The text of a manual · part 12 of 43
Instruction Manual RFL 9745 Teleprotection Channel: Section 3. INSTALLATION, pages 84 to 93
Pages 84 to 93 of 394, from Instruction Manual RFL 9745 Teleprotection Channel
The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the RFL RFL-9745
Page 84
Section 3. INSTALLATION 3.1 INTRODUCTION This section contains installation instructions for the RFL 9745 and the Fiber Service Unit, including unpacking, mounting, and interconnection wiring.
3.2 UNPACKING RFL 9745 equipment may be supplied as individual chassis or interconnected with other chassis or assemblies as part of a system. The following paragraphs provide unpacking instructions for individual chassis and interconnected chassis; use the procedure that suits your equipment.
3.2.1 INDIVIDUAL CHASSIS RFL 9745 terminals supplied as individual chassis are packed in their own shipping cartons: 1.
Open each carton carefully to make sure the equipment is not damaged.
2.
After the chassis is removed from the carton, carefully examine all packing material to make sure no items of value are discarded.
3.
Carefully remove any packing materials inserted into the chassis to hold circuit cards in place during transit.
4.
Make sure all modules are fully seated in the chassis. The machine screws securing all I/O modules to the rear of the chassis should be fully tightened.
If you notice any signs of shipping damage, immediately notify RFL Customer Service at the phone number at the bottom of this page. Save all the packing material and the shipping carton, in case a damage claim needs to be filed with the shipping company that delivered the unit.
RFL 9745 February 24, 2009
3-1
RFL Electronics Inc. (973) 334-3100
Page 85
3.2.2 INTERCONNECTED CHASSIS RFL 9745 terminals ordered as part of a larger system may be interconnected with other chassis and mounted in a relay rack or cabinet, or on shipping rails for installation into a rack or cabinet at the customer's site. In such cases, the entire assembly is enclosed in a wood crate or delivered by air-ride van: 1.
If the equipment is crated, carefully open the crate to avoid damaging the equipment.
2.
Remove the equipment from the crate and carefully examine all packing materials to make sure no items of value are discarded.
3.
Carefully remove any packing materials that were inserted into the individual chassis to hold circuit cards in place during transit.
4.
Make sure all modules are fully seated in the chassis. The machine screws securing all I/O modules to the rear of the chassis should be fully tightened.
If you notice any signs of shipping damage, immediately notify RFL Customer Service at the phone number at the bottom of this page. Save all the packing material and the shipping carton, in case a damage claim needs to be filed with the shipping company that delivered the unit.
3.3 MOUNTING After unpacking, RFL 9745 equipment must be securely mounted, following the instructions in the following paragraphs. Procedures are provided for individual chassis, interconnected chassis installed in racks or cabinets, and interconnected chassis mounted on shipping rails; use the procedure that suits your equipment.
3.3.1 INDIVIDUAL CHASSIS RFL 9745 terminals housed in individual chassis have two mounting ears (one on each side). Hole sizes and spacings conform with EIA standards, so the RFL 9745 can be mounted in any standard 19inch rack or cabinet. Complete chassis dimensions are shown in Figure 3-1. The Fiber Service Unit (107460-x) is housed in a small rugged metal box, which has mountings for a variety of unistrut and DIN rail applications. Refer to the Fiber Service Unit Instruction Data sheet (publication number: ID C37.94FSU) for installation instructions.
RFL 9745 February 24, 2009
3-2
RFL Electronics Inc. (973) 334-3100
Page 86
FUNCTION TX
RFL Electronics Inc RFL 9745 TELEPROTECTION CHANNEL
RX
1
1
2
2
3
3
4
4
UP
5.25 in. (13.3 cm)
DOWN
2.25 in. (5.7cm) SELECT
RS232 I/O STATUS LEVELS LOG TEST ENTER
ALARM
1.5 in. (3.8 cm)
19.0 in. (48.3 cm)
NOTE: Allow 15 inches (38 cm) behind the rear panel for chassis and interconnect wiring.
Figure 3-1. Mounting dimensions, RFL 9745 Teleprotection Channel
CAUTION Any installation using an enclosed cabinet with a swing-out rack must be securely fastened to the floor. This will prevent the cabinet from falling forward when the rack is moved outward.
RFL 9745 February 24, 2009
3-3
RFL Electronics Inc. (973) 334-3100
Page 87
3.3.2 INTERCONNECTED CHASSIS INSTALLED IN RACK OR CABINET Systems mounted in racks or cabinets at the factory are to be placed in position and then bolted to the floor or wall, as appropriate, to secure the equipment in place. The type of hardware used will depend upon the particular surface to which the rack or cabinet is being mounted. Because of this, mounting hardware is not supplied with the rack or cabinet.
