Page 21
DP1100
DATALOGIC
2.4.2 Mounting DP1100 DP1100 can be mounted on a wall or a panel. To do this: 1) Open the decoder as described in paragraph 2.3. If necessary, using the two mounting holes inside the DP1100 as a pattern, mark the panel or the wall with an appropriate object and then drill two pilot holes in the panel or in the wall. 2) Align the decoder and insert two appropriate screws (M5 x 35 UNI 6107 or M5 x 40) with their washers and then screw them into the panel or the wall until tight (see figure 2.8).
Figure 2.8 - Mounting DP1100
2.8 - Installation
Page 22
DATALOGIC
2.5
DP1100
POWER SUPPLY CONNECTIONS
All versions of DP1100 are powered from the AC mains (see paragraph 1.2). A connection cable terminated with the 4 pin male connector provided with the package is used. A.C. CONNECTION GND
3 LINE
2
1 NEUTRAL
4 PIN MALE CONNECTOR
Figure 2.9 - Power supply connector - Cable side view
2.6
MAIN SERIAL INTERFACE CONNECTIONS
The signals relative to the following serial interface types are available for the DP1100 main serial interface: EIA RS232 EIA RS485 POLLED EIA RS485 NON POLLED 20mA CURRENT LOOP DP1100 automatically recognizes the type of interface selected at each power on of the decoder. If the recognized interface type is not compatible with the current communication handshaking, then the system forces the XON/XOFF protocol. The parameters relative to the main interface (baud rate, data bits, etc.) can be defined using the Winhost utility program or Keyboard Mode programming or Host Mode programming. For more details refer to the section "Main Interface Menu" in the Help On Line of the Winhost utility program.
Installation - 2.9
Page 23
DP1100
DATALOGIC
Pinout The terminals of the internal connectors are numbered as illustrated in figure 2.10 depending on the model:
H1 models
J1
J2
1 SHIELD 2 C.L. GND 3 DRVCLOUT 4 DRVCLIN 5 GND485 6 TX232 / TXRX485+ / CLIN7 RTS232 / TXRX485- / CLIN+ 8 RX232 / RX485+ / CLOUT9 CTS232 / RX485- / CLOUT+ 10 SGND 11 RXAUX 12 CTSAUX 13 RTSAUX 14 TXAUX 1 2 3 4 1 2 3 4
J3
J4
1 WRONG+ 2 WRONG3 RIGHT+ 4 RIGHT5 NO READ+ 6 NO READ7 8 9 10 11 PS1AUX+ 12 PS1AUX13 GND1 14 VDC1
1 PS1+ 2 PS13 VDC1 4 GND1
H2 models
J1
J2 J3
J4
Figure 2.10 - Internal connectors pinouts
2.10 - Installation
1 SHIELD 2 C.L. GND 3 DRVCLOUT 4 DRVCLIN 5 GND485 6 TX232 / TXRX485+ / CLIN7 RTS232 / TXRX485- / CLIN+ 8 RX232 / RX485+ / CLOUT9 CTS232 / RX485- / CLOUT+ 10 SGND 11 RXAUX 12 CTSAUX 13 RTSAUX 14 TXAUX 1 PS2+ 2 PS21 2 3 4 3 VDC2 1 PS1+ 4 GND2 1 2 3 4 2 PS13 VDC1 4 GND1 1 RIGHT2+ 2 RIGHT23 RIGHT1+ 4 RIGHT15 NO READ1+ 6 NO READ17 PS2AUX+ 8 PS2AUX9 GND2 10 VDC2 11 PS1AUX+ 12 PS1AUX13 GND1 14 VDC1
Page 24
DATALOGIC
DP1100
Grounding Rules Shielding the communication cable is an effective way to protect against capacitive conduction and radiated interference, while the effect against noise due to inductive coupling is small. In any case, the shielding effect occurs only if the shield is grounded; otherwise the entire voltage of the shielded material will be floating and will not give protection against electrical noise. When installing the DP1100 in a large system, remember that a voltage drop may occur between ground connections made at distant points. This could be the undesirable effect of variable electromagnetic fields due, for instance, to the presence of engines, leakage currents, lightning or other sources. For long distances between the devices (about 50 meters, but this length depends widely on the environment), the voltage drop between ground connections can be 100 V or higher. If you ground the shield in several points the voltage drop across the shield will cause a current, increasing the noise on the signal wires. Therefore, to avoid damage to the device drivers and loss of system performance in general, the shield should be grounded at most in one point only. Since the shielding protection is more effective near to the ground connection, it is advisable to ground the shield where electric noise is higher. Typically this is done at the DP1100 device. The shield is provided on J1 Pin 1.
Bad shielding effect Good shielding effect Figure 2.11 - Shield grounding effect
Installation - 2.11
Page 25
DP1100
DATALOGIC
RS232 Interface The serial interface is used in this case for point to point connections; it handles communication with the host computer and allows both transmission of code data and the configuration of the decoder. The terminals of the external cable must be connected to the following pins of connector J1 (see figure 2.10) for RS232 interface connection: RS232 connection Pin
Name
Function
6 7 8 9 10
TX232 RTS232 RX232 CTS232 SGND
Transmitted Data Request to Send Received Data Clear to Send Signal Ground
DP1100
USER INTERFACE 6
TX232
7
RTS232
8
RX232
9
CTS232
10 SGND
RXD DCD TXD DTR SGND
MAXIMUM LENGTH: 15 m RTS/CTS HARDWARE HANDSHAKING ENABLED
Figure 2.12 - RS232 main interface connections
To select this interface type, follow the instructions in paragraph 2.3.1 "Main Serial Interface Selection".
