Page 65
2.7.9 LOGIC TABLE SYNTAX The syntax used in the RFL 9745's logic table is very simple. Every connection point in the logic diagram is called a "node." Each node has one gate that causes it to be either true or false; the node is said to be "driven" by that gate. The RFL 9745's hardware inputs drive gates, which in turn drive other nodes. The final nodes in a logic expression may be used to drive the RFL 9745's hardware outputs. (A typical logic diagram appears in Figure 2-24. Figure 2-25 shows how this logic diagram is converted into a logic table.) Each node is described by a single line in the RFL 9745's logic table. When complete, a logic table will have the same number of lines as there are nodes in the diagram. Each line contains four or five items: the node number, the gate type, the first input to the gate, the second input to the gate, and any output attached to this node. If the output is an input to another gate, then you don’t list the output. INPUT 3A
OUTPUT 3A 2
INPUT 3B 1
TX_FUNC1
3 4
IN
OUTPUT 1A
TIMER #1 5
Figure 2-24. Typical logic diagram
# 001 002 003 004 005
Gate: NOT AND OR XOR TIMER
Input 1: INPUT3B INPUT3A NODE1 NODE3 NODE4
Input 2: #0 NODE1 NODE2 NODE1 TIMER1
Output: OUTPUT3A TX_FUNC1 OUTPUT1A
Figure 2-25. Logic table for logic diagram in Figure 2-24
RFL 9745 February 10, 2009
2 -31
RFL Electronics Inc. (973) 334-3100
Page 66
2.8 9745 FILE DESCRIPTIONS The RFL 9745 uses batch files, logic files, schematic files and system files. Each of these files is described below.
2.8.1 BATCH FILES RFL 9745 files with a .BAT extension are referred to as batch files. Batch files contain parameter tables, alarm name tables and timer value tables. There are three generic batch files supplied on the PC_APRIL diskette as follows: 6750.BAT 9745.BAT Digital.BAT 6750.BAT provides the parameters necessary to program the RFL 9745 so that it can operate with an RFL 6750 audio tone transfer trip chassis. 9745.BAT contains the default program parameters for the audio tone version of the RFL 9745. Digital.BAT contains the default program parameters for both the digital and optical versions of the RFL 9745. If a users RFL 9745 is programmed with customer specific application software, a custom batch file with a file name similar to S00254PA.BAT, will be supplied. This batch file will contain the custom parameter tables for the system, and is pre-loaded into the RFL 9745 at the factory. A copy of this file will also be supplied on the CUSTOM LOGIC diskette. This file can be uploaded from a PC to the RFL 9745 as working parameter software.
2.8.2 LOGIC FILES RFL 9745 files with an .MHX extension are referred to as logic files. Logic files contain primitive logic and alarm logic tables for the RFL 9745. There are four generic logic files supplied on the PC_APRIL diskette as follows: 6750.MHX 9745.MHX Digital.MHX OPTIC.MHX If a users RFL 9745 is programmed with customer specific application software, a custom logic file with a file name similar to S00254PA.MHX, will be supplied. This logic file will contain the custom tables for the system, and is pre-loaded into the RFL 9745 at the factory. A copy of this file will also be supplied on the CUSTOM LOGIC diskette. A customer specific logic drawing will also be supplied, which will be located in the accessory section of the instruction manual. This file can be uploaded from a PC to the RFL 9745 as working logic software.
RFL 9745 February 10, 2009
2 -32
RFL Electronics Inc. (973) 334-3100
Page 67
2.8.3 SCHEMATIC FILES RFL 9745 files with an .DXF extension are referred to as schematic files. There are two files with this extension provided on the CUSTOM LOGIC diskette. These are schematics generated from ORCAD. ORCAD is a computer aided development tool which is run on a workstation and is used to edit the logic graphically as a schematic representation of the logic. Logic files with the .MHX extension are then derived from these schematics. The schematic files do not run with PC_APRIL and do not run on the RFL 9745 itself. There are usually two schematic files supplied on the PC_APRIL diskette which have file names similar to the following: S00254AA.DXF S00254PA.DXF
(Alarm logic) (Primitive logic)
These schematic files correspond to the custom logic files discussed in paragraph 2.7.2.