3.3.3 INTERCONNECTED CHASSIS MOUNTED ON SHIPPING RAILS Equipment to be installed in a rack or cabinet at the customer's site is mounted on shipping rails at the factory. To remove the shipping rails and mount the equipment, proceed as follows: 1.
Place the equipment as close to the front of the rack or cabinet as possible, with the rear panels of the equipment facing the front of the rack or cabinet.
2.
Remove all the screws securing the shipping rails to the equipment.
3.
Slide the equipment into the rack or cabinet.
4.
Install and tighten screws to all panels to secure the equipment in place.
3.4 VENTILATION The specified operating temperature range for RFL 9745 equipment is -30oC to +65oC (-22oF to +149oF). Operation at higher temperatures may affect system reliability and performance. Systems installed in enclosed cabinets should be ventilated to keep the temperature inside the cabinet within limits.
3.5 CONNECTIONS Electrical connections are made to each RFL 9745 chassis through the terminal blocks and connectors on the chassis rear panel. The rear panel of a typical RFL 9745 terminal is shown in Figure 3-2. The following paragraphs provide basic descriptions of all the connections that must be made. A diagram showing these typical connections appears in Figure 3-3. Refer to the "as supplied" drawings furnished with your RFL 9745 for more detailed descriptions of the connections that must be made to your system. NOTE Specific terminals on the rear panel terminal blocks are noted by the terminal block number followed by a dash and the terminal number (TB1-1, TB1-2, TB1-3).
RFL 9745 February 24, 2009
3-4
RFL Electronics Inc. (973) 334-3100
Page 88
REMOTE RS-232
IRIG-B ON
TB3
RXB-4W
TXB-4W (2W A/B)
TXA-4W
RXA-4W
ON
J2 CAUTION TO MAINTAIN SYSTEM INTEGRITY ALL SCREWS MUST BE SECURE FOR PROPER GROUNDING
1 2
TB2
1
2
3
4
5
6
7
RFL Electronics Inc. Boonton, New Jersey, USA
8
TB1 1
J1
2 3
3 OFF
OFF
4
4 5
5
TBA
6
6 9
1
10
16 C
7 OUT 1
8 9+
OUT 2
IN 1
IN 2
IN 3
NC
IN 4
NO
25
17
C
NC
ANC 1
NO
C
ANC 2
7
NC ANC 3
OUT 3
OUT 4
8
!
!
+9 -10
10TBB 9
1
16
10 C
OUT 1
OUT 2
IN 1
IN 2
IN 3
IN 4
ANC OUT 1
TBC
NC
NO
ANC 1
ANC OUT 2
ANC OUT 3
25
17
C
NC
NO
ANC 2
ANC OUT 4
C
NC ANC 3
ANC OUT 5
OUT 3
OUT
ANC OUT 6
12
1
Figure 3-2. Typical Rear view, RFL 9745 Teleprotection Channel, Audio System with Status Option
3.5.1 MAKING CONNECTIONS TO TERMINAL BLOCKS Most of the terminal blocks on the rear of the RFL 9745 are conventional screw-type barrier blocks. As an option, SWC I/O Modules and Audio Communications Modules can be fitted with compressiontype terminal blocks with a quick-disconnect feature that simplifies servicing. Screw-Type Terminal Blocks
With conventional screw-type barrier blocks, a retaining screw is loosened, a wire is slipped under the screw head, and the screw is re-tightened to secure the wire in place. Wires can either be stripped or terminated in spade lugs, depending on local practice.
Compression-Type Terminal Blocks
The RFL 9745's SWC I/O Modules and Audio Communications Modules can be optionally fitted with compression-type terminal blocks. With these blocks, individual wires are pushed into each terminal position, where a pressure screw closes a set of gripping jaws to clamp the wire in place. Wires can either be tinned or untinned, depending on local practice.
