Operating Instructions: CLV640 Bar Code Scanner, Advanced Line: 6 Electrical installation
Pages 51 to 64 of 132, from Operating Instructions: CLV640 Bar Code Scanner, Advanced Line
The original document is the PDF (7.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Sick CLV640
Page 51
Operating Instructions
Electrical installation
Chapter 6
CLV640 Bar Code Scanner
6
Electrical installation 6.1 Important
Overview of installation sequence
Electrical installation must be performed by qualified staff. The following list provides an overview of a typical installation sequence: •
Connecting the bar code scanner to connection module CDB620 or CDM420
•
Wiring the bar code scanner's data and function interfaces
•
Connecting the connection module to the supply voltage
•
Connecting a PC for start-up and configuration (RS-232 or Ethernet)
The actual installation work which has to be carried out depends on the respective system configuration and the version of the bar code scanner (see chapter 6.2 Electrical installation preparation, page 51). Once electrical installation has been completed, the bar code scanner is started up and configured (see chapter 7 Startup and configuration, page 65).
6.2
Electrical installation preparation
The following general requirements should be observed for the electrical installation: •
Supply voltage 18 ... 30 V DC (functional extra-low voltage in accordance with IEC 3644-41 (VDE 0100 Part 410)) and min. 10 W output power – Using connection module CDB620/CDM420: supply voltage provided by terminals of the connection module - or – Free wiring by customer (without connection module CDB620/CDM420): connection of supply voltage e.g. by cable no. 6034418 (15-pole D-Sub-HD socket to open end)
•
With external reading pulsing – Appropriate reading pulse sensor (start/stop), e. g. photoelectric reflex switch: for registering an object in the reading area – Additional appropriate reading pulse sensor (stop), e.g. photoelectric reflex switch: For registering the end of pulse with extended external reading pulse
Important
•
Appropriate incremental encoder: For separating identical bar codes
•
Host computer with RS-232, RS-422/485 data interface or Ethernet: For further processing the reading data
•
Connection cables: See chapter 11.4.7 Accessories: Cables for Ethernet version, page 115
The possible distance between the bar code scanner and the host computer depends on the physical version of the selected host interface and the set data transfer rate. The following tools and resources are required for electrical installation:
8011975/0000/2008-04-14
•
Tool
•
Digital measuring device (current/voltage measurement)
© SICK AG · Division Auto Ident · Germany · All rights reserved
51
Page 52
Chapter 6
Electrical installation
Operating Instructions CLV640 Bar Code Scanner
6.3
Electrical connections and cables
Fig. 6-1:
Standard version: Electrical connections at the bar code scanner with connection cable
Fig. 6-2:
Ethernet version: Electrical connections at the bar code scanner with connector unit
52
© SICK AG · Division Auto Ident · Germany · All rights reserved
8011975/0000/2008-04-14
Page 53
Operating Instructions
Electrical installation
Chapter 6
CLV640 Bar Code Scanner
6.3.1 Important
Electrical connections at the bar code scanner
Prerequisites for enclosure rating IP 65: •
The black rubber cover of the memory card (optional) has to be closed and lie flush against the device.
•
The connectors attached to the used electrical connections of the Ethernet version have to be firmly screwed.
The same applies to the EMC requirement (ESD) according to CE. Depending on the device version, the following electrical connections are available at the bar code scanner: Device version
Connection (design)
Interfaces
CLV640-0000 CLV640-1000 CLV640-2000 CLV640-3000 CLV640-6000
Cable with connector (D-Sub-HD, 15-pole, plug)
e. g. connection mod• RS-232 ule CDB620 or • RS-422/485 CDM420 • CAN • Two digital inputs • Two digital outputs • Power supply
Tab. 6-1:
8011975/0000/2008-04-14
Electrical connections to the bar code scanner with a fixed cable and connector (standard version)
Device version
Connection (design)
Interfaces
For connection to
CLV640-0120 CLV640-1120 CLV640-2120 CLV640-3120 CLV640-6120
Connector 1 at the connector unit (M-12, 4-pole, socket)
• Ethernet
Network provided by the client
Connector 2 at the connector unit M-12, 12-pole, plug
• RS-232 • RS-422/485 • CAN • One digital input • Power supply e. g. connection module CDB620 or CDM420
Tab. 6-2:
Important
For connection to
Electrical connections to the bar code scanner with connector unit (Ethernet version)
Additional digital inputs and outputs are available at connection module CDB620/CDM420 (available from week 07/2008) in combination with the parameter memory module CMC600.
