Operating Instructions CLX490 Compact OMNI Scanner for Bar Codes: 8 Troubleshooting
Pages 89 to 102 of 158, from Operating Instructions CLX490 Compact OMNI Scanner for Bar Codes
The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Sick CLX490
Page 89
Operating Instructions
Troubleshooting
Chapter 8
CLX490
8
Troubleshooting 8.1
Overview of the possible errors and malfunctions
8.1.1
Mounting errors
•
CLX aligned incorrectly with the object carrying the bar code (e. g. blanking)
•
Reading pulse sensor positioned incorrectly
•
With event-controlled focus control: sensors for object height detection positioned incorrectly
8.1.2
Electrical installation errors
•
Interfaces on the CLX connected incorrectly (wiring error in AMV/S60)
•
Host interface on AMV/S60 configured incorrectly
8.1.3
Parameter errors
•
Functions not adjusted to local conditions, e. g. communication parameters on the host interface are set incorrectly
•
Technical limits of the device exceeded, e. g. relationship between the scanning frequency and the reading distance
8.1.4
Malfunctions
•
Start/stop mode: no external reading trigger, more than one object in the reading field
•
Tracking mode: gap between the objects in conveying direction fallen below minimum
•
Laser timeout for incorrectly terminated reading pulse
•
Device error (hardware/software)
8.2
Monitoring error and malfunctions
The CLX is self-monitoring:
8009237/RB47/2007-08-03
•
After the power supply has been switched on, the CLX automatically carries out a selftest, in which it checks important hardware components, before it is initialized (parameter set loaded and device functions initialized). The self-test can be repeated at any time by cancelling Reading mode. See Chapter 6.5.8 Self-test, Page 6-24.
•
If the CLX detects an error during the self-test or at any other time, it outputs the error status ST=3 on the host interface. Prerequisite: the error status is enabled for transmission. This is disabled by default. The CLX displays the diagnosed error as a numeric combination on the auxiliary interface (see Table 8-1, Page 8-2).
•
While it is in operation, the CLX constantly monitors the laser diode and speed of the polygon mirror wheel. In addition, a watchdog circuit responds to error statuses. The CLX carries out referencing at regular cycles. To do so, the laser diode is switched on for max. 10 s.
•
A timer (laser timeout) automatically deactivates the laser diode in Reading mode ("Sensor input" and "Serial interface trigger" mode) if the reading interval has not ended after 10 minutes (default setting). However, it does not end the reading interval. In this case, the CLX outputs the message: "Laser safety timeout" on the auxiliary interface. The reading interval must be terminated by resetting the trigger signal. The laser diode is activated again by the next reading trigger.
© SICK AG · Division Auto Ident · Germany · All rights reserved
8-1
Page 90
Chapter 8
Troubleshooting
Operating Instructions CLX490 Compact OMNI Scanner
8.3
Error messages
The CLX outputs coded error message (number combinations) via the auxiliary interface only. Table 8-1 contains a list of the messages. Displaying messages: To display the messages on the PC, proceed as follows in CLV-Setup: ¾
Click in the toolbar. The Terminal Emulator is launched.
CLV-Setup logs the error messages automatically in a file (sys_msg.log). 8.3.1
CLX without external parameter memory
Message
Meaning
"CLV SYS-Failure: xxx"
The CLX has diagnosed a system error. The "Device Ready" LED does not light up or extinguishes. The system is restarted.
Possible cause 1)
Error key: 011 Data error (RAM) 012 Address error (RAM) 013 RAM to small 051 Speed out of tolerance (mirror wheel) 061 Mirror interval out of tolerance 071 Error: laser shutter 091to095Error: focus control 101to118Error: external parameter memory 130 Amplifier error 131 Background profile invalid 132 Center reading angle RA 50 implausible 133 Brightness overflow 201to215DSP error
Remedy If the error occurs again after the CLX is restarted, contact the SICK Service department. 1) Deactivate the CAN interface to suppress error numbers above 300 (not relevant in stand-alone mode). To do so, upload the parameter set from the CLX using CLV-Setup, choose the CAN INTERFACE tab and deactivate the function in the CAN INTERFACE FUNCTION section. Download the parameter set to the CLX!
