Page 21

DP1100

DATALOGIC

2.4.2 Mounting DP1100 DP1100 can be mounted on a wall or a panel. To do this: 1) Open the decoder as described in paragraph 2.3. If necessary, using the two mounting holes inside the DP1100 as a pattern, mark the panel or the wall with an appropriate object and then drill two pilot holes in the panel or in the wall. 2) Align the decoder and insert two appropriate screws (M5 x 35 UNI 6107 or M5 x 40) with their washers and then screw them into the panel or the wall until tight (see figure 2.8).

Figure 2.8 - Mounting DP1100

2.8 - Installation

Page 22

DATALOGIC

2.5

DP1100

POWER SUPPLY CONNECTIONS

All versions of DP1100 are powered from the AC mains (see paragraph 1.2). A connection cable terminated with the 4 pin male connector provided with the package is used. A.C. CONNECTION GND

3 LINE

2

1 NEUTRAL

4 PIN MALE CONNECTOR

Figure 2.9 - Power supply connector - Cable side view

2.6

MAIN SERIAL INTERFACE CONNECTIONS

The signals relative to the following serial interface types are available for the DP1100 main serial interface: EIA RS232 EIA RS485 POLLED EIA RS485 NON POLLED 20mA CURRENT LOOP DP1100 automatically recognizes the type of interface selected at each power on of the decoder. If the recognized interface type is not compatible with the current communication handshaking, then the system forces the XON/XOFF protocol. The parameters relative to the main interface (baud rate, data bits, etc.) can be defined using the Winhost utility program or Keyboard Mode programming or Host Mode programming. For more details refer to the section "Main Interface Menu" in the Help On Line of the Winhost utility program.

Installation - 2.9

Page 23

DP1100

DATALOGIC

Pinout The terminals of the internal connectors are numbered as illustrated in figure 2.10 depending on the model:

H1 models

J1

J2

1 SHIELD 2 C.L. GND 3 DRVCLOUT 4 DRVCLIN 5 GND485 6 TX232 / TXRX485+ / CLIN7 RTS232 / TXRX485- / CLIN+ 8 RX232 / RX485+ / CLOUT9 CTS232 / RX485- / CLOUT+ 10 SGND 11 RXAUX 12 CTSAUX 13 RTSAUX 14 TXAUX 1 2 3 4 1 2 3 4

J3

J4

1 WRONG+ 2 WRONG3 RIGHT+ 4 RIGHT5 NO READ+ 6 NO READ7 8 9 10 11 PS1AUX+ 12 PS1AUX13 GND1 14 VDC1

1 PS1+ 2 PS13 VDC1 4 GND1

H2 models

J1

J2 J3

J4

Figure 2.10 - Internal connectors pinouts

2.10 - Installation

1 SHIELD 2 C.L. GND 3 DRVCLOUT 4 DRVCLIN 5 GND485 6 TX232 / TXRX485+ / CLIN7 RTS232 / TXRX485- / CLIN+ 8 RX232 / RX485+ / CLOUT9 CTS232 / RX485- / CLOUT+ 10 SGND 11 RXAUX 12 CTSAUX 13 RTSAUX 14 TXAUX 1 PS2+ 2 PS21 2 3 4 3 VDC2 1 PS1+ 4 GND2 1 2 3 4 2 PS13 VDC1 4 GND1 1 RIGHT2+ 2 RIGHT23 RIGHT1+ 4 RIGHT15 NO READ1+ 6 NO READ17 PS2AUX+ 8 PS2AUX9 GND2 10 VDC2 11 PS1AUX+ 12 PS1AUX13 GND1 14 VDC1

Page 24

DATALOGIC

DP1100

Grounding Rules Shielding the communication cable is an effective way to protect against capacitive conduction and radiated interference, while the effect against noise due to inductive coupling is small. In any case, the shielding effect occurs only if the shield is grounded; otherwise the entire voltage of the shielded material will be floating and will not give protection against electrical noise. When installing the DP1100 in a large system, remember that a voltage drop may occur between ground connections made at distant points. This could be the undesirable effect of variable electromagnetic fields due, for instance, to the presence of engines, leakage currents, lightning or other sources. For long distances between the devices (about 50 meters, but this length depends widely on the environment), the voltage drop between ground connections can be 100 V or higher. If you ground the shield in several points the voltage drop across the shield will cause a current, increasing the noise on the signal wires. Therefore, to avoid damage to the device drivers and loss of system performance in general, the shield should be grounded at most in one point only. Since the shielding protection is more effective near to the ground connection, it is advisable to ground the shield where electric noise is higher. Typically this is done at the DP1100 device. The shield is provided on J1 Pin 1.

Bad shielding effect Good shielding effect Figure 2.11 - Shield grounding effect

Installation - 2.11

Page 25

DP1100

DATALOGIC

RS232 Interface The serial interface is used in this case for point to point connections; it handles communication with the host computer and allows both transmission of code data and the configuration of the decoder. The terminals of the external cable must be connected to the following pins of connector J1 (see figure 2.10) for RS232 interface connection: RS232 connection Pin

Name

Function

6 7 8 9 10

TX232 RTS232 RX232 CTS232 SGND

Transmitted Data Request to Send Received Data Clear to Send Signal Ground

DP1100

USER INTERFACE 6

TX232

7

RTS232

8

RX232

9

CTS232

10 SGND

RXD DCD TXD DTR SGND

MAXIMUM LENGTH: 15 m RTS/CTS HARDWARE HANDSHAKING ENABLED

Figure 2.12 - RS232 main interface connections

To select this interface type, follow the instructions in paragraph 2.3.1 "Main Serial Interface Selection".

