Page 27
Installing Your Hardware This chapter provides the information needed to install the readers, their mounting brackets, their power supplies, and interface boxes. Items include: • RS-232 installations • master/slave installations Because of the variety of uses for the information, users of and those responsible for applying this information must satisfy themselves as to the acceptability of each application and use of the program. In no event will Allen-Bradley Company be responsible or liable for indirect or consequential damages resulting from the use of application of this information. The examples shown in this document are intended solely to illustrate the principles of the bar code reader and some of the methods used to apply them. Particularly because of the many requirements associated with any particular installation, Allen-Bradley Company cannot assume responsibility or liability for actual use based upon the illustrative uses and applications.
Publication 2755-6.13
Page 28
4–2
Installing Your Hardware
RS232 Installations
Refer to the following sections to install your system hardware, based on the type of equipment you select:
PLC or PC to the Reader 1. Make sure your system is planned properly. Refer to Chapter 3 for information about planning your system. 2. Refer to Appendix A for dimensions of readers, mounting brackets, power supplies, and interface boxes. Cable pinouts are shown in Appendix B. 3. Install the mounting bracket (Catalog Nos. 77126-898-01 or 77126-898-02) for the readers (Catalog Nos. 2755-LHR-5B, 2755-LHR-3C, 2755-LHR-5C, and 2755-LHR-5BX1). Make sure placement of the mounting bracket allows you to connect the reader to the PLC or PC and power supply. Also make sure bracket placement provides the correct read range for the reader. The maximum cable length from the reader to another device is 50 ft. (15.24 m) when using RS232. Use RS422 when distances reach up to 2000 feet (609.6 m). 4. Mount the reader to the mounting bracket. 5. Install your PLC or PC. For proper installation refer to the installation information provided with each product.
Mounting Bracket
Reader
Publication 2755-6.13
Page 29
Installing Your Hardware
4–3
6. Connect the null modem cable (Catalog No. 2755-LHC-11) to the PLC or PC (9–pin connector) and the reader (25–pin connector). 7. Place the power supply (Catalog No. 77126-896-01) within 12 ft. (3.66 m) of the reader. Connect the power supply to the reader.
Power Supply
To Power Receptacle
Grounding Pin
77126–896–01 To Reader (9-pin connector) 2755–LHC–11
To Reader (25-pin connector) To PC (9-pin connector) Reader
8. Connect the power supply cable to the power supply and to the power receptacle supplying 100/240V ac. When power is applied to the reader, the green LED flashes on and off, then the red LED turns on and remains on. A beep is emitted from the reader as well, indicating the reader has power. Scan beams are also emitted from the reader.
Publication 2755-6.13
Page 30
4–4
Installing Your Hardware
PLC or PC to the Reader and Interface Box 1. Make sure your system is planned properly. Refer to Chapter 3 for information about planning your system. 2. Refer to Appendix A for dimensions of readers, mounting brackets, power supplies, and interface boxes. Cable pinouts are shown in Appendix B. 3. Install the mounting bracket (Catalog Nos. 77126-898-01 or 77126-898-02) for the readers (Catalog Nos. 2755-LHR-5B, 2755-LHR-3C, 2755-LHR-5C, and 2755-LHR-5BX1). Make sure placement of the mounting bracket allows you to connect the reader to the PLC or PC, interface box, and power supply. Also make sure bracket placement provides the correct read range for the reader. The maximum cable length from the reader to another device is 50 ft. (15.24 m) when using RS232. Use RS422 when distances reach up to 2000 feet (609.6 m). 4. Mount the reader to the mounting bracket.
Mounting Bracket
Reader
5. Install your PLC or PC. For proper installation refer to the installation information provided with each product.
Publication 2755-6.13
Page 31
Installing Your Hardware
4–5
6. Connect the null modem cable (Catalog No. 2755-LHC-11) to the PLC or PC (9–pin connector) and the reader (25–pin connector). 7. Place the power supply (Catalog No. 77126-896-01) within 12 ft. (3.66 m) of the reader. Connect the power supply to the reader. 8. Connect the interface box cable (Catalog No. 2755-LHC-2) to the interface box and the reader. The 15–pin end of the cable connects to the reader and the 8–pin end to the interface box. Make sure you lock into place the interface box end of the cable.