Table 8-1: Error messages output on the auxiliary interface
8-2
© SICK AG · Division Auto Ident · Germany · All rights reserved
8009237/RB47/2007-08-03
Page 91
Operating Instructions
Troubleshooting
Chapter 8
CLX490
8.3.2
LED error messages for the external parameter memory
The CLX also reports errors accessing the external parameter memory by means of the "Device Ready" and "Read Result" LEDs. LED behavior
Meaning
Possible cause
1. When the device is – Start option: START WITH switched on, the "Device EXTERNAL PARAMETERS. Ready" LED blinks for ap- The CLX has successfully loaded prox. 10 s and then lights the external parameter set to its RAM. up constantly. 2. When the device is swit- Start option: START WITH ched on, the "Device Rea- EXTERNAL PARAMETERS. The CLX has successfully dy" and "Read Result" loaded the external parameter LEDs blink for approx. 10 s. set with tolerated errors1) to its The "Device Ready" LED RAM then lights up constantly.
Remedy None.
Transfer ok, but different parame- Upload parameter set to CLVter versions in the external mem- Setup and check parameters1). ory and CLX.
3. The "Device Ready" LED • Start option: START WITH • External parameter memory not • OK if the device is to be operated without an external lights up constantly when EXTERNAL PARAMETERS. connected. parameter memory. the device is switched on. The CLX has not loaded external parameter set. Instead, • Check whether the external it has loaded the internal paparameter memory is connectrameter set to its RAM. ed correctly (free wiring: check wire assignment). • Start ok. • Start option: START WITH • None. INTERNAL PARAMETERS. The CLX has successfully loaded the internal parameter set to its RAM. 4. When the device is switched on, the "Device Ready" LED and "Read Result" LEDs blink continuously 2).
• Start option: START WITH EX• External parameter memory not • See 3 Remedy. TERNAL PARAMETERS. connected. The CLX has not loaded the • The parameter set in the exter- • Use the correct external paraexternal parameter set. meter memory or overwrite the nal memory is not from a Instead, it has loaded the CLX490. current one. internal parameter set to its • The external parameter memo- • Repeat the startup procedure. RAM. The CLX, however, If the error is still present after ry is defective. does not output data on the following 4 Remedy, 1st and host interface. 2nd paragraph, contact the SICK Service department. • Start option: START WITH COPY • External parameter • Ensure that the external paINTERN –> EXTERN. memory is not connected. rameter memory is connected The CLX was not able to copy correctly (free wiring: check the internal parameter set to wire assignment). the external memory. • Repeat the startup procedure. • Data transmission error. It has loaded the internal paIf the error is still present after rameter set to its RAM. following 4 Remedy, 2nd and 3rd paragraph, contact the SICK Service department. • Internal parameter set too large • Contact the SICK Service department. to be copied to the external memory (memory is full). • The external parameter memo- • See 4 Remedy, 3rd paragraph. ry is defective.
1) The software of the parameter set in the CLX is older than that of the parameter set in the external memory: print out the parameter set using CLV-Setup. If necessary, display the ID of the unknown/errored command group(s) using the <STX> 8?ERR <ETX> command in the Terminal Emulator window of CLV-Setup. Decode the ID using the reference manual entitled Command Language of the CLV Bar Code Scanners and check the relevant parameter values in the tabs. The software of the parameter set in the CLX is newer than that of the parameter set in the external memory: all of the new parameters in the CLX are set to the default values. If these parameters are necessary, edit the values in the relevant tabs in CLV-Setup and download them to the CLX and the external memory. 2) Flashing stops when the device switches from Reading mode to Parameter mode (e. g. during download from CLV-Setup).
Table 8-2: LED error messages for access to the external parameter memory
8009237/RB47/2007-08-03
© SICK AG · Division Auto Ident · Germany · All rights reserved
8-3
Page 92
Chapter 8
Troubleshooting
Operating Instructions CLX490 Compact OMNI Scanner
LED behavior
Meaning
Possible cause
Remedy
5. When the device is switched on, the "Device Ready" LED and "Read Result" LEDs blink alternately for approx. 10 s. The "Device Ready" LED then lights up constantly.