2.8.4 SYSTEM FILE The system file is located on the diskette labeled “RFL 9745 SYSTEM DOWNLOAD SOFTWARE SW9745SY026”. This file contains the main operating program for the RFL 9745. A typical system file name on this diskette is S9745RXX.MHX, where XX is the latest revision. In the event the basic operating program in the RFL 9745 is revised or is erroneously lost, the system can be reprogrammed using this diskette by following the instructions provided in Section 9 of this instruction manual.
RFL 9745 February 10, 2009
2 -33
RFL Electronics Inc. (973) 334-3100
Page 68
2.9 INPUTS AND OUTPUTS During normal system operation, the RFL 9745 uses many signal inputs to make its logic decisions. Based on these decisions, the RFL 9745 produces many output signals. All of the Primitive and Alarm Processor input and output signals used for the Audio and Digital Systems are shown in Section 2.9.1 and 2.9.2. Typical Primitive and Alarm logic diagrams appear in Figures 2-26 through 2-30. For diagrams that are specific to your system, refer to Section 12 of this manual or the "as supplied" drawings furnished with the equipment. Not all of the input and output signals listed in Section 2.9.1 and 2.9.2 are used in the logic diagrams shown in Figures 2-26 through 2-30. However, they can be used if the logic diagrams are edited by the user to satisfy a special requirement. The logic diagrams shown in Figures 2-26 through 2-30 do not physically exist, but are schematic representations of how the logic is configured in the RFL 9745 software, which can be edited by the user. A list of these logic diagrams is shown below. Figure
Logic Diagram
2-26
9745 Audio default primitive logic diagram
2-27
9745 Audio default alarm logic diagram
2-28
6750 Audio default primitive logic diagram
2-29
9745 Digital default primitive logic diagram
2-30
9745 Digital default alarm logic diagram
RFL 9745 February 10, 2009
2 -34
RFL Electronics Inc. (973) 334-3100
Page 69
2.9.1 PRIMITIVE AND ALARM LOGIC INPUTS (For Audio and Digital Systems) The following inputs are accepted by the Primitive and Alarm logic in the RFL 9745 units equipped for Audio or Digital communications. PRIMITIVE & ALARM INPUTS
ALARM INPUTS ONLY
Analog 9745
Digital 9745
#0
X
X
This input is used as a standard false input to any gate.
#1
X
X
This input is used as a standard true input to any gate.
X
An address test was performed with the remote unit. The remote unit did respond to the test but the wrong return address was received. This indicates that communications with another 9745 is functioning, but the wrong 9745 is connected to the remote end.
X
In Digital System, active when the BER (bit error rate) exceeds the value set by the user in the programming menu. In Audio System, always inactive.
ADR_FAIL
X
ALRM_BER AMIH_CH1
X
AMIH_CH2
X
AMIH_CH3
X
AMIH_CH4
X
AMIL_CH1
X
AMIL_CH2
X
AMIL_CH3
X
AMIL_CH4
X
AM2H_CH1
X
AM2H_CH2
X
AM2H_CH3
X
AM2H_CH4
X
AM2L_CH1
X
AM2L_CH2
X
AM2L_CH3
X
AM2L_CH4
X
RFL 9745 February 10, 2009
BATTERY
X
BOOST1
X
BOOST2
X
BOOST3
X
BOOST4
X
BUS_ERR
X
Definition
Each FSK channel has two bandpass filters associated with it. One,AM1, has a pass band from the low edge of the band passed by the channel filter to the center frequency. AM2 goes from the center frequency to the upper band edge. AM1H becomes active when the signal level in that filter has exceeded a preset upper limit. This limit is fixed at 11 dB more than nominal. Each FSK channel has two bandpass filters associated with it. One, AM1, has a pass band from the low edge of the band passed by the channel filter to the center frequency. AM2 goes from the center frequency to the upper band edge. AM1L becomes active when the signal level in that filter has not exceeded a preset lower limit. This limit is fixed at 10 dB less than nominal. Each FSK channel has two bandpass filters associated with it. One, AM1, has a pass band from the low edge of the band passed by the channel filter to the center frequency. AM2 goes from the center frequency to the upper band edge. AM2H becomes active when the signal level in that filter has exceeded a preset upper limit. This limit is fixed at 11 dB more than nominal. Each FSK channel has two bandpass filters associated with it. One, AM1, has a pass band from the low edge of the band passed by the channel filter to the center frequency. AM2 goes from the center frequency to the upper band edge. AM2L becomes active when the signal level in that filter has not exceeded a preset lower limit. This limit is fixed at 10 dB less than nominal.