© SICK AG · Division Auto Ident · Germany · All rights reserved
53
Page 54
Chapter 6
Electrical installation
Operating Instructions CLV640 Bar Code Scanner
6.3.2
Bar code scanner connections to the cable and connector (standard version)
6 1
11
15
Pin
Signal
Function
1
18 ... 30 V DC
Operating voltage
2
RxD (Aux)
Aux interface (receiver)
3
TxD (Aux)
Aux interface (sender)
4
Sensor 2
Digital switching input (adjustable function, e. g. external reading pulse)
5
GND
Ground
6
RD+ (RS-422/485)
Host interface (receiver)
7
RD– (RS-422/485); RxD (RS-232)
Host interface (receiver)
8
TD+ (RS-422/485)
Host interface (sender)
9
TD– (RS-422/485); TxD (RS-232)
Host interface (sender)
10
CAN H
CAN bus (IN/OUT)
11
CAN L
CAN bus (IN/OUT)
12
Result 1
Digital switching output, adjustable function
13
Result 2
Digital switching output, adjustable function
14
Sensor 1
Digital switching input for external reading pulse
15
SensGND
Common ground for the switching inputs
-
–
Shield
Tab. 6-3:
Standard version: Pin assignment of the 15-pole D-Sub-HD cable connector
6.3.3
Bar code scanner's connections with connector unit (Ethernet version)
Pin
Signal
Function
1
TD+
Transmitter+
2
RD+
Receiver+
3
TD-
Transmitter-
4
RD-
Receiver-
-
-
Shield
Tab. 6-4:
54
5 10
Ethernet version: Pin assignment of the 4-pole M12 socket
© SICK AG · Division Auto Ident · Germany · All rights reserved
8011975/0000/2008-04-14
Page 55
Operating Instructions
Electrical installation
Chapter 6
CLV640 Bar Code Scanner
Pin
Signal
Function
1
GND
Ground
2
18 ... 30 V DC
Operating voltage
3
CAN L
CAN bus (IN/OUT)
4
CAN H
CAN bus (IN/OUT)
5
TD+ (RS-422/485)
Host interface (sender)
6
TD– (RS-422/485); TxD (RS-232)
Host interface (sender)
7
TxD (Aux)
Aux interface (sender)
8
RxD (Aux)
Aux interface (receiver)
9
SensGND
Switching input Sensor 1 ground
10
Sensor 1
Digital switching input (external reading pulse)
11
RD+ (RS-422/485)
Host interface (receiver)
12
RD– (RS-422/485); RxD (RS-232)
Host interface (receiver)
-
–
Shield
Tab. 6-5:
Important
8011975/0000/2008-04-14
Ethernet version: Pin assignment on the 12-pole M12 plug
The "Sensor 2", "Result 1" and "Result 2" connections are only available on the bar code scanner with a cable and connector (standard version) and for the Ethernet version via the CDB620/CDM420 connection module in combination with the parameter memory module CMC600.
© SICK AG · Division Auto Ident · Germany · All rights reserved
55
Page 56
Electrical installation
Chapter 6
Operating Instructions CLV640 Bar Code Scanner
6.4 Important
Performing electrical installation
To ensure secure fastening of the connected connectors and adherence to the enclosure rating, the knurled nuts/coupling rings of the M12 connectors have to be tightened or the cable connectors have to be secured. 1.
Connect or release current linkages only under de-energised conditions.
2.
All wire cross sections and their shields on customer side have to be selected and implemented according to valid engineering standards.
Damage to the connector unit at the bar code scanner due to overwinding. The connector unit at the bar code scanner has two end positions. ¾
Never turn the connector unit more than 180° in one direction (comming from one of the end positions).
¾
Always rotate the connector unit in the direction of the laser diode name.
