The text of a manual · part 2 of 2
Inductive sensor, IM 30 (SENSICK Catalogue), pages 10 to 18
Pages 10 to 18 of 18
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Sick IM30
Page 10
IM 30
Sensing range Sn
22BNS 22BPS 40NPS -ZW1 -ZC1 -ZC1
IM30-
Technical data
40 mm 22 mm
Electrical configuration
DC 3-wire
Supply voltage Vs
DC 10 ... 30 V
Ripple Vpp
≤ 20 %1)
Voltage drop Vd
≤ 2 V2)
Current consumption
≤ 10 mA3)
Continuous current Ia
≤ 200 mA
Time delay before availability tv
≤ 100 ms
Hysteresis H (of sr)
1 ... 15 %
Repeatability R
≤ 5 % (Ub and Ta constant)4)
Temperature drift, of sr
± 10 %
EMC
According to EN 60 947-5-2
Switching output
PNP NPN
Output function
Normally open5)
Installation
Non-flush Quasi-flush6)
Connection types
Plug, M12, 4-pin Cable, PVC, 2 m
Enclosure rating Max. switching frequency
IP 677) 100 Hz 200 Hz
Dimensions Short-circuit protection
M30 x 1.58) 9)
Reverse polarity protection Power-up pulse suppression Shock / vibration stress
30 g, 11 ms / 10 ... 55 Hz, 1 mm
Ambient temperature Ta
-25 °C ... +70 °C
Housing material
Brass, chrome-plated, plastic
Tightening material
60 Nm
1) of Ub 2) at Ia max 3)
4) of sr 5)
without load other output functions available on request
6)
when mounting in conductible materials the sensors have to be installed with a distance A to the surface. A Steel, metal =
6 mm / A Stainless steel = 2 mm
7) according to EN 60 529 8) thread diameter x pitch (mm) 9)
(pulsed)
Order information Type IM30-22BNS-ZW1 IM30-22BPS-ZC1 IM30-40NPS-ZC1
Order no. 6 027 520 6 027 521 6 027 522
SENSICK CATALOGUE
271
Page 11
Inductive sensor, IM 30, DC 3-wire, INOX series Dimensional drawing
3
Inductive sensor
M30x1.5
Sensing range 20 / 40 mm
2
Triple sensing range Installation flush or non-flush
1 8 11 in metal Robust stainless steel V4A, 316L
13
5
8
63.5 one piece housing, with fine thread M30 x 1.5 mm Enclosure rating IP 69K
M30x1.5
3 2
Especially suitable for use in the food and beverage sector
1 8 11 13
5
8
10
63.5
1
Connection
2
Display LED
3
Fastening nuts (2 x); width across 36, stainless steel V4A, 316L
Connection type IM30-20BNS-NC1 IM30-20BPS-NC1 IM30-40NNS-NC1 IM30-40NPS-NC1
See chapter Accessories Connector, M12, 4-pin M12, 4-pin brn
1 blk
4
L+ NO
2 blu
272
SENSICK CATALOGUE
3
M
Page 12
IM 30 20BNS 20BPS 40NNS 40NPS -NC1 -NC1 -NC1 -NC1
IM30-
Technical data
Sensing range Sn
40 mm 20 mm
Electrical configuration
DC 3-wire
Supply voltage Vs
DC 10 ... 30 V
Ripple Vpp
≤ 20 %1)
Voltage drop Vd
≤ 2 V2)
Current consumption
≤ 15 mA3)
Continuous current Ia
≤ 200 mA
Time delay before availability tv
≤ 80 ms
Hysteresis H (of sr)
1 ... 15 %
Repeatability R
≤ 5 % (Ub and Ta constant)4)
Temperature drift, of sr
± 10 %
EMC
According to EN 60 947-5-2
Switching output
PNP NPN
Output function
Normally open5)
Installation
Non-flush6) Flush
Connection types
Plug, M12, 4-pin
Enclosure rating
IP 69K
Max. switching frequency
100 Hz
Dimensions
M30 x 1.57) 8)
Short-circuit protection Reverse polarity protection Power-up pulse suppression Shock / vibration stress