Start option: START WITH COPY INTERN –> EXTERN. The CLX has successfully copied the internal parameter set to the external-memory3) and set the option for the next start to START WITH EXTERNAL PARAMETERS. It has loaded the internal parameter set to its RAM.
Transfer ok.
Not applicable.
3) The parameter set stored in the external memory is not checked automatically to determine whether it can be read. To check the parameter set, switch off the power supply to the CLX briefly and monitor the "Device Ready" LED as described under 1.
Table 8-2: LED error messages for access to the external parameter memory (contd.)
8-4
© SICK AG · Division Auto Ident · Germany · All rights reserved
8009237/RB47/2007-08-03
Page 93
Operating Instructions
Troubleshooting
Chapter 8
CLX490
8.3.3
Messages for errors accessing the external parameter memory
The CLX outputs further error messages, in addition to the general error messages in Chapter 8.3.1 CLX without external parameter memory, Page 8-2, if problems arise when the external parameter memory is accessed. Message
Meaning
1. "error: access to external parameters not successful internal parameters loaded" (Error type: 104, 105, 106, 111, 112,115)
The external parameter memory is Repeat the startup procedure. If • Start option: START WITH EXTERNAL PARAMETERS. defective. the error is still present, contact The CLX has not loaded the the SICK Service department. external parameter set. Instead, it has loaded the internal parameter set to its RAM. The CLX, however, does not output data on the host interface. • Start option: START WITH COPY INTERN –> EXTERN. The CLX was not able to copy the internal parameter memory. It has loaded the internal parameter set to its RAM.
2. "error: external parameter memory full internal parameters loaded" (Error type: 108)
The internal parameter set is too Start option: START WITH COPY INTERN –> EXTERN. large for the external memory The CLX was not able to copy (memory is full). the internal parameter memory. It has loaded the internal parameter set to its RAM.
Contact the SICK Service department.
Start option: START WITH EXTER-
Use the correct external parameter memory or overwrite the current one.
3. "error: external parameters not valid for device internal parameters loaded" (Error type: 116)
NAL PARAMETERS.
Possible cause
The parameter set in the external memory is not from a CLX490.
The CLX has not loaded the external parameter set. Instead, it has loaded the internal parameter set to its RAM. The CLX, however, does not output data on the host interface.
4. "error: no external parameter memory connected internal parameters loaded" (Error type: 102)
• • Start option: START WITH EXTERNAL PARAMETERS. The CLX has not loaded the external parameter set. Instead, it has loaded the internal parameter set to its RAM. • Start option: START WITH COPY • INTERN –> EXTERN. The CLX was not able to copy the internal parameter set to the external memory. It has loaded the internal parameter set to its RAM.
5. "error: writing parameters CLV->EXT internal parameters loaded" (Error type: 110, 111, 112)
Start option: START WITH COPY INTERN –> EXTERN. The CLX was not able to copy the internal parameter set to the external memory. It has loaded the internal parameter set to its RAM
Remedy
External parameter memory not • OK if the device is to be operaconnected. ted without an external parameter memory. • Check whether the memory is connected correctly (free wiring: check wire assignment). External parameter memory not • See 5 Remedy 2nd paragraph connected.
Data transmission error.
Check whether the external parameter memory is connected correctly (free wiring: check wire assignment). Repeat the startup procedure. If the error is still present, contact the SICK Service department.
Table 8-3: For messages for problems accessing the external parameter memory
8009237/RB47/2007-08-03
© SICK AG · Division Auto Ident · Germany · All rights reserved
8-5
Page 94
Chapter 8
Troubleshooting
Operating Instructions CLX490 Compact OMNI Scanner
Message
Meaning
Possible cause
Remedy
6. "warning: additional unknown parameter(s) external parameters loaded" (Error type: 101, 114)
Start option: START WITH EXTERNAL PARAMETERS. The CLX has successfully loaded the external parameter set with tolerated errors1) to its RAM.
