For the Wenglor FIS-6300

Page 321

Appendices Codabar Interleaved 2 of 5 UPC/EAN Code 128/EAN 128

Code 93 PDF417 Pharmacode Data Matrix QR Code BC412 RSS-14 RSS Limited RSS Expanded MicroPDF417 I/O Parameters Power On/Reset Counts Time Since Reset Service Message Serial Verification Beeper Quality Output Symbol Data Output Read Duration Output Noread Message Bad Symbol Message No Symbol Message 1D/Stacked Symbology Qualification 2D Symbology Qualification

Frame Information FIS-6300 ESD Imager User’s Manual

<K471,status,start/stop match,start/stop output,large intercharacter gap,fixed symbol length status,symbol length,check digit type,check digit output> <K472,status,check digit status,check digit output status,symbol length #1, symbol length #2, guard bar status,range mode status> <K473,UPC status,EAN status,supplemental status,separator status,separator character,supplemental type,format UPC-E as UPC-A> <K474,status,fixed symbol length status,fixed symbol length,EAN 128 status,output format,application record separator status,application record separator character,application record brackets,application record padding> <K475,status,fixed symbol length status,symbol length> <K476,status,[unused],fixed symbol length status,fixed symbol length,[unused],codeword collection> <K477,status,fixed bar count status,fixed bar count,minimum bar count,bar width mode,direction,fixed threshold value> <K479,ECC 200 status, ECC 000 status,ECC 050 status, ECC 080 status,ECC 100 status,ECC 140 status,ECC 120 status,ECC 130 status> <K480,status> <K481,status,check digit output,fixed symbol length status,fixed symbol length> <K482,status> <K483,status> <K484,status,fixed symbol length status,fixed symbol length> <K485,status,[unused],fixed symbol length status,fixed symbol length> <K406,power-on,resets,power-on saves,power-on flash saves> <K407,hours,minutes> <K409,status,service message,threshold,resolution> <K701,serial command echo status,serial command beep status,control/hex output> <K702,status> <K704,quality output separator,decodes/trigger status> <K705,symbol data output status,when to output> <K706,status,separator> <K714,status,message> <K715,[unused],message> <K716,[unused],message> <K717,minimum number of bars,minimum number of qualified scan lines,start/stop status> <K718,finder pattern status,symbol size status,symbol size 1,symbol size 2,symbol size tolerance,dimension status,dimension 1,dimension 2,dimension tolerance,orientation status,orientation value> <K734,output frame number,output coordinates>

A-7

Page 322

Serial Configuration Commands LED Configuration Image Output

<K737,LED mode,ISO/IEC 16022 grade> <K739,image output mode,communication port,file format,jpeg quality> Target/Flood LEDs <K750,green flash LED status,target pattern LED status,green flash duration> Database Identifier Output <K759,status,separator> EZ Button <K770,global status,default on power-on,load configuration database,save for power-on> EZ Button Modes <K771,single beep,two beeps,three beeps,four beeps> Trend Analysis Output 1 <K780,trend analysis mode,trigger evaluation period,number to output on> Trend Analysis Output 2 <K781,trend analysis mode,trigger evaluation period,number to output on> Trend Analysis Output 3 <K782,trend analysis mode,trigger evaluation period,number to output on> Diagnostic Output 1 <K790,unused 1,service unit> Diagnostic Output 2 <K791,unused 1,service unit> Diagnostic Output 3 <K792,unused 1,service unit> ISO/IEC 16022 Symbol Quality Output 1 <K800,output on symbol contrast,symbol contrast threshold,output on print growth,print growth threshold,output on axial non-uniformity,axial non-uniformity threshold,output on UEC,UEC threshold> ISO/IEC 16022 Symbol Quality Output 2 <K801,output on symbol contrast,symbol contrast threshold,output on print growth,print growth threshold,output on axial non-uniformity,axial non-uniformity threshold,output on UEC,UEC threshold> ISO/IEC 16022 Symbol Quality Output 3 <K802,output on symbol contrast,symbol contrast threshold,output on print growth,print growth threshold,output on axial non-uniformity,axial non-uniformity threshold,output on UEC,UEC threshold> Configurable Output 1 <K810,output on,output state,pulse width,output mode> Configurable Output 2 <K811,output on,output state,pulse width,output mode> Configurable Output 3 <K812,output on,output state,pulse width,output mode> Symbol Quality Symbol Quality Separator/ Data Matrix <K708,symbol quality separator,data matrix output mode> Output Mode ISO/IEC 16022 Symbol Quality Output <K709,symbol contrast,print growth,axial non-uniformity,UEC> wenglor Symbol Quality Output <K710,percent cell damage,total read time,capture time,locate time,decode time,pixels per element,ECC level,matrix size,quiet zone> Static Validation Report <VAL> Matchcode Matchcode Type <K223,matchcode type,sequential matching,match start position,match length,wild card character,sequence on noread,sequence on mismatch> Number of Master Symbols <K224,number of master symbols> New Master Pin <K225,status> Enter Master Symbol Data <K231,master symbol number,master symbol data> Request Master Symbol Data <K231?,>[for all] or <K231?,master symbol number> Delete Master Symbol Data <K231,master symbol number,>

