3.5.2.3.1 CONTROLS AND INDICATORS Figure 3-6 shows the location of all controls and indicators on the RFL 9745 Short Haul Fiber Interface module. These controls and indicators are described below. Controls DS9
Fiber optic emitter
U7
Fiber optic detector
J1
Digital Communications board connector
Indicators D1
Data LED (Green):
Loss of signal when not illuminated. Active when fiber data is valid with no bit errors. Extinguished indicates loss of signal. Pulsing indicates bit errors.
D2
Yellow Alarm LED (Amber):
Yellow alarm when illuminated. Indicates that the remote fiber has failed and the remote transmitter is sending yellow code detected by the local fiber receive channel.
D1
J1
D2
U7
DS9
Figure 3-6. Controls and Indicators, RFL 9745 short haul interface module
RFL 9745 February 24, 2009
3 - 11
RFL Electronics Inc. (973) 334-3100
Page 95
3.5.2.4 FIBER SERVICE UNIT
RFL FSU
107460-1
PWR
YEL
SYNC
TX DATA
RX
RS-449 RFL Electronics Inc. Boonton, New Jersey USA
Figure 3-7. Fiber Service Unit, front panel view
The RFL FSU Fiber Service Unit (Figure 3-7) is used with the RFL 9745 Short Haul Fiber Interface module (Figure 3-4). The FSU consists of an input section (detector) and an output section (emitter) and is housed in a black anodized aluminum box. There are four types of Fiber Service Units, providing RS-449, G.703, V.35 or X.21 inputs and outputs on the non-fiber side of the connection. The FSU can be located up to 2km away from the RFL 9745. The RFL FSU Fiber Service Unit has a 15-pin or 37-pin male D-subminiature connector on its front panel depending on the application. During installation, make sure that the screws on both ends of the mating connector are tightened to secure the connector to the FSU panel. Fiber optic cables with type ST series bayonet fiber optic connectors (or their equivalent) must be connected to the fiber optic heads on the rear panels of the RFL FSU module and the RFL 9745 Short Haul Fiber Interface module. The exact mating connectors used will depend upon the heads that are installed in these modules and the specific optic cable being used. When connecting fiber optic cables, make sure the connectors are properly aligned before tightening, and then fully tighten them. This will help minimize losses in the connector. Figure 3-8 shows a typical Fiber Service Unit installation. Refer to the Fiber Service Unit Instruction Data sheet (publication number: ID C37.94FSU) for additional information.
RFL 9745 February 24, 2009
3 - 12
RFL Electronics Inc. (973) 334-3100
Page 96
Type ST bayonet connector ( 4 places)
Short haul fiber interface module
Fiber Service Unit
Up To 2km for multimode Up to 10km for single mode
107310 Or 107340
Front panel of 9745
Tx fiber
Tx
Rx fiber
Rx
Rx
Tx
Rear panel of 9745 RFL 9745 Chassis (Top View)
107460-X Or 108015-X
38 to 150 Vdc Input Power
RS-449 G.703 V.35 or X.21 as applicable
15-pin or 37-pin connector as applicable
Figure 3-8. Typical Installation of Fiber Service Unit Switch
Position
SW1
1 – 6 DOWN 7 UP 8 N/A
Both Digital Modules set to 64k, J6 set to ‘B’
RFL 9745 February 24, 2009
3 - 13
RFL Electronics Inc. (973) 334-3100
Page 97
3.5.3 KEYING INPUT CONNECTIONS Keying input connections are made to the following terminals on rear-panel terminal blocks TBA and TBB. Additional information can be found in Figures 3-2 and 3-3 and in the "as supplied" drawings furnished with the equipment. INPUT 1A Positive Negative
TBA-5 TBA-6
INPUT 2A Positive Negative
TBA-7 TBA-8
INPUT 3A Positive Negative
TBA-9 TBA-10
INPUT 4A Positive Negative
TBA-11 TBA-12
INPUT 1B Positive Negative
TBB-5 TBB-6
INPUT 2B Positive Negative
TBB-7 TBB-8
INPUT 3B Positive Negative
TBB-9 TBB-10
INPUT 4B Positive Negative
TBB-11 TBB-12
Each input can be assigned a unique name or label that will appear on the RFL 9745's front-panel display and menus during system operation. Section 6 of this manual contains more information on how to label the inputs.