Transfer ok but different parameter versions in the external memory and the CLX.
Upload the parameter set to CLVSetup and check the values1).
1) The software of the parameter set in the CLX is older than that of the parameter set in the external memory: print out the parameter set using CLV-Setup. If necessary, display the ID of the unknown/errored command group(s) using the <STX> 8?ERR <ETX> command in the Terminal Emulator window of CLV-Setup. Decode the ID using the reference manual entitled Command Language of the CLV Bar Code Scanners and check the relevant parameter values in the tabs. The software of the parameter set in the CLX is newer than that of the parameter set in the external memory: all of the new parameters in the CLX are set to the default values. If these parameters are necessary, edit the values in the relevant tabs in CLV-Setup and download them to the CLX and the external memory.
Table 8-3: For messages for problems accessing the external parameter memory (contd.)
8-6
© SICK AG · Division Auto Ident · Germany · All rights reserved
8009237/RB47/2007-08-03
Page 95
Operating Instructions
Troubleshooting
Chapter 8
CLX490
8.4
ST error status in the reading result of a bar code
Value
Meaning
Possible cause
Remedy
0
Good Read.
–
None
2
No bar code of the enabled code type found according to the evaluation criteria.
• No bar code in the CLX‘s reading field during the reading pulse.
• Synchronize the pulse of the CLX with the entry of a bar code into the reading field. • Correct the code configuration parameters. • Check the reading window.
• Code type/length in the CLX not enabled for decoding. • Reading window obstructed/dirty. 3
Device fault.
Device fault.
5
Required number of successful multiple • Conveyor speed of the object is too reads for the bar code not reached. high. • Scanning frequency is too low. • Ladder-type arrangement for bar code relative to the conveyor direction: code height (bar length) too poor. • Print quality too poor.
Call up the self-test. See Chapter 6.5.8 Self-test, Page 6-24. If result ≠ 15000: Contact the SICK Service department. • Check the conveyor speed. • Adjust the scanning frequency. • Check the code height.
• Check the print quality.
6
Master: • The parameterized number of slaves • Check the entered number of slaves. Number of slave reading results does does not match the actual number of not match the parameterized number of slaves available. slaves. • The master timeout is too short. • Check the master timeout setting. • The data connection between the • Check the cables between the slaves slaves and/or the master has been and the master. interrupted.
7
The source of the reading result is the auxiliary input via the auxiliary interface.
The bar code was not detected by the reading function of the CLX, but was entered subsequently with the auxiliary function of the auxiliary interface and sent to the host in a separate data string.
9
The OUTPUT FILTER function is activated for the code comparison. The CLX has detected valid bar codes. However, these do not match the active match code(s).
The scanned object does not have a bar – code that matches the specified match code.
A
The CHECK MAX. NUMBER OF CODES function is active. The number of valid bar codes detected by the CLX in Reading mode exceeds that specified under NUMBER OF CODES: MAXIMUM. It repeatedly outputs the defined error string until the number specified under NUMBER OF CODES: MINIMUM is reached.
One object in a set of objects with a constant number of bar codes, for example, contains more bar codes than defined in the application.
D
The CODE 32 evaluation option is activa- The read 6-digit bar code is not a C32 ted for Code 39. The CLX is attempting bar code. The CLX outputs the defined to interpret 6-digit C39 bar codes as error string instead. C32 bar codes (output as 9-digit decimal values).
–
This message is used to indicate errors on the objects (e. g. check whether objects are homogeneous: mixed with incorrect objects).
–
Table 8-4: Meaning of the ST error status in the reading result
8009237/RB47/2007-08-03
© SICK AG · Division Auto Ident · Germany · All rights reserved
8-7
Page 96
Troubleshooting
Chapter 8
Operating Instructions CLX490 Compact OMNI Scanner
Value
Meaning
Possible cause
Remedy
F
The CHECK MIN. NUMBER OF CODES function is active. The number of valid codes detected by the CLX in Reading mode is less than that specified under NUMBER OF CODES: MINIMUM. Instead of the code contents, it outputs the defined error string in the quantity defined under NUMBER OF CODES: MINIMUM
One object in a set of objects with a constant number of codes, for example, contains fewer codes than defined in the application.