A-8

FIS-6300 ESD Imager User’s Manual

Page 323

Appendices Match Replace Mismatch Replace Camera and IP Setup IP Threshold Mirrored Image Window of Interest Hollow Mode Number of Symbols in Field of View Damaged Symbol Focal Distance Increment Focus Position Decrement Focus Position Focal Distance Table IP Mode Illumination Brightness Camera Pixel Sub-Sampling Configuration Database Number of Active Indexes Configuration Database Status

Save Current Settings to Database Load Current Settings from Database Request Selected Index Settings Request All Database Settings Database Mode Output Format Format Extract Format Insert Format Assign Format Status Output Filter Configuration Ordered Output Filter

FIS-6300 ESD Imager User’s Manual

<K735,status,match replacement string> <K736,status,mismatch replacement string> <K512,threshold mode,fixed threshold value> <K514,mirrored image> <K516,row pointer,column pointer,row depth,column width> <K517,hollow mode status> <K518,number of symbols in field of view> <K519,damaged symbol status> <K525,focal distance> <525+> <525-> <K526,number of focal distances,focal distance> <K527,IP Mode,FLM direction> <K536,brightness> <K541,shutter speed,gain> <K542,sub-sampling> <K252,number of active database settings> <K255,index,shutter speed,gain,focal distance,digital zoom,row pointer,column pointer,row depth, column width,threshold mode,fixed threshold value,processing mode,background color,narrow margins,symbology type> <K255+,index> <K255-,index> <K255?,index> <K255?> <K256,switch mode,frame count/time,image process looping,image dimensions> <K740,output index,start location,length> <K741,output index,length,hex string> <K742,symbol number,status> <K743,output format status> <K744,filter number,symbology type,length,wildcard, placeholder,data,unused,database index> <K745,number of filters>

A-9

Page 324

Communication Protocol Commands

Serial Command Format Serial commands are of two types: utility and configuration.

Rules that apply to both utility and configuration commands • A less than < and greater than > character enclose the commands. • Commands and data are “case sensitive.” That is, characters must be entered as upper or lower case, as specified.

Serial Utility Commands These are sent during operations and are not followed by <A> or <Z>.

Serial Configuration “K” Commands These begin with a single “K” character followed by a 3-digit numeric character, data fields, and an initializing command, as follows: <Knumeric parameter,data,data,...etc.><initializing command> An initializing command <A> or <Z> may follow the command. A <Z> initializes the Imager’s memory and saves for power-on; an <A> initializes the Imager’s memory but does not save for power-on. For example, to enable UPC and save the change for power-on, send <K473,1><Z>. To change Baud Rate and reset without saving changes for power-on, send <K100,3><A>.

Serial Configuration Command Conventions • All data fields (except the last) must be followed by a comma (without a space). • NUL cannot be used. The characters <, >, and , can be used, but only if entered as hex pairs (see ASCII Character Entry Modifier on page 3-23). • All fields preceding a modified field must be included. • If there is no change in preceding fields, then commas alone can be entered in these fields. For example, if only the last field in the following command is changing, <K100,4,1,0,0> can be entered as <K100,,,,0>. • All fields following a modified field can be omitted. For example, to change Baud Rate only, send <K100,3>.

Concatenating Configuration Commands Commands can be concatenated (added together) in a single string or data block. For example, <K145,1><K220,1><K450,1><A> enables LRC, sets End of Read Cycle mode to New Trigger, enables Narrow Margins, and resets the data buffers (without saving the changes for power-on).

Serial Command Status Request To ensure that any command was received and accepted, you can send the Show Reader Status command: <?>. The status of a specific serial command can be requested by entering the command followed by a question mark. For example, send <K142?> to request the status of Postamble. A-10

FIS-6300 ESD Imager User’s Manual

Page 325

Appendices

Entering Control Characters in Serial Commands To enter control characters within a serial command, hold down the Ctrl key while typing the desired character. Example: To enter a carriage return and line feed (^M^J), enter <K141,1,CNTL-m CNTL-j>

FIS-6300 ESD Imager User’s Manual

A-11

Page 326

Communications Protocol

Appendix D, Communications Protocol ACK / NAK Data Flow Examples Setup 1 RES REQ STX ETX ACK NAK LRC

0x00 (disabled) 0x00 (disabled) 0x00 (disabled) 0x00 (disabled) 0x06 0x15 disabled

Transfer 1 HOST_TX IMAGER_TX

<K141,0> ‘ACK’

Transfer 2 HOST_TX IMAGER_TX IMAGER_TX HOST_TX

<K141?> ‘ACK’ <K141,0> ‘ACK’

