Page 10

IM 30

Sensing range Sn

22BNS 22BPS 40NPS -ZW1 -ZC1 -ZC1

IM30-

Technical data

40 mm 22 mm

Electrical configuration

DC 3-wire

Supply voltage Vs

DC 10 ... 30 V

Ripple Vpp

≤ 20 %1)

Voltage drop Vd

≤ 2 V2)

Current consumption

≤ 10 mA3)

Continuous current Ia

≤ 200 mA

Time delay before availability tv

≤ 100 ms

Hysteresis H (of sr)

1 ... 15 %

Repeatability R

≤ 5 % (Ub and Ta constant)4)

Temperature drift, of sr

± 10 %

EMC

According to EN 60 947-5-2

Switching output

PNP NPN

Output function

Normally open5)

Installation

Non-flush Quasi-flush6)

Connection types

Plug, M12, 4-pin Cable, PVC, 2 m

Enclosure rating Max. switching frequency

IP 677) 100 Hz 200 Hz

Dimensions Short-circuit protection

M30 x 1.58) 9)

Reverse polarity protection Power-up pulse suppression Shock / vibration stress

30 g, 11 ms / 10 ... 55 Hz, 1 mm

Ambient temperature Ta

-25 °C ... +70 °C

Housing material

Brass, chrome-plated, plastic

Tightening material

60 Nm

1) of Ub 2) at Ia max 3)

4) of sr 5)

without load other output functions available on request

6)

when mounting in conductible materials the sensors have to be installed with a distance A to the surface. A Steel, metal =

6 mm / A Stainless steel = 2 mm

7) according to EN 60 529 8) thread diameter x pitch (mm) 9)

(pulsed)

Order information Type IM30-22BNS-ZW1 IM30-22BPS-ZC1 IM30-40NPS-ZC1

Order no. 6 027 520 6 027 521 6 027 522

SENSICK CATALOGUE

271

Page 11

Inductive sensor, IM 30, DC 3-wire, INOX series Dimensional drawing

3

Inductive sensor

M30x1.5

Sensing range 20 / 40 mm

2

Triple sensing range Installation flush or non-flush

1 8 11 in metal Robust stainless steel V4A, 316L

13

5

8

63.5 one piece housing, with fine thread M30 x 1.5 mm Enclosure rating IP 69K

M30x1.5

3 2

Especially suitable for use in the food and beverage sector

1 8 11 13

5

8

10

63.5

1

Connection

2

Display LED

3

Fastening nuts (2 x); width across 36, stainless steel V4A, 316L

Connection type IM30-20BNS-NC1 IM30-20BPS-NC1 IM30-40NNS-NC1 IM30-40NPS-NC1

See chapter Accessories Connector, M12, 4-pin M12, 4-pin brn

1 blk

4

L+ NO

2 blu

272

SENSICK CATALOGUE

3

M

Page 12

IM 30 20BNS 20BPS 40NNS 40NPS -NC1 -NC1 -NC1 -NC1

IM30-

Technical data

Sensing range Sn

40 mm 20 mm

Electrical configuration

DC 3-wire

Supply voltage Vs

DC 10 ... 30 V

Ripple Vpp

≤ 20 %1)

Voltage drop Vd

≤ 2 V2)

Current consumption

≤ 15 mA3)

Continuous current Ia

≤ 200 mA

Time delay before availability tv

≤ 80 ms

Hysteresis H (of sr)

1 ... 15 %

Repeatability R

≤ 5 % (Ub and Ta constant)4)

Temperature drift, of sr

± 10 %

EMC

According to EN 60 947-5-2

Switching output

PNP NPN

Output function

Normally open5)

Installation

Non-flush6) Flush

Connection types

Plug, M12, 4-pin

Enclosure rating

IP 69K

Max. switching frequency

100 Hz

Dimensions

M30 x 1.57) 8)

Short-circuit protection Reverse polarity protection Power-up pulse suppression Shock / vibration stress

30 g, 11 ms / 10 ... 55 Hz, 1 mm

Ambient temperature Ta

-25 °C ... +70 °C

Housing material

Stainless steel V4A, 316L

Tightening material

150 Nm

1) of Ub 2)

3) without load 4)

at Ia max of sr

5)

other output functions available on request

6) see installation notes 7) thread diameter x pitch (mm) 8)

