Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeEnglishEspañolContact

The text of a manual · part 9 of 43

Instruction Manual RFL 9745 Teleprotection Channel: Section 2. SYSTEM OVERVIEW, pages 55 to 64

Pages 55 to 64 of 394, from Instruction Manual RFL 9745 Teleprotection Channel

The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the RFL RFL-9745

Page 55

Figure 2-16. Example of typical system operation in remote RFL 9745 terminal

SWITCHES 8

LAMPS 9 LED

LCD DISPLAY 2 X 16 CHAR

SUPPRESSION COMPONENTS

DRIVERS

15

BUS INTERFACE

STATUS OPTION BOARD

SOLID STATE OUTPUTS 6 FORM A

BUS I/O 8052

DUART

DRIVER BOARD

DRIVE LOGIC

EPROM 2K X 8

INTERRUPT CONTROLLER

PROGRAM RAM 32K X 16 I/O REGISTERS + ARBITRATION

14

TMS320C25 25 MHZ

RAM 32K X 16

FAST BUS

RAM 32K X 8

BUS CONTROL

FRONT PANEL BRD

Rs232 PORT

13

FLASH 128K X 16

CAPACITOR

REAL TIME CLOCK

SLOW BUS

PROC 68K 12.5 MHZ

WATCH DOG

12

ISOLATION RS232 PORTS

INTERFACE

BUS

COMMS I/F

SOLID STATE OUTPUTS 4 FORM A

OPTICAL INPUTS 4

ALARMS RELAYS 3 FORM C

SOLID STATE OUTPUTS 4 FORM A

OPTICAL INPUTS 4

ALARMS RELAYS 3 FORM C

IRIG-B RECEIVER

8052

16

DSP TMS32OC50

DSP TMS32OC50

SWC I/O BOARD

SUPPRESSION COMPONENTS

SUPPRESSION COMPONENTS

SUPPRESSION COMPONENTS

SWC I/O BOARD

SUPPRESSION COMPONENTS

SUPPRESSION COMPONENTS

SUPPRESSION COMPONENTS

11

DIGITAL SIGNAL PROCESSORS

AUDIO COMMS

TERMINAL BLOCK

CPU BOARD

TERMINAL BLOCK

2 -21

TERMINAL BLOCK

RFL 9745 February 10, 2009

RFL Electronics Inc. (973) 334-3100

AUDIO CIRCUITS

RS232

IRIG-B

AUDIO LINES

10

AUDIO TRANSFORMERS

Page 56

8.

The Communications I/F passes the message through to Transceiver #1 on the Audio Communications Module.

9.

The DSP processor in Transceiver #1 generates a high-frequency tone.

10.

At the remote RFL 9745, the tone is received by Transceiver #1.

11.

Transceiver #1 sends a high-frequency received message to the Communications I/F processor.

12.

The Communications I/F processor send this message down to the CPU.

13.

The 68000 processor receives the message from the Communications I/F processor. The message is then sent to the TMS320C25 on the CPU Module which processes the Logic Table using this new input value. From the TMS320C25 the message is sent back to the 68000 processor. For the purposes of this example, a high-frequency received on Channel 1 causes Output 1A to close.

14.

The output of the Logic Table causes Output 1A to close.

15.

The 68000 sends a message to the Driver Module to close Output 1A.

16.

The Driver Module sends a signal to SWC I/O (A) that closes Output 1.

2.4 SPECIAL FEATURES The RFL 9745 system offers the following special features: 1.

If Transceiver #1 is not used for any other function, it can provide a serial link to the remote RFL 9745. This is done by selecting the transceiver as a modem. The serial connection can serve several purposes. It can be used to do checkback or address-type tests. The round-trip delay can also be measured by performing ping-pong tests. These tests can be done manually or automatically. The values available on the RS-232 port of the remote unit can be read through the modem.

2.

The Real-Time Clock (either set manually or through an IRIG-B link) can be used to time-tag the change-in-state of any of the inputs or outputs. Up to 100 events can be recorded and displayed. The front panel gives a constant readout of system time.

3.

The DSP nature of the audio transceivers allows their operating parameters (such as frequencies, filters, levels, and gains) to be easily re-programmed. The shifts and bandwidths are also programmable to tailor the system to the exact requirements of each application.

RFL 9745 February 10, 2009

2 -22

RFL Electronics Inc. (973) 334-3100

Page 57

4.

The current flowing through the eight solid-state outputs is sensed. This allows the RFL 9745 to detect and report if any output is shorted or failed. These reports can be used to generate alarms if desired.

5.

The front panel display can be used to call up information about the system, including the following: o

The status of all inputs, outputs, and functions.

o

Transmit and receive levels.

o

The state of all alarms.

User text can be added to most of the displays to clarify the application. 6.

Any of the RFL 9745's four channels can be configured to operate as a transfer filter as shown in Figure 2-17. (This is also referred to as the "pass-through" mode.) When operating in thismode, the RFL 9745's programmable parameters can be used to define the filter's bandwidth and amplification factors.