X
Not used on units with capacitor-backed RAM.
This alarms input is the result of the appropriate channels boost going active.
X
A bus error has occurred involving one of the RFL 9745's buses.
2 -35
RFL Electronics Inc. (973) 334-3100
Page 70
PRIMITIVE & ALARM INPUTS
ALARM INPUTS ONLY
Analog 9745
Digital 9745
CH_DLY
X
X
The measured channel delay is longer than the program value (See Figure 6-10).
CHKBK
X
X
Checkback test failure
CLK_ERR
X
This input becomes active when the variation in the timing for an entire message exceeds the preset limit of 30 microseconds. This calculates out to 2 unit intervals or 12.8 percent.
CONF_ERR
X
This input becomes active when a digital comms module is installed but no digital SIO is installed.
X
An error has occurred involving the CPU.
CPUFAIL
X
FDH_CH1
X
FDH_CH2
X
FDH_CH3
X
FDH_CH4
X
FDL_CH1
X
FDL_CH2
X
FDL_CH3
X
FDL_CH4
X
FM_CH1
X
FM_CH2
X
FM_CH3
X
FM_CH4
X
FRM_ERR
Definition
The frequency discriminator for channel 1, 2, 3 or 4 has determined that a tone which is higher than the center frequency and lower than the highest frequency allowed by the bandpass filter is being received. There is a slight dead zone around the center frequency that is proportional to the distance between the programmed high and low frequencies The frequency discriminator for channel 1, 2, 3 or 4 has determined that a tone which is lower than the center frequency and higher than the lowest frequency allowed by the bandpass filter is being received. There is a slight dead zone around the center frequency that is proportional to the distance between the programmed high and low frequencies.
This input goes active when the rate of change of the input frequency exceeds the programmable limit. The limit is set in percent in April. The setting refers to how much the discriminator output is allowed to change in 125 microseconds.
X FTT1A
X
X
FTT1B
X
X
FTT2A
X
X
FTT2B
X
X
FTT3A
X
X
FTT3B
X
X
FTT4A
X
X
FTT4B
X
X
This error is active whenever the digital comms board on the receiving end is unable to detect the framing pattern embedded in the digital data stream.
Fail To Trip - According to the system conditions, The Output should be in its trip state, but less than 150 ma is being sensed through its contacts.
Continued….. RFL 9745 February 10, 2009
2 -36
RFL Electronics Inc. (973) 334-3100
Page 71
PRIMITIVE & ALARM INPUTS
ALARM INPUTS ONLY
Analog 9745
Digital 9745
INPUT1A
X
X
INPUT1B
X
X
INPUT2A
X
X
INPUT2B
X
X
INPUT3A
X
X
INPUT3B
X
X
INPUT4A
X
X
INPUT4B
X
X
X
X
The output of the RFL 9745's left (main) power supply module is low.
MAJR_ERR
X
This input goes active when the digital receiver has detected enough messages with CRC errors to declare that the major error setting in the programming has been exceeded.
MINR_ERR
X
This input goes active when the digital receiver has detected enough messages with CRC errors to declare that the minor error setting in the programming has been exceeded.
LPWR
OSPARE0
X
X
OSPARE1
X
X
OSPARE2
X
X
OSPARE23
X
X
OSPARE3
X
X
OSPARE31
X
X
OSPARE4
X
X
OSPARE5
X
X
OSPARE6
X
X
OSPARE7
X
X
Definition
The hardware input has detected sufficient voltage to declare input 1A, 2A, 3A, 4A, 1B, 2B, 3B, or 4B active. (See Section 6 for more information on input labels).
This primitive input is a logic gate path to connect primitive logic to alarm logic.
Continued…..