2.12 - Installation

Page 26

DATALOGIC

DP1100

Figure 2.13 - RS232 control signals

The RTS232 and CTS232 signals control data transmission and synchronize the connected devices. If the RTS/CTS handshaking protocol is enabled, the DP1100 activates the RTS232 output to indicate a message is to be transmitted. The receiving unit activates the CTS232 input to enable the transmission.

RS485 Non Polled Interface The RS485 NON POLLED interface is a Full Duplex interface. The NON POLLED configuration is used for point to point connections over longer distances than those acceptable for RS232 communications or in electrically noisy environments. The terminals of the external cable must be connected to the following pins of connector J1 (see figure 2.10) for RS485 NON POLLED communications: RS485 NON POLLED connection Pin

Name

Function

5 6 7 8 9

GND485 TXRX485+ TXRX485RX485+ RX485-

Signal Ground RS485 Output (+) RS485 Output (-) RS485 Input (+) RS485 Input (-) Installation - 2.13

Page 27

DP1100

DATALOGIC

DP1100

USER INTERFACE 5

GND485

6

TXRX485+

7

TXRX485-

8

RX485+

9

RX485-

RS485REF RX485

TX485

MAXIMUM LENGTH: 1200 m

Figure 2.14 - RS485 NON POLLED connections

To select this interface type, follow the instructions in paragraph 2.3.1 "Main Serial Interface Selection" .

RS485 Polled Interface The terminals of the external cable must be connected to the following pins of connector J1 (see figure 2.10) for RS485 POLLED communications: RS485 POLLED connection Pin

Name

Function

5 6 7

GND485 TXRX485+ TXRX485-

Signal Ground RS485 Input/output (+) RS485 Input/output (-)

DP1100

MULTIPLEXER 5

GND485

6

TXRX485+

7

TXRX485-

RS485REF +RTX485 -RTX485

MAXIMUM LENGTH: 1200 m

Figure 2.15 - RS485 POLLED connections

To select this interface type, follow the instructions in paragraph 2.3.1 "Main Serial Interface Selection". 2.14 - Installation

Page 28

DATALOGIC

DP1100

For this interface type, the multidrop address must also be set on the DIP switch as shown in the figure below. Refer to paragraph 2.3 for details on how to open the DP1100. Record this information for further setup of the multidrop line.

5 4 3 2 1

ON

Figure 2.16 - DIP switch for multiplexer address selection

The following table shows the multiplexer address settings where: 0 = ON 1 = OFF

5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

4 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0

Position 3 2 1 1 1 1 1 0 1 0 0 1 0 1 0 0 0 0 1 1 1 1 1 0 1 0 0 1 0 1 0 0 0 0

Address 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

4 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0

Position 3 2 1 1 1 1 1 0 1 0 0 1 0 1 0 0 0 0 1 1 1 1 1 0 1 0 0 1 0 1 0 0 0 0

Address 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Installation - 2.15

Page 29

DP1100

DATALOGIC

Example address selections for DP1100 Multidrop connections: Address 1

Address 9

Address 20

5 4 3 2 1

5 4 3 2 1

5 4 3 2 1

ON

ON

ON

Figure 2.17 - DP1100 multidrop address selections

The following figure shows a multidrop configuration with DP1100 decoders and a multiplexer connected. max. 2 m.

DP1100

6

#x

7

120 Ohm

5 DP1100

6

#1

7 5 max. 1200 m.

DP1100

6

#0

7 5

TXRX485+ TXRX485GND485 three wires + shield +RTX485

MUX

-RTX485 RS485REF SHIELD

120 Ohm Figure 2.18 - DP1100 multidrop connection to a multiplexer

2.16 - Installation

Page 30

DATALOGIC

DP1100

20 mA Current Loop Interface The DP1100 has two current generators (one for transmission and one for reception), allowing active and passive type connections. The terminals of the external cable must be connected to the following pins of connector J1 (see figure 2.10) for 20 mA Current Loop communications: 20 mA C.L. connection Pin

Name

Function

2 3 4 6 7 8 9

C.L. GND DRVCLOUT DRVCLIN C.L. INC.L .IN+ C.L. OUTC.L. OUT+

Generator Reference Output Current Generator Input Current Generator Current Loop Input (-) Current Loop Input (+) Current Loop Output (-) Current Loop Output (+)

DP1100

USER INTERFACE

I = 20 mA 3

DRVCLOUT

9 C.L. OUT+ 8

C.L. OUT-

2

C.L. GND

4

DRVCLIN

SGND

I = 20 mA

7 C.L. IN+ 6

C.L. IN-

2

C.L. GND SGND

MAXIMUM LENGTH: 300 m

Figure 2.19 - 20 mA C.L. active connections

Installation - 2.17