Power Supply
To Power Receptacle
Grounding Pin
77126–896–01 To Reader (9-pin connector)
To PC (9-pin connector)
2755–LHC–11
8–pin connector
To Reader (25-pin connector)
To Reader (15-pin connector)
Reader
2755–LHC–2
Interface Box
9. Connect your sensor (PhotoSwitch 6000 or 9000 Series) to the interface box by attaching the sensor leads to the sensor terminal block inside the interface box. The sensor itself will have the proper connection scheme imprinted on its housing. Follow the method shown there. For instance, brown to +12V out, white to sink-in, blue to common, black to source. (Black is often disregarded.)
Publication 2755-6.13
Page 32
4–6
Installing Your Hardware
Sensor Terminal Block
Interface Box
Common Sensor Cable
+12V out Sink in
Sensor housing
10. Mount the interface box (Catalog No. 2755-LHB-1). Its dimensions are shown in Appendix A.
Screw Holes
Publication 2755-6.13
Screw Holes
Page 33
Installing Your Hardware
!
ATTENTION: Before connecting power, make sure that the 3 power leads from the interface box power cord are connected to their proper locations on the power terminal block and grounding posts inside the interface box case. A domestic and a European example are shown in the following illustration. Make sure that the interface box is connected to an ac source per local/regional electrical codes.
US 3–Wire Color Code To Grounding post
4–7
Power Terminal Block
N Ln In Interface Box Cover Grn Blk Wht
European 3–Wire Color Code To Grounding post
N Ln In Grounding posts Grn/Yel Blue Brn
Power Cable Voltage Selector Switch To Power Receptacle
!
ATTENTION: Before applying power to the interface box, make sure the voltage selector switch is in the correct position.
11. Connect the interface box to the power receptacle supplying 100/240V ac. 12. Connect the power supply cable to the power supply and to the power receptacle supplying 100/240V ac. When power is applied to the reader, the green LED flashes on and off, then the red LED turns on and remains on. A beep is emitted from the reader as well, indicating the reader has power. Scan beams are also emitted from the reader. When power is applied to the interface box, the green 12V LED turns on and remains on.
Publication 2755-6.13
Page 34
4–8
Installing Your Hardware
Master/slave Installation (Without Interface Box)
Refer to the following steps to install your system hardware:
PLC or PC to the Reader, Reader to a Second Reader 1. Make sure your system is planned properly. Refer to Chapter 3 for information about planning your system. 2. Refer to Appendix A for dimensions of readers, mounting brackets, power supplies and interface boxes. Cable pinouts are shown in Appendix B. 3. Install the mounting brackets (Catalog Nos. 77126-898-01 or 77126-898-02) for the readers (Catalog Nos. 2755-LHR-5B, 2755-LHR-3C, 2755-LHR-5C and 2755-LHR-5BX1). Make sure placement of the mounting brackets allows you to connect the first reader to the PLC or PC, interface box, and power supply. It should also allow you to connect the second reader to the interface box and a power supply. Also make sure bracket placement provides the correct read range for both readers. The maximum cable length from the reader to another device is 50 ft. (15.24 m) when using RS232. Use RS422 when distances reach up to 2000 feet (609.6 m). 4. Mount each reader to its mounting bracket.
Mounting Bracket
Reader
5. Install your PLC or PC. For proper installation refer to the installation information provided with each product.
Publication 2755-6.13
Page 35
Installing Your Hardware
4–9
6. Connect the PLC or PC to the master reader (25–pin connector). 7. Connect the Master/Slave cable (Catalog No. 2755-LHC-1) to the first reader (master) and the second reader (slave). The 15-pin end of the cable connects to the master reader. 8. Connect the 25-pin end of the cable to the slave reader. 9. Connect each reader to a power supply.
Power Supply
To Power Receptacle
Grounding Pin
77126–896–01 To Reader (9-pin connector) 2755–LHC–11
To Reader (25-pin connector) To PC (9-pin connector)
Master Reader To Reader (15-pin connector) 2755–LHC–1 To Reader (25-pin connector) Slave Reader To Reader (9-pin connector) 77126–896–01
Power Supply
To Power Receptacle
Grounding Pin
Publication 2755-6.13
Page 36
4–10
Installing Your Hardware
!