30 g, 11 ms / 10 ... 55 Hz, 1 mm
Ambient temperature Ta
-25 °C ... +70 °C
Housing material
Stainless steel V4A, 316L
Tightening material
150 Nm
1) of Ub 2)
3) without load 4)
at Ia max of sr
5)
other output functions available on request
6) see installation notes 7) thread diameter x pitch (mm) 8)
(pulsed)
Correction factors: Flush installation:
Non-flush installation:
Steel (ST37)
1.0
1.0
Copper
0.9
0.9
Aluminium
1.0
1.0
Brass
1.2
1.2
Stainless steel
0.5 / 0.9
- / 0.5
1 mm / 2 mm thick
Order information Type IM30-20BNS-NC1 IM30-20BPS-NC1 IM30-40NNS-NC1 IM30-40NPS-NC1
Order no. 6 027 583 6 027 582 6 027 585 6 027 584
SENSICK CATALOGUE
273
Page 13
Inductive sensor, IM 30, DC 2-wire
Sensing range 10 / 15 mm
Dimensional drawing 3 2
Short-circuit protection (pulsed) Robust brass housing, nickel-
M30x1.5
Inductive sensor
1 plated with fine thread M30 x 1 mm
50
60 3
Enclosure rating IP 67
M30x1.5
2
1 38
12
60
M30x1.5
3 2
1 16
50
76
M30x1.5
3 2
1 16
38
12
76
See chapter Accessories Connector, M12, 4-pin Mounting systems
1
Connection
2
Display LED
3
Fastening nuts (2 x); width across 36, metal
Connection type IM30-10BDS-ZW1 IM30-15NDS-ZW1
IM30-10BDS-ZC1 IM30-15NDS-ZC1
2 x 0.34 mm²
M12, 4-pin brn
L+ brn
1 blu
M blu
4 2 3
274
SENSICK CATALOGUE
L+ M
Page 14
IM 30 IM30-
Technical data
Sensing range Sn
10BDS 10BDS 15NDS 15NDS -ZW1 -ZC1 -ZW1 -ZC1
15 mm 10 mm
Electrical configuration
DC 2-wire
Supply voltage Vs
DC 10 ... 30 V
Ripple Vpp
≤ 10 %
Voltage drop Vd
≤ 2.8 V1)
Continuous current Ia
≤ 100 mA
Min. load current
≥ 3 mA
Residual current
≤ 0.8 mA
Time delay before availability tv
≤ 50 ms
Hysteresis H (of sr)
2 ... 10 %
Repeatability R
≤ 2 % (Ub and Ta constant)2)
Temperature drift, of sr
± 10 %
EMC
According to EN 60 947-5-2
Output function
Normally open3)
Installation
Non-flush Flush
Connection types
Plug, M12, 4-pin Cable, PVC, 2 m
Enclosure rating
IP 674)
Max. switching frequency
150 Hz
Dimensions
M30 x 1.55) 6)
Short-circuit protection Reverse polarity protection Shock / vibration stress
30 g, 11 ms / 10 ... 55 Hz, 1 mm
Ambient temperature Ta
-25 °C ... +70 °C
Housing material
Brass nickel-plated, plastic
Tightening material
60 Nm
1) at Ia max 2)
3)
of sr normally closed function available on request
4) according to EN 60 529 5)
6)
(pulsed)
thread diameter x pitch (mm)
Order information Type IM30-10BDS-ZW1 IM30-10BDS-ZC1 IM30-15NDS-ZW1 IM30-15NDS-ZC1
Order no. 6 020 326 6 020 328 6 020 330 6 020 332
SENSICK CATALOGUE
275
Page 15
Inductive sensor, IM 30, AC / DC 2-wire
Sensing range 10 / 15 mm
Dimensional drawing 3 2
Broad supply voltage range in AC and DC
M30x1.5
Inductive sensor
1
Robust brass housing, nickelplated, with fine thread
18
59
81
M30 x 1.5 mm Enclosure rating IP 67 3
M30x1.5
2
1 18
44
81
1
Connection
2
Display LED
3
Fastening nuts (2 x); width across 36, metal
Connection type IM30-10BUO-ZU0 IM30-10BUS-ZU0 IM30-15NUO-ZU0 IM30-15NUS-ZU0
See chapter Accessories Mounting systems 2 x 0.5 mm²
276
SENSICK CATALOGUE brn
L+ blu
M
15
Page 16
IM 30
Sensing range Sn