RFL 9745 February 24, 2009
3 - 14
RFL Electronics Inc. (973) 334-3100
Page 98
3.5.4 OUTPUT CONNECTIONS Trip output connections are made to the following terminals on rear-panel terminal blocks TBA and TBB. Additional information can be found in Figures 3-2 and 3-3 and in the "as supplied" drawings furnished with the equipment. OUTPUT 1A Positive Negative
TBA-1 TBA-2
OUTPUT 2A Positive Negative
TBA-3 TBA-4
OUTPUT 3A Positive Negative
TBA-22 TBA-23
OUTPUT 4A Positive Negative
TBA-24 TBA-25
OUTPUT 1B Positive Negative
TBB-1 TBB-2
OUTPUT 2B Positive Negative
TBB-3 TBB-4
OUTPUT 3B Positive Negative
TBB-22 TBB-23
OUTPUT 4B Positive Negative
TBB-24 TBB-25
These are one-ampere, solid-state outputs. Each output can be assigned a unique name or label that will appear on the RFL 9745's front-panel display and menus during system operation. Section 6 of this manual contains more information on how to label the outputs.
RFL 9745 February 24, 2009
3 - 15
RFL Electronics Inc. (973) 334-3100
Page 99
3.5.5 ANNUNCIATOR OUTPUT CONNECTIONS Annunciator output connections are made to the following terminals on rear-panel terminal blocks TBA and TBB. Additional information can be found in Figures 3-2 and 3-3 and in the "as supplied" drawings furnished with the equipment. ANC 1A Common Normally-Closed (N.C.) Normally-Open (N.O.)
TBA-13 TBA-14 TBA-15
ANC 2A Common Normally-Closed (N.C.) Normally-Open (N.O.)
TBA-16 TBA-17 TBA-18
ANC 3A Common Normally-Closed (N.C.) Normally-Open (N.O.)
TBA-19 TBA-20 TBA-21
ANC 1B Common Normally-Closed (N.C.) Normally-Open (N.O.)
TBB-13 TBB-14 TBB-15
ANC 2B Common Normally-Closed (N.C.) Normally-Open (N.O.)
TBB-16 TBB-17 TBB-18
ANC 3B Common Normally-Closed (N.C.) Normally-Open (N.O.)
TBB-19 TBB-20 TBB-21
RFL 9745 February 24, 2009
3 - 16
RFL Electronics Inc. (973) 334-3100
Page 100
If the RFL 9745 is equipped with the status option, six additional solid-state annunciator outputs are available. Connections to these outputs are made at 12-position terminal block TBC on the rear panel of a 1U chassis mounted directly below the RFL 9745, as shown in Figure 3-9. Additional information can be found in the "as supplied" drawings furnished with the equipment. ANC OUT 1 Positive Negative
TBC-1 TBC-2
ANC OUT 2 Positive Negative
TBC-3 TBC-4
ANC OUT 3 Positive Negative
TBC-5 TBC-6
ANC OUT 4 Positive Negative
TBC-7 TBC-8
ANC OUT 5 Positive Negative
TBC-9 TBC-10
ANC OUT 6 Positive Negative
TBC-11 TBC-12
Each annunciator output can be assigned a unique name or label that will appear on the RFL 9745's front-panel display and menus during system operation. Section 6 of this manual contains more information on how to label the annunciator outputs.