This message is used to indicate errors on the objects (e. g. check whether objects are homogeneous: mix with incorrect objects).
Table 8-4: Meaning of the ST error status in the reading result
8-8
© SICK AG · Division Auto Ident · Germany · All rights reserved
8009237/RB47/2007-08-03
Page 97
Operating Instructions
Troubleshooting
Chapter 8
CLX490
8.5
Troubleshooting
The following are required for troubleshooting purposes using the tables below: •
These Operating Instructions
•
Tools
•
A tape measure (up to 2,000 mm)
•
A digital measuring device (current/voltage mesurement)
•
A PC running CLV-Setup
•
A 3-core RS 232 data cable (null modem cable), pins 2 and 3 crossed, e. g. no. 2014054
8.5.1
General malfunctions: CLX not ready
Malfunction
Possible cause
The "Device Ready" LED is not lit. The "Result 1" output is not outputting a pulse (default setting: Device Ready)
After switching on the power supply: • The CLX has no power
• The CLX has diagnosed a device error during the self-test
Remedy • Check wiring (power connector fitted securely to the AMV/S60 Connection Module). Measure voltage at pin 1 and pin 5. • Switch CLX off and on again. Does the LED light up? If not, contact SICK Service department
During operation: • The CLX is not in "Reading" mode
• Return to Reading mode using the "CLVSetup" program. See Chapter 6.5.1 Reading mode (standard operating mode), Page 6-14 • Terminate reading pulse. Check the rea• The CLX has deactivated the laser diode ding pulse function. Supply new pulse. 10 min. (default setting) after the start of See Chapter 6.4.3 Guide to parameterithe current reading pulse (Trigger mode: zation menu, Page 6-8, Section Adjust sensor input/serial interface) Laser timeout Table 8-5: Troubleshooting: restoring operation (Reading mode)
8009237/RB47/2007-08-03
© SICK AG · Division Auto Ident · Germany · All rights reserved
8-9
Page 98
Chapter 8
Troubleshooting
Operating Instructions CLX490 Compact OMNI Scanner
8.5.2 ¾
Malfunctions in Reading mode: reading trigger errors
Check whether the "Device Ready" LED lights up. If the LED does not light, see Table 8-5, Page 8-9.
CLX in stand-alone configuration Malfunction
Possible cause
Remedy
1. Trigger mode: Sensor input (external sensor).
• Sensor not connected or connected to incorrect switching input.
• Connect sensor to "Sensor" switching input. Check sensor wiring (see Fig. 5-4, Page 5-16). Measure output signal on sensor. • Insert jumper between pin 5 and pin 15.
The CLX cannot be clocked: – the "Sensor" LED does not light up – the red scan line does not appear
• If sensor supplied by CLX: sensor not connected to ground potential. • Incorrect reading pulse source parameterized in the CLX.
• In the "CLV-Setup" program: choose the DEVICE CONFIGURATION tab, READING TRIGGER SOURCE section: is Sensor input selected? (active high: reading pulse starts when power applied) • Photoelectric switch not aligned with the • Align sensor. Check functioning. reflector (photoelectric proximity switch/ inductive sensor not dampened). • Incorrect reading pulse source parameterized on the CLX.
2. Trigger mode: Serial interface The CLX cannot be clocked: – the "Sensor" LED does not light up – the red scan line does not appear
3. CLX does not respond to an external signal that ends the reading pulse (sensor input, serial interface)
• In the "CLV-Setup" program: choose the DEVICE CONFIGURATION tab, READING TRIGGER SOURCE section: is serial interface selected? Click the READING TRIGGER PARAMETERS button, SERIAL INTERFACE section: is trigger type correct? • The CLX is not receiving any command • Check data connection to host. In the "CLV-Setup" program: choose the HOST strings to start the reading interval on the INTERFACE tab. In DATA FORMAT section: are data interface. the correct interface type (hardware) and data format selected? INTERFACE PROTOCOL section: are the correct start and stop characters selected? Use the "CLV-Setup" program to check the host command strings: choose AUXILIARY INTERFACE tab. Choose MONITOR HOST INTERFACE function. See Chapter 6.5.6 Monitor Host Interface, Page 6-22. Download temporarily to the CLX. Incorrect end of reading pulse parameterized on the CLX.