(pulsed)

Correction factors: Flush installation:

Non-flush installation:

Steel (ST37)

1.0

1.0

Copper

0.9

0.9

Aluminium

1.0

1.0

Brass

1.2

1.2

Stainless steel

0.5 / 0.9

- / 0.5

1 mm / 2 mm thick

Order information Type IM30-20BNS-NC1 IM30-20BPS-NC1 IM30-40NNS-NC1 IM30-40NPS-NC1

Order no. 6 027 583 6 027 582 6 027 585 6 027 584

SENSICK CATALOGUE

273

Page 13

Inductive sensor, IM 30, DC 2-wire

Sensing range 10 / 15 mm

Dimensional drawing 3 2

Short-circuit protection (pulsed) Robust brass housing, nickel-

M30x1.5

Inductive sensor

1 plated with fine thread M30 x 1 mm

50

60 3

Enclosure rating IP 67

M30x1.5

2

1 38

12

60

M30x1.5

3 2

1 16

50

76

M30x1.5

3 2

1 16

38

12

76

See chapter Accessories Connector, M12, 4-pin Mounting systems

1

Connection

2

Display LED

3

Fastening nuts (2 x); width across 36, metal

Connection type IM30-10BDS-ZW1 IM30-15NDS-ZW1

IM30-10BDS-ZC1 IM30-15NDS-ZC1

2 x 0.34 mm²

M12, 4-pin brn

L+ brn

1 blu

M blu

4 2 3

274

SENSICK CATALOGUE

L+ M

Page 14

IM 30 IM30-

Technical data

Sensing range Sn

10BDS 10BDS 15NDS 15NDS -ZW1 -ZC1 -ZW1 -ZC1

15 mm 10 mm

Electrical configuration

DC 2-wire

Supply voltage Vs

DC 10 ... 30 V

Ripple Vpp

≤ 10 %

Voltage drop Vd

≤ 2.8 V1)

Continuous current Ia

≤ 100 mA

Min. load current

≥ 3 mA

Residual current

≤ 0.8 mA

Time delay before availability tv

≤ 50 ms

Hysteresis H (of sr)

2 ... 10 %

Repeatability R

≤ 2 % (Ub and Ta constant)2)

Temperature drift, of sr

± 10 %

EMC

According to EN 60 947-5-2

Output function

Normally open3)

Installation

Non-flush Flush

Connection types

Plug, M12, 4-pin Cable, PVC, 2 m

Enclosure rating

IP 674)

Max. switching frequency

150 Hz

Dimensions

M30 x 1.55) 6)

Short-circuit protection Reverse polarity protection Shock / vibration stress

30 g, 11 ms / 10 ... 55 Hz, 1 mm

Ambient temperature Ta

-25 °C ... +70 °C

Housing material

Brass nickel-plated, plastic

Tightening material

60 Nm

1) at Ia max 2)

3)

of sr normally closed function available on request

4) according to EN 60 529 5)

6)

(pulsed)

thread diameter x pitch (mm)

Order information Type IM30-10BDS-ZW1 IM30-10BDS-ZC1 IM30-15NDS-ZW1 IM30-15NDS-ZC1

Order no. 6 020 326 6 020 328 6 020 330 6 020 332

SENSICK CATALOGUE

275

Page 15

Inductive sensor, IM 30, AC / DC 2-wire

Sensing range 10 / 15 mm

Dimensional drawing 3 2

Broad supply voltage range in AC and DC

M30x1.5

Inductive sensor

1

Robust brass housing, nickelplated, with fine thread

18

59

81

M30 x 1.5 mm Enclosure rating IP 67 3

M30x1.5

2

1 18

44

81

1

Connection

2

Display LED

3

Fastening nuts (2 x); width across 36, metal

Connection type IM30-10BUO-ZU0 IM30-10BUS-ZU0 IM30-15NUO-ZU0 IM30-15NUS-ZU0

See chapter Accessories Mounting systems 2 x 0.5 mm²

276

SENSICK CATALOGUE brn

L+ blu

M

15

Page 16

IM 30

Sensing range Sn

10BUO 10BUS 15NUO 15NUS -ZU0 -ZU0 -ZU0 -ZU0

IM30-

Technical data

15 mm 10 mm

Electrical configuration

AC / DC 2-wire

Supply voltage Vs

AC / DC 20 ... 250 V

Voltage drop Vd AC / DC

≤ 6.5 V / ≤ 6 V

Continuous current Ia

≤ 350 mA (... + 50 °C) ≤ 250 mA (... + 80 °C) ≤ 100 mA DC

Peak current Ik

2.2 A (20 ms/0.5 Hz)

Min. load current

5 mA

Residual current

≤ 2.5 mA (250 V AC) ≤ 1.3 mA (110 V AC) ≤ 0.8 mA (24 V DC)