ATTENTION: To prevent unsuccessful programming of your master/slave scanner configuration, follow this setup sequence when installing master/slave option: 1. Connect master and slave scanners with the appropriate master/slave cable. 2. Connect Allen–Bradley StrataScan Configuration software to the master scanner. 3. Apply power to the master/slave units. 4. Program the master scanner as you would a regular scanner with the StrataScan Configuration software. 5. The master scanner automatically programs the slave to the same parameters.
10. Connect each power supply cable to each power supply and to the power receptacle supplying 100/240V ac. When power is applied to each reader, the green LED flashes on and off, then the red LED turns on and remains on. A beep is emitted from each reader as well, indicating the reader has power. Scan beams are also emitted from each reader.
Master/slave Installation (With Interface Box)
Refer to the following steps to install your system hardware:
PLC or PC to the Reader, Interface Box, and a Second Reader 1. Make sure your system is planned properly. Refer to Chapter 3 for information about planning your system. 2. Refer to Appendix A for dimensions of readers, mounting brackets, power supplies and interface boxes. Cable pinouts are shown in Appendix B. 3. Install the mounting brackets (Catalog Nos. 77126-898-01 or 77126-898-02) for the readers (Catalog Nos. 2755-LHR-5B, 2755-LHR-3C, 2755-LHR-5C, and 2755-LHR-5BX1). Make sure placement of the mounting brackets allows you to connect the first reader to the PLC or PC, interface box, and power supply. It should also allow you to connect the second reader to the interface box and a power supply. Also make sure bracket placement provides the correct read range for both readers. The maximum cable length from the reader to another device is 50 ft. (15.24 m) when using RS232. Use RS422 when distances reach up to 2000 feet (609.6 m).
Publication 2755-6.13
Page 37
Installing Your Hardware
4–11
4. Mount each reader to its mounting bracket.
Mounting Bracket
Reader
5. Install your PLC or PC. For proper installation refer to the installation information provided with each product.
Publication 2755-6.13
Page 38
4–12
Installing Your Hardware
6. Connect the PLC or PC to the first reader. 7. Connect the Master/Slave Interface Box Cable (Catalog No. 2755-LHC-3) to the first reader (master) and the interface box. Make sure you lock into place the interface box end of the cable. The 15-pin end of the cable connects to the master reader. 8. Connect each reader to a power supply. 9. Connect the Master/Slave Interface Box Cable (Catalog No. 2755-LHC-3) to the second reader (slave). The 25-pin end of the cable connects to the slave reader.
Power Supply
To Power Receptacle
Grounding Pin
77126–896–01 To Reader (9-pin connector)
To PC (9-pin connector)
2755–LHC–11
To interface box (8–pin connector)
2755–LHC–3
To Reader (25-pin connector) To Reader (15-pin connector)
Master Reader
To Reader (25-pin connector)
Slave Reader To Reader (9-pin connector) To Power Receptacle 77126–896–01
Power Supply
Publication 2755-6.13
Grounding Pin
Page 39
Installing Your Hardware
!
ATTENTION: Before connecting power, make sure that the 3 power leads from the interface box power cord are connected to their proper locations on the power terminal block and grounding posts inside the interface box case. A domestic and a European example are shown in the following illustration. Make sure that the interface box is connected to an ac source per local/regional electrical codes.
US 3–Wire Color Code To Grounding post
4–13
Power Terminal Block
N Ln In Interface Box Cover Grn Blk Wht
European 3–Wire Color Code To Grounding post
N Ln In Grounding posts Grn/Yel Blue Brn
Power Cable
To Power Receptacle
!
ATTENTION: Before applying power to the interface box, make sure the voltage selector switch is in the correct position.
10. Mount the interface box. The dimensions of the interface box are shown in Appendix A.
Screw Holes
Screw Holes
11. Connect the interface box to the power receptacle supplying 100/240V ac. 12. Connect each power supply cable to each power supply and to the power receptacle supplying 100/240V ac.
Publication 2755-6.13
Page 40
4–14
Installing Your Hardware
When power is applied to each reader, the green LED flashes on and off, then the red LED turns on and remains on. A beep is emitted from each reader as well, indicating the reader has power. Scan beams are also emitted from each reader. When power is applied to the interface box, the green 12V LED turns on and remains on.
Publication 2755-6.13