pasting fields You can copy fields to the clipboard and paste them at a different location, such as when you need several similar protective fields or warning fields. But you cannot mix field types: you can only paste a protective field back in as a protective field, and a warning field as a warning field.

• • •

From the menu choose Edit – Copy to copy the current field to the clipboard. From the “Active Field” list select another field of the same type (protective field or warning field). From the menu choose Edit – Paste to paste the field from the clipboard.

You can then edit the field you have just pasted as normal.

Saving individual fields You can save individual fields as files so they are available to be used in other configurations.

•

From the menu choose Edit – Copy To… and save the current field under the desired file name on the hard disk or on a floppy.

•

To insert the stored field at the desired location, such as in another configuration, choose Edit – Paste From and enter the file name and storage location.

The field is inserted. You can then edit the field as normal.

38

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

Page 39

Fixing co-ordinates When editing a segmented field you can fix one of the coordinates of a point. This may be necessary when the coordinate in question must not be changed, such as when configuring a protective field for a narrow alley.

• •

From the menu choose Edit – Field Co-ordinates. In the list select the point whose position you want to change and click on “Edit”.

This dialogue box appears.

• •

Enter the co-ordinates you want for x and y. Select which co-ordinate must not deviate from the entered value, for example “Fix X-value”, and click on “Calculate”.

The next closest point on a measuring ray with the desired coordinates is calculated.

•

The calculated co-ordinates are displayed. To accept them, click on “OK”.

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved

39

Page 40

9.6 Teaching-in a protective field You can teach-in protective fields. In the teach-in process the active sensor scans the defined space contour, and the LSI generates a protective field from the scan. You can influence the physical extent of the protective field by marking out its contour with a target board, for example. You have to check learned protective fields. You can also edit a learned protective field subsequently, just like any other segmented field. (This function is not available for the LSI used with PLS 101-316 .)

•

•

• •

From the “Active Field” list select the protective field you want to edit.

From the “Active Sensor” list select the sensor from which you want to receive the data.

From the menu choose Monitoring area – Teach-in. Or click on the “Teach-in Monitoring area” button on the toolbar.

The active sensor scans its surroundings and shows you the result. The contour you see on-screen is the largest possible extent of the protective field. (The precise contour of the protective field is based on the ambient dimensions).

•

If you want to reduce the size of the learned contour, run a target (e.g. a piece of cardboard, at least 10 x 10 cm in size) slowly along the edge of your desired protective field.

The contour of the protective field is reduced at the relevant point. On the screen you can track how the protective field adopts to the taught-in contour.

Note: To prevent fixed obstacles in the scanning plane subsequently producing false signals, 13 cm (= max. measuring error of LSI) is automatically deducted from the learned contour. Take this into account as appropriate when reviewing over the protective field.

•

40

To terminate teach-in, deactivate the “Teach-in Monitoring area” button.

8 008 310/M848/06-05-02 Technical Description • LSI © SICK AG • Industrial Safety Systems • Germany • All rights reserved