Time delay before availability tv

≤ 8 ms

Hysteresis H (of sr)

1 ... 15 %

Repeatability R

≤ 10 % (Ub and Ta constant)1)

Temperature drift, of sr

± 10 %

EMC

According to EN 60 947-5-2

Output function

Normally open Normally closed

Installation

Non-flush Flush

Connection types

Cable, PVC/PUR, 2 m

Enclosure rating

IP 672)

VDE potection class Max. switching frequency AC / DC

25 Hz / 30 Hz

Dimensions

M30 x 1.53)

Wire-break protection Short-circuit protection Reverse polarity protection Power-up pulse suppression Shock / vibration stress

30 g, 11 ms / 10 ... 55 Hz, 1 mm

Ambient temperature Ta

-25 °C ... +70 °C

Housing material

Brass nickel-plated, plastic

Tightening material

50 Nm

1)

2)

of sr according to EN 60 529

3)

thread diameter x pitch (mm)

Order information Type IM30-10BUO-ZU0 IM30-10BUS-ZU0 IM30-15NUO-ZU0 IM30-15NUS-ZU0

Order no. 7 902 127 7 902 126 7 902 129 7 902 128

SENSICK CATALOGUE

277

Page 17

Inductive sensor, IM 30, NAMUR

Sensing range 10 / 15 mm

Dimensional drawing 2

NAMUR to EN 60 947-5-6 High switching frequency

M30x1.5

Inductive sensor

1

Robust brass housing, nickelplated, with fine thread

15

41

2

M30 x 1.5 mm Classification PTB 03 ATEX 2037 II 2 G EEx ia IIC T6

M30x1.5

2

1

2

1

Connection

2

Fastening nuts (2 x); width across 36, metal

Connection type IM30-10B-N-ZW0 IM30-15N-N-ZW0

See chapter Accessories Mounting systems Switching units

278

SENSICK CATALOGUE

41

2 x 0.5 mm² brn

L+ blu

M

Page 18

IM 30

Sensing range Sn

N-ZW0 N-ZW0

IM30-10B-

Technical data

15 mm 10 mm

Electrical configuration

NAMUR

Supply voltage Vs

DC 5 ... 25 V

Rated voltage Vn

DC 8.2 V

Power consumption, attenuated

≤ 1 mA

Power consumption, unattenuated

≥ 2.2 mA

Internal capacitance

≤ 240 nF ≤ 230 nF

Internal inductance

≤ 100 µH ≤ 130 µH

Cable resistance

≤ 50 Ohm

Temperature drift, of sr

± 10 %

EMC

According to EN 60 947-5-2

Switching output

Control current dependent on switching1)

Output function

NAMUR

Installation

Non-flush Flush

Connection types

Cable, PVC, 2 m

Enclosure rating

IP 672)

Max. switching frequency

200 Hz 450 Hz

Dimensions

M30 x 1.53)

Short-circuit protected Reverse polarity protected Shock / vibration stress

30 g, 11 ms / 10 ... 55 Hz, 1 mm

Ambient temperature Ta

-25 °C ... +70 °C

Housing material

Brass nickel-plated, plastic

Tightening material

50 Nm

1)

2)

according to EN 60 947-5-6 according to EN 60 529

3)

thread diameter x pitch (mm)

Max. data for connecting Isolating unit EN 2 EX or other approved isolating amplifier: Short circuit current 1Kmax

50 mA

No load voltage UO

16 V

Power loss Pmax

75 mW

Order information Type Order no. IM30-10B-N-ZW0 6 021 128 IM30-15N-N-ZW0 6 021 129

SENSICK CATALOGUE

279