Error Condition Transfer 1 IMAGER_TX HOST_TX IMAGER_TX HOST_TX symbol data ‘NAK’ (host rejects) symbol data (resend data) ‘ACK’ (transaction complete)

Transfer 2 HOST_TX <K141?> IMAGER_TX ‘ACK’ IMAGER_TX <K141,0> timeout reached... timeout reached... timeout reached... Timeout Reached transaction aborted, data is flushed

A-12

FIS-6300 ESD Imager User’s Manual

Page 327

Appendices

Setup 2 RES REQ STX ETX ACK NAK LRC

0x00 (disabled) 0x00 (disabled) 0x00 (disabled) 0x00 (disabled) 0x06 0x15 enabled

Transfer 1 HOST_TX IMAGER_TX

<K141,0>a ‘ACK’

Transfer 2 HOST_TX IMAGER_TX IMAGER_TX HOST_TX

<K141?>B ‘ACK’ <K141,0>a ‘ACK’

Error Condition Transfer 1 HOST_TX IMAGER_TX HOST_TX IMAGER_TX

<k141,0>x (BAD LRC) ‘NAK’ <K141,0>a (GOOD LRC) ‘ACK’

FIS-6300 ESD Imager User’s Manual

A-13

Page 328

Communications Protocol

Setup 3 RES REQ STX ETX ACK NAK LRC

0x00 (disabled) 0x00 (disabled) 0x28 ‘(‘ 0x29 ‘)’ 0x06 0x15 enabled

Transfer 1 HOST_TX IMAGER_TX

(<K141,0>)H ‘ACK’

Transfer 2 HOST_TX IMAGER_TX IMAGER_TX HOST_TX

A-14

(<K141?>)k ‘ACK’ (<K141,^M>)w ‘ACK’

FIS-6300 ESD Imager User’s Manual

Page 329

Appendices

Setup 4 RES REQ STX ETX ACK NAK LRC

0x21 ‘!’ 0x3D ‘=’ 0x28 ‘(‘ 0x29 ‘)’ 0x06 0x15 enabled

Transfer 1 HOST_TX IMAGER_TX

(<K141,0>)H ‘ACK’

Transfer 2 HOST_TX IMAGER_TX HOST_TX IMAGER_TX HOST_TX IMAGER_TX

(<K100?>)n ‘ACK’ ‘!’ (<K100,8,0,0,1>)X ‘ACK’ ‘!’

Error Condition Transfer 1 HOST_TX (<K141,0>)H IMAGER_TX ‘ACK’ HOST_TX (<K100?>)n IMAGER_TX ‘ACK’ HOST_TX ‘!’ IMAGER_TX (<K100,8,0,0,1>)X timeout reached... IMAGER_TX ‘=’ timeout reached... IMAGER_TX ‘=’ timeout reached... IMAGER_TX ‘=’ timeout reached... IMAGER_TX ‘!’

FIS-6300 ESD Imager User’s Manual

A-15

Page 330

Communications Protocol

Polling Mode Data Flow Examples Setup 1 Address RES REQ STX ETX ACK NAK LRC

0x01 (translates to) Poll Req @ ‘0x1C’, Unit Select @ ‘0x1D’ 0x04 0x05 0x02 0x03 0x06 0x15 disabled

Transfer 1 HOST_TX IMAGER_TX HOST_TX IMAGER_TX HOST_TX

‘RES’ ‘0x1D’ ‘REQ’ (Select Unit 1 to receive data) ‘0x1D’ ‘ACK’ (Unit responds with its address) ‘STX’ <T> ‘ETX’ ‘0x1D’ ‘ACK’ (Unit responds with its address) ‘RES’ (Terminate Transfer 2)

Transfer 2 HOST_TX IMAGER_TX HOST_TX IMAGER_TX

‘RES’ ‘0x1C’ ‘REQ’ (Poll Unit 1 for data) ‘0x1C’ ‘STX’ <T/00000> ‘ETX’ ‘ACK’ ‘RES’ (Terminate Transfer 1)

Starting with a ‘RES’ ensures a clean transaction, without “leftovers” from the previous transaction.

Error Condition 1 HOST_TX ‘RES’ ‘0x1C’ ‘REQ’ (Poll Unit 1 for data) IMAGER_TX ‘0x1C’ ‘STX’ <T/00000> ‘ETX’ HOST_TX ‘Nothing’ (Host should ‘ACK’ here) timeout reached... IMAGER_TX ‘REQ’ (Unit requests an ‘ACK’ again) timeout reached... IMAGER_TX ‘REQ’ (Unit requests an ‘ACK’ again) timeout reached... IMAGER_TX ‘REQ’ (Unit requests an ‘ACK’ again) timeout reached... IMAGER_TX ‘RES’ (Terminate Transfer 1, data is flushed)

A-16

FIS-6300 ESD Imager User’s Manual