Rx

Amp

Tx

Figure 2-17. Transfer Filter

2.5 ADDRESS TESTING OR CHECKBACK TESTING (AUTOTEST) The RFL 9745 uses Autotest to check its address or checkback functions. Autotest is the initiation of an Address Test or a Checkback Test and depends on how the system is configured. Autotest can be initiated by any one of the following actions: o

By forcing Autotest with alarm logic. This requires a modification to the alarm logic table.

o

The user initiates Autotest using an RS-232 terminal or PC (APRIL). (Section 6 of this manual provides more information on initiating tests using an RS-232 terminal.)

o

The user initiates Autotest from the front panel. (Section 7 of this manual provides more information on initiating tests from the front panel.)

o

The RFL 9745 automatically initiates Autotest, based on its "next test start" setting. See paragraph 6.11.3 for more information.

RFL 9745 February 10, 2009

2 -23

RFL Electronics Inc. (973) 334-3100

Page 58

To perform this test, the local RFL 9745 sends an address request to the remote RFL 9745. Based on the communications channel and the setup of the remote RFL 9745, either no response is made or the remote address is returned. Three possible results can occur: RECEIVED ADDRESS MATCHES PROGRAMMED ADDRESS

This means the local and remote RFL 9745s pass both the address test and the checkback test. If the tests were initiated from the front panel, the display would read: CHECKBACK TEST PASS X4094 R4094 (X denotes the expected address) (R denotes the received address)

RECEIVED ADDRESS AND PROGRAMMED ADDRESS DO NOT MATCH

This means the local and remote RFL 9745s fail the address test, but pass the checkback test. If the tests were initiated from the front panel, the display would read: CHECKBACK TEST FAIL X4094 R3085 (X denotes the expected address) (R denotes the received address)

THE LOCAL RFL 9745 DOES NOT RECEIVE A VALID RESPONSE

This means the local and remote RFL 9745s fail the checkback test and the address test is inconclusive. If the tests were initiated from the front panel, the display would read: CHECKBACK TEST TEST TIMEOUT

The "CHECKBACK FAIL" flag is an input to the RFL 9745's alarm logic. The "ADDRESS FAIL" flag is an input to the RFL 9745's primitive logic and alarm logic. In all cases, when a Checkback Test is initiated, the tests performed count is incremented. The Tests Pass/Tests Failed counts are incremented according to the test result.

RFL 9745 February 10, 2009

2 -24

RFL Electronics Inc. (973) 334-3100

Page 59

2.6 PING PONG TESTING The RFL 9745 uses ping pong testing to measure channel delay between a local 9745 and a remote 9745. In an audio system, channel 1 must be selected as a modem at both sites for ping pong testing to be functional. The channel delay can be set by the user in the read settings menu (Parameter #062, Chan delay alarm) as shown in Figure 6-10. If the measured channel delay exceeds the programmed value, the Channel Delay (Parameter #093) in the alarms display will be set to A (Active) as shown in Figure 6-2. Otherwise, Parameter #093 will be reset to I (Inactive). Parameter #093 (Channel Delay) indicates the result of the last ping pong test run. The ping pong test can be activated by any one of the following actions: •

The user initiates ping pong using RFL 9745 front panel controls. (See paragraph 2.6.1 and Section 7 for more information.)

•

The user initiates ping pong using an RS-232 terminal or PC April. (See paragraph 2.6.2 and Section 6 for more information.)

•

The RFL 9745 automatically performs the ping pong test every 10 minutes.

2.6.1 RUNNING PING PONG TEST FROM FRONT PANEL At the RFL 9745 front panel press the TEST button to view the first entry of the TEST menu. Press the DOWN button to scroll down the TEST menu list until PING PONG is displayed. PING PONG will appear only if channel 1 is configured as a modem in an audio system. Press the ENTER button to run the PING PONG test and view the results. When the ENTER button is pressed, the local 9745 sends a ping pong signal to the remote 9745. Based on the communication channel and the setup of the remote 9745, either no response is made or the ping pong signal is returned. If the local 9745 does not receive a response from the remote 9745 within three seconds, the ping pong test has failed and the words “TEST FAILURE” will be displayed. If the local 9745 receives a response from the remote 9745 which is over 77.5 ms and less than 3 seconds, the words “TEST TIMEOUT” will be displayed. If the local 9745 receives a valid response from the remote 9745 (77.5 ms or less), the 9745 display will indicate the following: “TIME XX.X mSec”, where XX.X can be 00.0 to 77.5 mSec. The resolution of the display is 0.5 mSec. A typical ping pong response is 2.0 to 8.0 ms for a digital system and 8.0 to 12.0 ms for an audio system. The time displayed is the round trip delay divided by two.

RFL 9745 February 10, 2009

2 -25

RFL Electronics Inc. (973) 334-3100

Page 60

2.6.2 RUNNING PING PONG TEST FROM RS-232 Connect your PC to the 9745 RS-232 port, either directly or through an RFL 9660 digital switch. Press the [W] key, then press the [ENTER] key twice. The 9745 will send the following prompt to your PC: !9745> Press the [H] key, and then press the [ENTER] key. The April command list will now be visible on your PC. Press [T] and then [ENTER] to view the test parameters list. Press [1, 4] and then press [ENTER] to run the PING PONG test and view the results.