Fig. 6-3:
6.4.1
Direction of rotation of the connector unit
Connecting the power supply for the bar code scanner
The bar code scanner requires a supply voltage of 18 ... 30 V DC (functional extra-low voltage in accordance with IEC 364-4-41 (VDE 0100 (Part 410)) for operation. The functional extra-low voltage can be created using a safety transformer in accordance with IEC 742 (VDE 0551). The maximum current consumption is 6.5 W. The bar code scanner is supplied with 18 ...30 V DC via connection module CDB620 or CDM420. If the power supply module CMP400/CMP490 is used, the input voltage is 100 ... 250 V AC/ 50 ... 60 Hz at the module.
Important
56
The output circuit must be electrically separated from the input circuit. This is usually created by means of a safety transformer in accordance with IEC 742 (VDE 0551).
© SICK AG · Division Auto Ident · Germany · All rights reserved
8011975/0000/2008-04-14
Page 57
Operating Instructions
Electrical installation
Chapter 6
CLV640 Bar Code Scanner
Connecting supply voltage When wiring the bar code scanner using connection module CDB620 or CDM420, the bar code scanner's data and function interfaces are contacted to the connection module together with the power supply. 1.
Ensure that the connection module's supply voltage has been switched off.
2.
Standard version: Connect the bar code scanner's 15-pole cable plug to the connection module's 15-pole socket and screw it tight. - or Ethernet version: Connect the bar code scanner's 12-pole plug via a corresponding cable (e.g. 2042916) to the connection module's 15-pole socket and screw it tight.
6.4.2
Wiring serial data interfaces
The maximum data transfer rate depends on the cable length and the interface type. Interface type
Transfer rate
RS-232 up to 19,200 Bd max. 10 m (32.8 ft)
38,400 ... 57,600 Bd max. 3 m (9.8 ft)
115,200 Bd max. 2 m (6.6 ft)
max. 38,400 Bd max. 1,200 m (3,937 ft)
max. 115,200 Bd max. 500 m (1,640 ft)
RS-422/485
1)
Distance to the host
1) With corresponding line termination according to specification
Tab. 6-6:
8011975/0000/2008-04-14
Recommended maximum cable lengths, depending on the selected data transfer rate
© SICK AG · Division Auto Ident · Germany · All rights reserved
57
Page 58
Chapter 6
Electrical installation
Operating Instructions CLV640 Bar Code Scanner
RS-232 CLV
Host
CLV
Host
RS-422
Fig. 6-4:
Wiring the serial host data interfaces (RS-232 or RS-422) on the 15-pole D-Sub-HD plug
Pin assignment for the serial auxiliary data interface on the 15-pole D-Sub-HD plug: •
RxD = Pin 2
•
TxD = Pin 3
•
GND = Pin 5
Damage to the interface module! Incorrect wiring of the serial data interfaces can damage electronic components in the bar code scanner. ¾
Observe information about wiring the serial data interface.
¾
Check the wiring carefully before switching on the bar code scanner.
1.
Connect the bar code scanner's serial interface to the host in accordance with the EMC regulations using shielded cables. Adhere to the maximum cable lengths.
2.
To prevent interference, do not lay cables parallel to power supply cables and motor lines over a longer distance, e. g. in cable channels.
Important
Terminating the RS-422 data interface Termination can be performed either in connection module CDB620 or CDM420. See operating instructions "Connection module CDB620" or "Connection module CDM420".
58
© SICK AG · Division Auto Ident · Germany · All rights reserved
8011975/0000/2008-04-14
Page 59
Operating Instructions
Electrical installation
Chapter 6
CLV640 Bar Code Scanner
6.4.3
Wiring CAN interface
Important
To wire and configure the bar code scanner's CAN interface for use in the CAN-SENSOR-network, see the operating instructions "Using the CAN Interface“ (no. 8009180, English). 6.4.4
Wiring Ethernet interface
Aux and host interface communication can also be executed in parallel via the Ethernet interface.
$X[ +RVW
&$1
(WKHUQHW
Fig. 6-5:
Important
Function of the Ethernet interface
The Ethernet interface has an auto-MDIX function. This automatically sets the speed and any cross connection that is required. 6.4.5
Wiring switching inputs
If the bar code scanner's reading process should be triggered by an external sensor, the reading pulse sensor is connected to the "Sensor 1" switching input.