RFL 9745 February 24, 2009
3-5
RFL Electronics Inc. (973) 334-3100
Page 89
9745 AUDIO SB+
TB1-9
TBA-1
SB-
TB1-10
TBA-2
SB+
TB3-9
TBA-3
SB-
TB3-10
TBA-4
MAIN
REDUNDANT TBA-22 TB2-5
TBA-23
TB2-6
TBA-24
TB2-1
TBA-25
TB2-2
TBB-1
TB2-7
TBB-2
TB2-8
TBB-3
TXB-4W
TB2-3
TBB-4
TX/RX 2W (A/B)
TB2-4
TBB-22
RXA-4W
+ _
OUTPUT 1A
+ _
OUTPUT 2A
+ _
OUTPUT 3A
+ _
OUTPUT 4A
+ _
OUTPUT 1B
+ _
OUTPUT 2B
+ _
OUTPUT 3B
+ _
OUTPUT 4B
RXB-4W
TXA-4W
TBB-23 IRIG-B
TBB-24
J2 (BNC)
TBB-25 RS-232
IN1A
IN2A
J1- (DB9)
TBA-13
C
TBA-14
NC ANC 1A
+ _
TBA-5
TBA-15
NO
TBA-6
TBA-16
C
+ _
TBA-7
TBA-17
NC ANC 2A
TBA-8
TBA-18
NO
TBA-9
TBA-19
C
TBA-10
TBA-20
NC ANC 3A
TBA-11
TBA-21
NO
TBA-12
TBB-13
C
TBB-5
TBB-14
NC ANC 1B
TBB-6
TBB-15
NO
TBB-7
TBB-16
C
TBB-8
TBB-17
NC ANC 2B
TBB-9
TBB-18
NO
TBB-10
TBB-19
C
TBB-11
TBB-20
NC ANC 3B
TBB-12
TBB-21
NO
+
IN3A _
+
IN4A _
+
IN1B _
+
IN2B _
+
IN3B _
+
IN4B _
Figure 3-3. Typical rear panel connection diagram, RFL 9745 Teleprotection Channel, Audio System RFL 9745 February 24, 2009
3-6
RFL Electronics Inc. (973) 334-3100
Page 90
3.5.2 CONNECTIONS TO INTERFACE MODULES AND FIBER SERVICE UNIT 3.5.2.1 CONNECTIONS TO RS-449, G.703, X.21 AND E1 INTERFACE MODULES If your Digital RFL 9745 is equipped with an RS-449 interface module (105065-1), there will be a 37pin D-type male connector on the rear of the chassis that mates with any standard female RS-449 connector. Table 3-1 shows the signal names and pin numbers on this connector that are supported by the RFL 9745. If your Digital RFL 9745 is equipped with a G.703 Contra-Directional interface module (105065-2), there will be a 25-pin D-type male connector on the rear of the chassis that mates with any standard female G.703 Contra-Directional connector. Table 3-1 shows the signal names and pin numbers on this connector that are supported by the RFL 9745. When using this module, octet timing in the external equipment must be disabled. If your Digital RFL 9745 is equipped with a G.703 Co-Directional interface module (105065-11), there will be a 15-pin D-type male connector on the rear of the chassis that mates with any standard female G.703 Co-Directional connector. Table 3-1 shows the signal names and pin numbers on this connector that are supported by the RFL 9745. This module will generate octet timing if the J1 jumper is inserted. If your Digital RFL 9745 is equipped with an X.21 interface module (105065-10), there will be a 15pin D-type male connector on the rear of the chassis that mates with an standard female X.21 connector. Table 3-1 shows the signal names and pin numbers on this connector that are supported by the RFL 9745. If your Digital RFL 9745 is equipped with an E1 serial interface adapter (107320), refer to paragraph 3.6.5.5 for installation instructions. Refer to Table 3-1 for interface connections. When fastening mating connectors to the D-subminiature connectors, make sure that the screws on both ends of the mating connector are tightened to secure the connector to the panel.
NOTE All cabling to and from RS-449, G.703, X.21 and 120 Ohm E1 interfaces must utilize shielded twisted pair cable to minimize crosstalk and interference from external sources. All cabling to and from 75 Ohm E1 interfaces must utilize 75 Ohm coaxial cable.
RFL 9745 February 24, 2009
3-7
RFL Electronics Inc. (973) 334-3100
Page 91
Table 3-1. RS-449, G. 703, X.21 and E1 Interface connections, RFL 9745 RS 449 Signal RDRD+ RT+ RTSDSD+ ST+ STSG Chassis
Pin No. 24 6 8 26 22 4 5 23 19 1
G.703 Contradirectional Signal Pin No. Chassis 1 Tx Data (A) 2 Rx Data (A) 3 Tx Data (B) 9 Rx Data(B) 16 Rx Timing (A) 12 Rx Timing (B) 13 Tx Timing (B) 14 Tx Timing (A) 15
G.703 Codirectional Signal Pin No. Chassis 1 Tx Data(A) 2 Rx Data(A) 4 Tx Data(B) 9 Rx Data(B) 11
X.21 Signal Chassis Tx Data (A) Rx Data (A) Tx Data (B) Rx Data (B) Sig Timing (B) Sig Timing (A) DGND B Control A (1) Control B (2)
E1 Pin No. 1 2 4 9 11 13 6 8 3 10
Signal TX Data+ TX DataRX Data+ RX DataChassis
Pin No. 9 1 11 3 7
(1) Connect to +5 Vdc, (2) Connect to DGND B
3.5.2.2 CONNECTIONS TO FIBER OPTIC INTERFACE MODULES WARNING YOUR 9745 TERMINAL MAY BE EQUIPPED WITH FIBER OPTIC INPUT/OUTPUT MODULES THAT HAVE FIBER OPTIC EMITTER HEADS. FIBER OPTIC EMITTER HEADS USE A LASER LIGHT SOURCE THAT PRODUCE INVISIBLE RADIATION. FIBER OPTIC COMMUNICATION SYSTEMS ARE INHERENTLY SAFE IN NORMAL OPERATION BECAUSE ALL RADIATION IS CONTAINED IN THE SYSTEM. IT IS POSSIBLE DURING MAINTENANCE TO EXPOSE THE RADIATION BY REMOVING OR BREAKING THE FIBER. STARING DIRECTLY INTO THE LIGHT BEAM MAY RESULT IN PERMANENT EYE DAMAGE AND/OR BLINDNESS. NEVER LOOK DIRECTLY INTO THE LIGHT BEAM AND BE CAREFUL NOT TO SHINE THE LIGHT AGAINST ANY REFLECTIVE SURFACE. THE LASER SOURCE IS A CLASS I LASER PRODUCT, WHICH COMPLIES WITH APPLICABLE FDA, OSHA AND ANSI STANDARDS.