RFL 9745 February 10, 2009

2 -26

RFL Electronics Inc. (973) 334-3100

Page 61

2.7 LOGIC/ALARM PROGRAMMING LANGUAGE The RFL 9745's logic/alarm programming language is used to transform a diagram of the logic desired by the user into a form the RFL 9745 can use. The basic primitives used in logic design are used by this language. Once the primitives and syntax are understood, any logic diagram can be easily converted. As in most logic design, the terms "true," "positive," "high," and "1" all refer to the same state. Also, the terms "false," "negative," "low," and "0" all refer to the same state. In the following paragraphs, the terms "true" and "false" will be used to describe these logic states.

2.7.1 AND GATE An AND gate has two inputs and one output, as shown in Figure 2-18. If both inputs are true, the output is true. If either input is false, the output is false.

Table 2-4. Truth table for AND gate

Input 1 False False True True

INPUT 1 OUTPUT INPUT 2

Input 2 False True False True

Output False False False True

Figure 2-18. AND gate

2.7.2 OR GATE An OR gate has two inputs and one output, as shown in Figure 2-19. If both inputs are false, the output is false. If either input is true, the output is true. Table 2-5. Truth table for OR gate

Input 1 False False True True

INPUT 1 OUTPUT INPUT 2

Input 2 False True False True

Output False True True True

Figure 2-19. OR gate

RFL 9745 February 10, 2009

2 -27

RFL Electronics Inc. (973) 334-3100

Page 62

2.7.3 NOT GATE A NOT gate (or inverter) has one input and one output, as shown in Figure 2-20. The output is always the opposite of the input. Table 2-6. Truth table for NOT gate

Input False True

OUTPUT

INPUT

Output True False

Figure 2-20. NOT gate

NOTE The logic/alarm programming language assumes that all gates have two inputs. Since the NOT gate has only one input, the user must set the non-existing second input to “#0”, as shown in the following example: NOT, input 1 of the gate, #0 Also refer to line 1 of Figure 2-25.

2.7.4 XOR GATE An XOR (or Exclusive-OR) gate has two inputs and one output, as shown in Figure 2-21. If one input is true and the other is false, the output is true. If both inputs are the same state (either true or false), the output is false.

Table 2-7. Truth table for XOR gate

Input 1 False False True True

INPUT 1 OUTPUT INPUT 2

Input 2 False True False True

Output False True True False

Figure 2-21. XOR gate

2.7.5 USING THE “NOP” COMMAND If a line of code in the logic table is not going to be used, use the “NOP” command to bypass that line of code.

2.7.6 USING THE “END” COMMAND After the last line of code, the “END” command is used to indicate the end of the logic table. When the logic table is viewed by using the "V” command, “END” is not displayed. RFL 9745 February 10, 2009

2 -28

RFL Electronics Inc. (973) 334-3100

Page 63

2.7.7 TIMER A timer has one input and one output, as shown in Figure 2-22. The output tracks the input after a given time delay. Each timer has two settings: "attack time" and "decay time." If the input goes true, the output will go true after a time delay equal to the attack time, as long as the input is still true; if the input is not true at the end of the attack time, the output will not change. If the input goes from true to false after the attack time has been satisfied, the output will go false after a time delay equal to the decay time. If the input remains false less than the decay time, the output will not go false.

TIMER # INPUT

GATE # OUT 20/30 ATTACK / DECAY VALUES (in ms)

IN

OUTPUT a. Symbol ATTACK TIME

20

20

TRUE

INPUT

FALSE 30

30

DECAY TIME TRUE

OUTPUT

FALSE b. Timing diagram Figure 2-22. Timer

RFL 9745 February 10, 2009

2 -29

RFL Electronics Inc. (973) 334-3100

Page 64

2.7.8 LATCH A latch has two inputs and one output, as shown in Figure 2-23. One input is called "SET," and the other is "RESET”. The SET input is active true and the RESET input is active false. The latch starts out in a false state. If the RESET input goes false, the output goes false. If the SET input goes true, the output goes true and stays true unless the RESET is false.

INPUT 1

SET GATE #

INPUT 2

Q

OUTPUT

RESET a. Symbol TRUE

INPUT 1 (SET)

FALSE

TRUE

INPUT 2 (RESET)

FALSE

TRUE

OUTPUT (Q)

FALSE b. Timing Diagram

Set X H ↑ ↓ X H L

Reset L H H H ↓ ↑ ↑

Output L No change H No change L L L

H = HIGH or TRUE L = LOW or FALSE ↑ = FALSE TO TRUE TRANSITION ↓ = TRUE TO FALSE TRANSITION X = DON’T CARE

Figure 2-23. Latch

RFL 9745 February 10, 2009

2 -30

RFL Electronics Inc. (973) 334-3100