Fig. 6-6:
8011975/0000/2008-04-14
Wiring the “Sensor 1“ switching input on the 15-pole D-Sub-HD plug
© SICK AG · Division Auto Ident · Germany · All rights reserved
59
Page 60
Electrical installation
Chapter 6
Operating Instructions CLV640 Bar Code Scanner
The "Sensor 2" switching input has the following functions, among others: Trigger source for •
Incremental encoder input
•
Reading pulse generator for reading pulse end
Fig. 6-7:
Important
Wiring the "Sensor 2" switching input on the 15-pole D-Sub-HD plug
The ratings for "Sensor 1" and "Sensor 2" are identical. Switching behaviour
Power fed to the input opens the internal reading gate of the bar code scanner. (Default setting: active high; debouncing: max. 30 ms (standard))
Features
– Optodecoupled, reverse polarity protected – Can be wired with the PNP output of a sensor
Electrical values
Low: |Vin| ≤ 2 V; |Iin| ≤ 0.3mA High: 6 V ≤ |Vin| ≤ 32 V; 0.7 mA ≤ |Iin| ≤ 5.0 mA
Tab. 6-7:
¾
Ratings for the switching inputs
Connect switching inputs depending on application.
Important
To wire the switching inputs using connection module CDB620 or CDM420, see operating instructions "Connection Module CDB620" (no. 8012119, German/English) or "Connection Module CDM420-0001" (no. 8010004, German/English).
60
© SICK AG · Division Auto Ident · Germany · All rights reserved
8011975/0000/2008-04-14
Page 61
Operating Instructions
Electrical installation
Chapter 6
CLV640 Bar Code Scanner
6.4.6
Wiring switching outputs
The two switching outputs "Result 1" and "Result 2" can be allocated various functions for outputting the result status independently of each other. If the assigned result occurs in the reading process, the corresponding switching output at the end of the reading pulse is live for the selected impulse duration. Important
The "result" LED is not coupled with one of the "result" outputs.
Fig. 6-8:
Important
The ratings of the two switching outputs are identical. Switching behaviour
PNP switching against the distribution voltage VS
Features
Short-circuit proof + temperature-protected, Galvanically not separate from VS
Electrical values
0 V ≤ Vout ≤ VS Guaranteed: (VS −1.5 V) ≤ Vout ≤ VS with Iout ≤ 100 mA
Tab. 6-8:
Important
Possible wiring of the "Result 1" switching output on the 15-pole D-Sub-HD plug
Ratings for the switching outputs
Capacitance loads at the switching output affect the switching behaviour. Threshold is a max. capacitance of 100 nF. Exeeding this value can lead to unwanted pulsing behaviour of the output. 1.
Connect switching outputs depending on application.
2.
Wire the switching outputs with a load resistance to test the switching functions using a high-resistance digital voltmeter. Indication of incorrect voltages/switching statuses is avoided this way.
Important
To wire the switching outputs using connection module CDB620 or CDM420, see the operating instructions "Connection Module CDB620" (no. 8012119, German/English) or "Connection Module CDM420-0001" (no. 8010004, German/English).
