The text of a manual · part 11 of 43
Instruction Manual RFL 9745 Teleprotection Channel: Section 2. SYSTEM OVERVIEW, pages 75 to 83
Pages 75 to 83 of 394, from Instruction Manual RFL 9745 Teleprotection Channel
The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the RFL RFL-9745
Page 75
2.9.2 PRIMITIVE AND ALARM LOGIC OUTPUTS (For Audio and Digital Systems) The following outputs are produced by the Primitive and Alarm logic in RFL 9745 units equipped for Audio or Digital communications. PRIMITIVE OUTPUTS ONLY
ALARM OUTPUTS ONLY
Analog 9745
Digital 9745
A_OUTPUT1
X
X
A_OUTPUT2
X
X
A_OUTPUT3
X
X
A_OUTPUT4
X
X
A_OUTPUT5
X
X
A_OUTPUT6
X
X
A_RELAY1A
X
X
A_RELAY1B
X
X
A_RELAY2A
X
X
A_RELAY2B
X
X
A_RELAY3A
X
X
A_RELAY3B
X
X
ASPARE1
X
X
ASPARE2
X
X
ASPARE3
X
X
ASPARE4
X
X
AUTO_TEST
X
X
Definition
The appropriate Optional Annunciator (Optional solid state output)
BOOST1
X
BOOST2
X
BOOST3
X
BOOST4
X
The appropriate Annunciator Relay (Form C electro-mechanical relay. Inactive state is energized)
This alarm output is a logic gate path to connect alarm logic to primitive logic.
Run auto test (Causes an automatic test to be run if the system is configured to run tests). Typical uses are after an outage goes inactive or if AUTO_TEST is linked to an external input.
This primitive output causes the appropriate channel to output a higher level from its transmitter. The added level in dB is programmed in APRIL.
Continued…..
RFL 9745 February 10, 2009
2 -41
RFL Electronics Inc. (973) 334-3100
Page 76
PRIMITIVE OUTPUTS ONLY
ALARM OUTPUTS ONLY
Analog 9745
Digital 9745
OSPARE0
X
X
OSPARE1
X
X
OSPARE2
X
X
OSPARE23
X
X
OSPARE3
X
X
OSPARE31
X
X
OSPARE4
X
X
OSPARE5
X
X
OSPARE6
X
X
OSPARE7
X
X
X
X
OUTPUT1A
X
X
OUTPUT1B
X
X
OUTPUT2A
X
X
OUTPUT2B
X
X
OUTPUT3A
X
X
OUTPUT3B
X
X
OUTPUT4A
X
X
OUTPUT4B
X
X
RELAY-2A
X
X
RELAY-2B
X
X
RELAY-3A
X
X
RELAY-3B
X
X
RELAY-4A
X
X
RELAY-4B
X
X
OUTAGE
Definition
This primitive output is a logic gate path to connect primitive logic to alarm logic.
Increment outage timer (If this output is active, the cumulative outage timer runs).
These outputs drive a solid state device in the upper and lower I/O modules. When the TRUE output of a gate, timer or latch in the primitive logic is programmed to feed one of the outputs, the contacts are closed, if the output is TRUE.
These outputs drive the contact closure FORM A relay outputs in the upper and lower I/O module. When the TRUE output of a gate, timer or latch in the primitive logic is programmed to feed one of the outputs, the contacts are closed, if the output is TRUE.
Continued…..
RFL 9745 February 10, 2009
2 -42
RFL Electronics Inc. (973) 334-3100
Page 77
PRIMITIVE OUTPUTS ONLY
ALARM OUTPUTS ONLY
Analog 9745
RSE_CH1
X
RSE_CH2
X
RSE_CH3
X
RSE_CH4
X
Digital 9745
This primitive output enables the receiver for the appropriate channel.
RSE_FUN1
X
RSE_FUN2
X
RSE_FUN3
X
RSE_FUN4
X
RSE_FUN5
X
RSE_FUN6
X
RSE_FUN7
X
RTS_CH1
X
RTS_CH2
X
RTS_CH3
X
RTS_CH4
X
Definition
This primitive output when active enables the corresponding function to be received.
This primitive output enables the transmitter for the appropriate channel.
RX_LED1
X
X
RX_LED2
X
X
RX_LED3
X
X
RX_LED4
X
X
Used to override the default setting of the four front panel RX LEDs.
Continued………
RFL 9745 February 10, 2009
2 -43
RFL Electronics Inc. (973) 334-3100
Page 78
PRIMITIVE OUTPUTS ONLY
ALARM OUTPUTS ONLY
Analog 9745
Digital 9745
TX_FUNC1
X
X
TX_FUNC2
X
X
TX_FUNC3
X
X
TX_FUNC4
X
X
TX_FUNC5
X
TX_FUNC6
X
TX_FUNC7
X TX_LED1
X
X
TX_LED2
X
X
TX_LED3
X
X
TX_LED4
X
X
Definition
For the Audio System, this primitive output causes the appropriate channel to transmit its upper frequency. For the Digital System, this primitive output causes the appropriate Function to be transmitted.
For the Digital System , this primitive output causes the appropriate Function to be transmitted.
Used to override the default setting of the four front panel TX LEDs.
RFL 9745 February 10, 2009
2 -44
RFL Electronics Inc. (973) 334-3100
Page 79
Figure 2-26. 9745 Audio default primitive logic diagram RFL 9745 February 10, 2009
2 -45 (2-46 Blank) RFL Electronics Inc. (973) 334-3100
Page 80
Flasher Alarm Decay must be less than Flasher Timer
Figure 2-27. 9745 Audio default alarm logic diagram RFL 9745 February 10, 2008
2 -47 (2-48 Blank) RFL Electronics Inc. (973) 334-3100
Page 81
Figure 2-28. 9745 Audio default primitive logic diagram RFL 9745 February 10, 2009
2 -49 (2-50 Blank) RFL Electronics Inc. (973) 334-3100
Page 82
Figure 2-29. 9745 Digital Default primitive logic diagram RFL 9745 February 10, 2009
2 -51 (2-52 Blank) RFL Electronics Inc. (973) 334-3100
Page 83
Figure 2-30. 9745 Digital default alarm logic diagram RFL 9745 February 10, 2009
2 -53 (2-54 Blank) RFL Electronics Inc. (973) 334-3100