In the "CLV-Setup" program: choose the DEVICE CONFIGURATION tab, click the READING TRIGGER PARAMETERS button. END OF READING INTERVAL section: is Generated by Trigger Source selected?
Table 8-6: Troubleshooting: reading trigger errors in Reading mode
8-10
© SICK AG · Division Auto Ident · Germany · All rights reserved
8009237/RB47/2007-08-03
Page 99
Operating Instructions
Troubleshooting
Chapter 8
CLX490
8.5.3 ¾
Malfunctions in Reading mode: result output errors
Check whether the "Device Ready" LED lights up. If the LED does not light, see Table 8-5, Page 8-9.
CLX in stand-alone configuration Here: number of bar codes to be read = 1 Malfunction
Possible cause
Remedy
1. The "Read Result" LED (default setting: • Read not successful, since there was no • Synchronize read with presence of an Good Read) does not light up at the end bar code in the reading field during the object in reading field. See Chapter 8.5.2 of the reading pulse. reading pulse. Malfunctions in Reading mode: reading trigger errors, Page 8-10. • Scan line positioned incorrectly. • Align CLX. Is bar code at center of scan – The "Result 2" switching output line? Check the reading quality with the (default setting: Good Read) is not "CLV-Setup" software. Choose PERCENTAoutputting a pulse GE EVALUATION. See Chapter 6.5.2 Per– The CLX outputs status ST=2 in the centage evaluation, Page 6-17. reading result on the host interface (if ST is enabled for the separator; this is • Bar code presented at incorrect reading • Check whether reading distance of bar code is in the specified reading range? distance. not selected in the default setting) • The presented bar code’s module width • Present a bar code with an acceptable module width. See Chapter 9 Technical cannot be read by the CLX type being data, Page 9-1. used. • In the "CLV-Setup" program: choose the • With event-controlled focus control: READING CONFIGURATION tab, click the DIwrong focus position in Distance ConfigSTANCE CONFIGURATION button. Does the uration choosen. focus position match the distance of the object? • In the "CLV-Setup" program: choose the • With event-controlled focus control: READING CONFIGURATION tab, in the FOCUS trigger source parameterized incorrectly. CONTROL section. a) Trigger source: "Switching input": Check functional assignment of IN 3 and IN 4 and connection of the sensors. See Fig. 5-5, Page 5-17. b) Trigger source: "Serial interface": Check the data connection to the host. Use the "CLV-Setup" program to check the host command strings: choose AUXILIARY INTERFACE tab. Choose MONITOR HOST INTERFACE function. See Chapter 6.5.6 Monitor Host Interface, Page 6-22. Download temporarily to CLX! c)Trigger source: Timer: Check switchover time. • The reading angles at which the bar code • In the "CLV-Setup" program: choose the CODE CONFIGURATION tab, DECODER appears to the CLX are too large. section: choose Standard decoder. Download temporarily to CLX! Start PERCENTAGE EVALUATION, choose DISTANCE CONFIGURATION. Monitor reading quality (reading quality > 70 %!). If necessary, realign CLX and/or reconfigure distance configuration. If ok, choose SMART DECODER. Download to CLX. Table 8-7: Troubleshooting: result output errors in Reading mode
8009237/RB47/2007-08-03
© SICK AG · Division Auto Ident · Germany · All rights reserved
8-11
Page 100
Chapter 8
Troubleshooting
Operating Instructions CLX490 Compact OMNI Scanner
Malfunction
Possible cause
Remedy
1. The "Read Result" LED default setting: • Evaluation criteria for bar code incorrect. • In CLV-Setup: choose the CODE CONFIGUGood Read) does not light up at the end RATION tab, CODES section. Enable all code of the reading pulse: types (except Pharmacode), set code lengths to FREE. Download temporarily to CLX! Start PERCENTAGE EVALUATION. Code – continued – type and length are displayed in the reading result. Enable recorded code type in the CODES section and disable all other types. Enter the code length under FIXED on the code type tab. Download to CLX! • Check: sufficient blank zones present? • Bar code quality inadequate. Print contrast adequate? Specified print tolerances exceeded? In the "CLVSetup" program: choose READING CONFIURATION tab, SEGMENTATION section. Is START/STOP selected? Perform read with reference code. 2. The CLX is not transferring any reading results to the host
• Reading pulse is not functioning correctly. • Wiring fault in data connection. • Voltage level incorrect. • Host interface in CLX parameterized incorrectly.