8011975/0000/2008-04-14
© SICK AG · Division Auto Ident · Germany · All rights reserved
61
Page 62
Chapter 6
Electrical installation
Operating Instructions CLV640 Bar Code Scanner
6.5
Pin assignment and wire colour assignment of the assembled cables
6.5.1
Pin assignment of the assembled cables
Cable no. 6034414, 6029630, 6034415, 6030928 (Ethernet version)
Pin (4-pole)
Signal
Function
Pin (6-pole)
1
TD+
Transmitter+
1
3
TD-
Transmitter-
2
2
RD+
Receiver+
3
-
-
4
-
-
5
4
RD-
Receiver-
6
-
-
Shield
-
Tab. 6-9:
Pin assignment of the 4-pole M12 plug and the 6-pole RJ45 plug
Cable no. 2042916, 2041834, 2042914, 2042915 (Ethernet version)
Pin (12-pole) Signal
Function
Pin (15-pole)
2
18 ... 30 V DC
Operating voltage
1
8
RxD (Aux)
Aux interface (receiver)
2
7
TxD (Aux)
Aux interface (sender)
3
-
-
-
4
1
GND
Ground
5
11
RD+ (RS-422/485)
Host interface (receiver)
6
12
RD– (RS-422/485); RxD (RS-232)
Host interface (receiver)
7
5
TD+ (RS-422/485)
Host interface (sender)
8
6
TD– (RS-422/485); TxD (RS-232)
Host interface (sender)
9
4
CAN H
CAN bus (IN/OUT)
10
3
CAN L
CAN bus (IN/OUT)
11
-
-
-
12
-
-
-
13
10
Sensor 1
Digital switching input for external reading pulse
14
9
SensGND
Common ground for the switching 15 inputs
-
–
Shield
Tab. 6-10:
62
-
Pin assignment of the 12-pole M12 socket and the 15-pole D-Sub-HD plug
© SICK AG · Division Auto Ident · Germany · All rights reserved
8011975/0000/2008-04-14
Page 63
Operating Instructions
Electrical installation
Chapter 6
CLV640 Bar Code Scanner
6.5.2
Pin assignment and wire colour assignment of the assembled cables with an open end
Cable no. 6034605 (Ethernet version)
Pin (12-pole) Signal
Function
Wire colour
1
GND
Ground brown
2
18 ... 30 V DC
Operating voltage blue
3
CAN L
CAN bus (IN/OUT)
white
4
CAN H
CAN bus (IN/OUT)
green
5
TD+ (RS-422/485)
Host interface (sender)
pink
6
TD– (RS-422/485); TxD (RS-232)
Host interface (sender)
yellow
7
TxD (Aux)
Aux interface (sender)
black
8
RxD (Aux)
Aux interface (receiver)
grey
9
SensGND
Common ground for the switching inputs red
10
Sensor 1
Digital switching input for external reading pulse violet
11
RD+ (RS-422/485)
Host interface (receiver)
grey-pink
12
RD– (RS-422/485); RxD (RS-232)
Host interface (receiver)
red-blue
Tab. 6-11:
Pin assignment of the 12-pole M12 socket and wire colours at the open end
Cable no. 6012166
Pin (5-pole)
Function
Wire colour
1
–
Shield
-
2
+24 V DC
Operating voltage red
3
GND
Ground black
4
CAN H
CAN bus (IN/OUT)
white
5
CAN L
CAN bus (IN/OUT)
blue
Tab. 6-12:
8011975/0000/2008-04-14
Signal
Pin assignment of the 5-pole M12 plug and wire colours at the open end
© SICK AG · Division Auto Ident · Germany · All rights reserved
63
Page 64
Chapter 6
Electrical installation
Operating Instructions CLV640 Bar Code Scanner
Cable no. 6034418 (Standard version)
Pin (15-pole) Signal
Function
Wire colour
1
18 ... 30 V DC
Operating voltage red
2
RxD (Aux)
Aux interface (receiver)
violet
3
TxD (Aux)
Aux interface (sender)
yellow
4
Sensor 2
Digital switching input (adjustable function, e. g. external reading pulse)
red-black
5
GND
Ground black
6
RD+ (RS-422/485)
Host interface (receiver)
light blue
7
RD– (RS-422/485); RxD (RS-232)
Host interface (receiver)
blue
8
TD+ (RS-422/485)
Host interface (sender)
light grey-turquoise
9
TD– (RS-422/485); TxD (RS-232)
Host interface (sender)
green
10
CAN H
CAN bus (IN/OUT)
grey
11
CAN L
CAN bus (IN/OUT)
pink
12
Result 1
Digital switching output, adjustable brown function
13
Result 2
Digital switching output, adjustable orange function
14
Sensor 1
Digital switching input for external reading pulse white
15
SensGND
Common ground for the switching inputs white-black
Tab. 6-13:
64
Pin assignment of the 15-pole D-Sub-HD socket and wire colours at the open cable end
© SICK AG · Division Auto Ident · Germany · All rights reserved
8011975/0000/2008-04-14