If your RFL 9745 is equipped with a Fiber Optic Module, fiber optic connectors must be connected to the fiber optic heads on the rear panel of the RFL 9745 chassis. Type ST series bayonet fiber optic connectors (or their equivalent) are used with both singlemode and multimode fibers. The exact mating connector used will depend upon the head that is installed in the FIO module, and the specific optic cable being used. When connecting fiber optic cables, make sure the connectors are properly aligned before tightening and then fully tighten them. This will help minimize losses in the connector.
RFL 9745 February 24, 2009
3-8
RFL Electronics Inc. (973) 334-3100
Page 92
3.5.2.3 SHORT HAUL FIBER INTERFACE MODULE
TX
RX
YELLOW ALARM
DATA
Assembly 107310 or 107340
Figure 3- 4. Front panel view of RFL 9745 Short Haul Fiber Interface module
The RFL 9745 Short Haul Fiber Interface module (Figure 3-4) is used in applications where the communications equipment is remotely located from interconnecting equipment. Data cables routed through cable troughs in a substation environment can be subjected to induced voltages from adjacent cables, producing intermittent loss of communications. To eliminate this problem the RFL 9745 Short Haul Fiber Interface module provides immunity by using a fiber optic communication path between the RFL 9745 and interconnecting equipment. The module operates in accordance with IEEE Standard: C37.94 for N times 64 kilobit per second Optical Fiber Interfaces between teleprotection and multiplexer equipment. The Short Haul Fiber Interface module is housed in a single 1.3 inch high module, which is installed at the rear of the 9745 chassis. The module consists of an input section (detector) and an output section (emitter). Table 3-2 contains general information related to the RFL 9745 Short Haul Fiber Interface module. Table 3-2. General Information, 9745 Short Haul Fiber Interface module characteristics at 25ºC Assembly Number
Type
Wavelength/Mode
Connector Type
Receiver Sensitivity (minimum)
TX Level (average)
Typical Distance
107310
LED Emitter/ Detector
830 (+/-40 nm) multimode
ST
-11dBm to-32dBm
-14dBm to -21dBm Average into 50µm fiber
Up to 2km (1.2mi)
-11dBm to -18dBm Average into 62.5µm fiber 107340
LED Emitter/ Detector
RFL 9745 February 24, 2009
1300 (+/- 30 nm) Single mode
ST
-35dBm
3-9
-19.5dBm to -26 dBm Average into 62.5µm fiber
Up to 10km (6.2mi)
RFL Electronics Inc. (973) 334-3100
Page 93
A typical application of the RFL 9745 Short Haul Fiber Interface module is shown in Figure 3-5, where the RFL 9745 is connected to an IMUX 2000. In this application there are no jumpers or settings on the 107310 or the MA-620, however, SW4-2 and SW4-3 on the DS562I must be set to the ON position.
Type ST bayonet connector ( 4 places)
Short haul fiber interface module Up To 2km for multimode Up to 10km for single mode Tx
Front panel of 9745
107310 or 107340
RFL 9745 Chassis (Top View)
Tx fiber
Rx
Rx fiber
Tx
MA-620 Rx
Rear panel of IMUX 2000
DS-562I
IMUX 2000 Chassis (Top View)
Rear panel of 9745
Figure 3-5. Typical Installation of an RFL 9745 Short Haul Fiber Interface module connected to an IMUX 2000
RFL 9745 February 24, 2009
3 - 10
RFL Electronics Inc. (973) 334-3100