2.12 - Installation
Page 26
DATALOGIC
DP1100
Figure 2.13 - RS232 control signals
The RTS232 and CTS232 signals control data transmission and synchronize the connected devices. If the RTS/CTS handshaking protocol is enabled, the DP1100 activates the RTS232 output to indicate a message is to be transmitted. The receiving unit activates the CTS232 input to enable the transmission.
RS485 Non Polled Interface The RS485 NON POLLED interface is a Full Duplex interface. The NON POLLED configuration is used for point to point connections over longer distances than those acceptable for RS232 communications or in electrically noisy environments. The terminals of the external cable must be connected to the following pins of connector J1 (see figure 2.10) for RS485 NON POLLED communications: RS485 NON POLLED connection Pin
Name
Function
5 6 7 8 9
GND485 TXRX485+ TXRX485RX485+ RX485-
Signal Ground RS485 Output (+) RS485 Output (-) RS485 Input (+) RS485 Input (-) Installation - 2.13
Page 27
DP1100
DATALOGIC
DP1100
USER INTERFACE 5
GND485
6
TXRX485+
7
TXRX485-
8
RX485+
9
RX485-
RS485REF RX485
TX485
MAXIMUM LENGTH: 1200 m
Figure 2.14 - RS485 NON POLLED connections
To select this interface type, follow the instructions in paragraph 2.3.1 "Main Serial Interface Selection" .
RS485 Polled Interface The terminals of the external cable must be connected to the following pins of connector J1 (see figure 2.10) for RS485 POLLED communications: RS485 POLLED connection Pin
Name
Function
5 6 7
GND485 TXRX485+ TXRX485-
Signal Ground RS485 Input/output (+) RS485 Input/output (-)
DP1100
MULTIPLEXER 5
GND485
6
TXRX485+
7
TXRX485-
RS485REF +RTX485 -RTX485
MAXIMUM LENGTH: 1200 m
Figure 2.15 - RS485 POLLED connections
To select this interface type, follow the instructions in paragraph 2.3.1 "Main Serial Interface Selection". 2.14 - Installation
Page 28
DATALOGIC
DP1100
For this interface type, the multidrop address must also be set on the DIP switch as shown in the figure below. Refer to paragraph 2.3 for details on how to open the DP1100. Record this information for further setup of the multidrop line.
5 4 3 2 1
ON
Figure 2.16 - DIP switch for multiplexer address selection
The following table shows the multiplexer address settings where: 0 = ON 1 = OFF
5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
4 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0
Position 3 2 1 1 1 1 1 0 1 0 0 1 0 1 0 0 0 0 1 1 1 1 1 0 1 0 0 1 0 1 0 0 0 0
Address 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
4 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0
Position 3 2 1 1 1 1 1 0 1 0 0 1 0 1 0 0 0 0 1 1 1 1 1 0 1 0 0 1 0 1 0 0 0 0
Address 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Installation - 2.15
Page 29
DP1100
DATALOGIC
Example address selections for DP1100 Multidrop connections: Address 1
Address 9
Address 20
5 4 3 2 1
5 4 3 2 1
5 4 3 2 1
ON
ON
ON
Figure 2.17 - DP1100 multidrop address selections
The following figure shows a multidrop configuration with DP1100 decoders and a multiplexer connected. max. 2 m.
DP1100
6
#x
7
120 Ohm
5 DP1100
6
#1
7 5 max. 1200 m.
DP1100
6
#0
7 5
TXRX485+ TXRX485GND485 three wires + shield +RTX485
MUX
-RTX485 RS485REF SHIELD
120 Ohm Figure 2.18 - DP1100 multidrop connection to a multiplexer
2.16 - Installation
Page 30
DATALOGIC
DP1100
20 mA Current Loop Interface The DP1100 has two current generators (one for transmission and one for reception), allowing active and passive type connections. The terminals of the external cable must be connected to the following pins of connector J1 (see figure 2.10) for 20 mA Current Loop communications: 20 mA C.L. connection Pin
Name
Function
2 3 4 6 7 8 9
C.L. GND DRVCLOUT DRVCLIN C.L. INC.L .IN+ C.L. OUTC.L. OUT+
Generator Reference Output Current Generator Input Current Generator Current Loop Input (-) Current Loop Input (+) Current Loop Output (-) Current Loop Output (+)
DP1100
USER INTERFACE
I = 20 mA 3
DRVCLOUT
9 C.L. OUT+ 8
C.L. OUT-
2
C.L. GND
4
DRVCLIN
SGND
I = 20 mA
7 C.L. IN+ 6
C.L. IN-
2
C.L. GND SGND
MAXIMUM LENGTH: 300 m
Figure 2.19 - 20 mA C.L. active connections
Installation - 2.17