RFL 9745 February 10, 2009
2 -37
RFL Electronics Inc. (973) 334-3100
Page 72
PRIMITIVE & ALARM INPUTS
ALARM INPUTS ONLY
Analog 9745
Digital 9745
OUTPUT1A
X
X
OUTPUT2A
X
X
OUTPUT3A
X
X
OUTPUT4A
X
X
OUTPUT1B
X
X
OUTPUT2B
X
X
OUTPUT3B
X
X
OUTPUT4B
X
X
RPWR
X
X
The output of the RFL 9745's right (redundant) power supply module is low.
RS232
X
X
The RFL 9745's RS-232 port is active.
RSE_CH1
X
RSE_CH2
X
RSE_CH3
X
RSE_CH4
X X
RSE_FUNC2
X
RSE_FUNC3
X
RSE_FUNC4
X
RSE_FUNC5
X
RSE_FUNC6
X
RSE_FUNC7
X X
RTS_CH2
X
RTS_CH3
X
RTS_CH4
X
These alarm inputs are driven from the primitive outputs to be used for an alarm condition.
These alarm inputs are driven from the primitive outputs to be used for an alarm condition.
These alarm inputs are driven from the primitive outputs to be used for an alarm condition.
RSE_FUNC1
RTS_CH1
Definition
In the digital system, these seven primitive outputs can be used as an alarm input to trigger an alarm condition. Seven received bits are available. Each one refers to the receipt of a valid transmitted function bit. RX_FUNC1, 2, 3, 4,5, 6, or 7 means that the receiver is detecting that the given bit is received in a high state.
This primitive output enables the appropriate channel transmitter.
Continued…..
RFL 9745 February 10, 2009
2 -38
RFL Electronics Inc. (973) 334-3100
Page 73
PRIMITIVE & ALARM INPUTS
ALARM INPUTS ONLY
Analog 9745
Digital 9745
RX_FUNC1
X
RX_FUNC2
X
RX_FUNC3
X
RX_FUNC4
X
RX_FUNC5
X
RX_FUNC6
X
RX_FUNC7
X
Definition
In the digital system, seven received bits are available. Each one refers to the receipt of a valid transmitted function bit. RX_FUNC1, 2, 3, 4,5, 6, or 7 means that the receiver is detecting that the given bit is received in a high state.
RXALARM1
X
RXALARM2
X
In the Audio System, active when the received signal level for channels 1, 2, 3 or 4 is lower than the programmed Rx Alarm Level in the alarms display.
RXALARM3
X
In Digital System, always inactive.
RXALARM4
X
S/N_CH1
X
S/N_CH2
X
S/N_CH3
X
S/N_CH4
X
This input goes active when the absolute value of the difference between the energy in the AM1 filter and the AM2 filter is less than the programmable limit (AM noise).
SHORT1A
X
X
SHORT1B
X
X
SHORT2A
X
X
SHORT2B
X
X
SHORT3A
X
X
SHORT3B
X
X
SHORT4A
X
X
SHORT4B
X
X
X
X
The Auto Test Active parameter is active for the duration of an auto test.
X
X
Set after address test performed, cleared on boot-up or outage.
X
This input goes active when the fiber optic transmitter has failed.
TEST_ACT TEST_RUN TX_FAIL
Output Shorted - According to the system conditions, These Outputs should be open. However, a current greater than 150 mA is being sensed through their contacts.
Continued…..
RFL 9745 February 10, 2009
2 -39
RFL Electronics Inc. (973) 334-3100
Page 74
PRIMITIVE & ALARM INPUTS
ALARM INPUTS ONLY
Analog 9745
Digital 9745
TX_FUNC1
X
X
TX_FUNC2
X
X
TX_FUNC3
X
X
TX_FUNC4
X
X
TX_FUNC5
X
TX_FUNC6
X
TX_FUNC7
X
Definition
These primitive outputs can be used as alarm inputs to drive an alarm condition. This bit goes active when the appropriate channel is transmitting.
The following LOGIC INPUTS are used in the PRIMITIVE LOGIC only. PRIMITIVE & ALARM INPUTS
ALARM INPUTS ONLY
Analog 9745
Digital 9745
ASPARE1
X
X
ASPARE2
X
X
ASPARE3
X
X
ASPARE4
X
X
RFL 9745 February 10, 2009
Definition
This primitive input is a logic gate path to connect alarm logic to primitive logic.
2 -40
RFL Electronics Inc. (973) 334-3100