10BUO 10BUS 15NUO 15NUS -ZU0 -ZU0 -ZU0 -ZU0
IM30-
Technical data
15 mm 10 mm
Electrical configuration
AC / DC 2-wire
Supply voltage Vs
AC / DC 20 ... 250 V
Voltage drop Vd AC / DC
≤ 6.5 V / ≤ 6 V
Continuous current Ia
≤ 350 mA (... + 50 °C) ≤ 250 mA (... + 80 °C) ≤ 100 mA DC
Peak current Ik
2.2 A (20 ms/0.5 Hz)
Min. load current
5 mA
Residual current
≤ 2.5 mA (250 V AC) ≤ 1.3 mA (110 V AC) ≤ 0.8 mA (24 V DC)
Time delay before availability tv
≤ 8 ms
Hysteresis H (of sr)
1 ... 15 %
Repeatability R
≤ 10 % (Ub and Ta constant)1)
Temperature drift, of sr
± 10 %
EMC
According to EN 60 947-5-2
Output function
Normally open Normally closed
Installation
Non-flush Flush
Connection types
Cable, PVC/PUR, 2 m
Enclosure rating
IP 672)
VDE potection class Max. switching frequency AC / DC
25 Hz / 30 Hz
Dimensions
M30 x 1.53)
Wire-break protection Short-circuit protection Reverse polarity protection Power-up pulse suppression Shock / vibration stress
30 g, 11 ms / 10 ... 55 Hz, 1 mm
Ambient temperature Ta
-25 °C ... +70 °C
Housing material
Brass nickel-plated, plastic
Tightening material
50 Nm
1)
2)
of sr according to EN 60 529
3)
thread diameter x pitch (mm)
Order information Type IM30-10BUO-ZU0 IM30-10BUS-ZU0 IM30-15NUO-ZU0 IM30-15NUS-ZU0
Order no. 7 902 127 7 902 126 7 902 129 7 902 128
SENSICK CATALOGUE
277
Page 17
Inductive sensor, IM 30, NAMUR
Sensing range 10 / 15 mm
Dimensional drawing 2
NAMUR to EN 60 947-5-6 High switching frequency
M30x1.5
Inductive sensor
1
Robust brass housing, nickelplated, with fine thread
15
41
2
M30 x 1.5 mm Classification PTB 03 ATEX 2037 II 2 G EEx ia IIC T6
M30x1.5
2
1
2
1
Connection
2
Fastening nuts (2 x); width across 36, metal
Connection type IM30-10B-N-ZW0 IM30-15N-N-ZW0
See chapter Accessories Mounting systems Switching units
278
SENSICK CATALOGUE
41
2 x 0.5 mm² brn
L+ blu
M
Page 18
IM 30
Sensing range Sn
N-ZW0 N-ZW0
IM30-10B-
Technical data
15 mm 10 mm
Electrical configuration
NAMUR
Supply voltage Vs
DC 5 ... 25 V
Rated voltage Vn
DC 8.2 V
Power consumption, attenuated
≤ 1 mA
Power consumption, unattenuated
≥ 2.2 mA
Internal capacitance
≤ 240 nF ≤ 230 nF
Internal inductance
≤ 100 µH ≤ 130 µH
Cable resistance
≤ 50 Ohm
Temperature drift, of sr
± 10 %
EMC
According to EN 60 947-5-2
Switching output
Control current dependent on switching1)
Output function
NAMUR
Installation
Non-flush Flush
Connection types
Cable, PVC, 2 m
Enclosure rating
IP 672)
Max. switching frequency
200 Hz 450 Hz
Dimensions
M30 x 1.53)
Short-circuit protected Reverse polarity protected Shock / vibration stress
30 g, 11 ms / 10 ... 55 Hz, 1 mm
Ambient temperature Ta
-25 °C ... +70 °C
Housing material
Brass nickel-plated, plastic
Tightening material
50 Nm
1)
2)
according to EN 60 947-5-6 according to EN 60 529
3)
thread diameter x pitch (mm)
Max. data for connecting Isolating unit EN 2 EX or other approved isolating amplifier: Short circuit current 1Kmax
50 mA
No load voltage UO
16 V
Power loss Pmax
75 mW
Order information Type Order no. IM30-10B-N-ZW0 6 021 128 IM30-15N-N-ZW0 6 021 129
SENSICK CATALOGUE
279