• See Chapter 8.5.2 Malfunctions in Reading mode: reading trigger errors, Page 8-10. • Check wiring as shown in Fig. 5-2, Page 5-14. • Measure voltages. • In "CLV-Setup" program: choose HOST INTERFACE tab, DATA FORMAT section. Are the interface type (hardware) and data format correct? Check settings in INTERFACE PROTOCOL section.
3. The CLX transfers the status ST=3 to the The CLX has diagnosed a device error in the Switch the CLX off and on again. Does the host in the reading result (if ST is enabled self-test "Device Ready" LED light up? If not, contact for the separator; this is disabled by dethe SICK Service department. fault) 4. The data content of the bar code output • The data format on the host interface is • In the "CLV-Setup" program: choose the by the CLX is incorrect or incomplete parameterized incorrectly in the CLX HOST INTERFACE tab, DATA FORMAT section. Are the values correct? • The CLX suppresses the last character in • In the "CLV-Setup" program: choose the CODE CONFIGURATION tab. Click the EDIT the bar code button. Choose the tab for the relevant code. Is the TRANSMIT CHECK DIGIT checkbox activated? Change if necessary. Download to CLX! Table 8-7: Troubleshooting: result output errors in Reading mode (contd.)
8-12
© SICK AG · Division Auto Ident · Germany · All rights reserved
8009237/RB47/2007-08-03
Page 101
Operating Instructions
Troubleshooting
Chapter 8
CLX490
8.5.4 ¾
Malfunctions in Reading mode: errors in the result status output
Check whether the "Device Ready" LED lights up. If the LED does not light, see Table 8-5, Page 8-9.
Malfunction
Possible cause
Remedy
The – "Result 1" (default setting: Device Ready) – "Result 2" (default setting: Good Read) – "Result 3" (default setting: No Read) – "Result 4" (default setting: Match 1) switching outputs are not outputting any pulses
• The event associated with the assigned • Not applicable. function for outputting the result status of the read does not occur in the reading operation. • Incorrect switching mode parameterized • In the "CLV-Setup" program: choose the in the CLX. DEVICE CONFIGURATION tab. Click the RESULT OUTPUT PARAMETERS button. Are the outputs set to NO INVERT OUTPUT? Change if necessary. Download to CLX!
Table 8-8: Troubleshooting: errors in the result status output in Reading mode
8009237/RB47/2007-08-03
© SICK AG · Division Auto Ident · Germany · All rights reserved
8-13
Page 102
Chapter 8
Troubleshooting
Operating Instructions CLX490 Compact OMNI Scanner
8.6
SICK Support
If a system error occurs repeatedly ("CLVSYS-Failure: xxx", xxx= 000 ... 299)or if you cannot correct an error using the above measures, the CLX may be defective. The CLX cannot be repaired by the user, meaning that it is not possible to re-establish functions after a failure. However, the CLX can be rapidly replaced by the user. See Chapter 10.11 Replacing a CLX (copying the parameter set), Page 10-33.
8-14
¾
Please contact our local SICK office or subsidary if an error occurs which cannot be eliminated:
•
The telephone numbers and email addresses are listed on the back page of this manual. For postal addresses see also www.sick.com.
¾
Do not send the device to the SICK service without first contacting us.