RFL 9745 February 24, 2009
3 - 17
RFL Electronics Inc. (973) 334-3100
Page 101
TBC
ANC OUT 1
ANC OUT 2
ANC OUT 3
ANC OUT 4
ANC OUT 5
ANC OUT 6
+
+
+
+
+
+
-
-
1
-
-
-
12
ANC OUT 1 + ANC OUT 1 ANC OUT 2+ ANC OUT 2 ANC OUT 3+ ANC OUT 3 ANC OUT 4+ ANC OUT 4 ANC OUT 5+ ANC OUT 5 ANC OUT 6+ ANC OUT 6 -
Figure 3-9. Typical connection diagram for RFL 9745 status option
3.5.6 IRIG-B CONNECTIONS If an IRIG-B signal is to be used to synchronize the RFL 9745's clock, it must be connected to rearpanel BNC connector J2 as shown in Figure 3-2. The user has the option of connecting the IRIG-B clock to the local, remote or to both of the 9745’s. If the IRIG-B clock is connected to just one of the 9745’s, for example the local unit, the IRIG-B clock will be transmitted to the remote unit automatically on the modem. For an audio system, this requires that channel 1 be configured as a modem. Software in the remote unit will automatically compensate for the channel delay between the two units by adding the actual measured channel delay to the IRIGB time received from the local unit. This insures that the local and remote units are running off of the same IRIG-B clock. This provides very accurate time stamping of the sequence of events logs at both the local and remote units. For even more accurate time stamping of the sequence of events logs at the local and remote units, the IRIG-B clock should be connected to both the local and remote 9745’s. Since the IRIG-B signal only provides hours, minutes, seconds, and date, but not the year, the year parameter must be programmed by the user by accessing parameter number 063 in the parameter settings display as shown in paragraph 6.7.4, Example 3. If the 9745 is connected to an IRIG-B source, the user only has to program the year parameter. The 9745 will then automatically set the day/month and time parameters (hours, minutes, seconds). If a user manually sets the 9745 day/month parameter incorrectly, this parameter will be automatically corrected during the next IRIG-B update, if the year is set correctly. If the user attempts to change the time setting of a 9745 running on an IRIG-B clock, the time will change to the new setting but will be overridden by the IRIG-B clock when the 9745 system clock is updated, which is about every 10 minutes. The following message: “IRIG-B will override” will alert the user of this fact. RFL 9745 February 24, 2009
3 - 18
RFL Electronics Inc. (973) 334-3100
Page 102
3.5.7 CONNECTIONS TO THE AUDIO COMMUNICATIONS MODULE If the RFL 9745 is equipped with the Audio Communications module, connections to the communications channel(s) are made to the rear-panel terminal block TB2. Refer to Table 3-3 for rear panel connections to the narrowband Audio Communications module. Refer to Table 3-4 for rear panel connections to the wideband Audio Communications module. Table 3-3. Rear panel connections to the narrowband Audio Communications module
Type of Connection Two-wire Four-wire
Number of Communication Channels Single Single
Channel B B
Dual
A
Rear Panel Connections Transmit/Receive: TB2-3 and TB2-4 Transmit: TB2-3 and TB2-4 Receive: TB2-1 and TB2-2 Transmit: TB2-7 and TB2-8 Receive: TB2-5 and TB2-6 Transmit: TB2-3 and TB2-4 Receive: TB2-1 and TB2-2
B
Table 3-4. Rear panel connections to the wideband Audio Communications module.
Type of Connection Two-Wire
Number of Communication Channels Single Dual
Channel
Four-Wire
Single
B A B B
Dual
A
Rear Panel Connections Transmit/Receive: TB2-3 and TB2-4 Transmit/Receive: TB2-7 and TB2-8 Transmit/Receive: TB2-3 and TB2-4 Transmit: TB2-3 and TB2-4 Receive: TB2-1 and TB2-2 Transmit: TB2-7 and TB2-8 Receive: TB2-5 and TB2-6 Transmit: TB2-3 and TB2-4 Receive: TB2-1 and TB2-2
B
3.5.8 REAR-PANEL RS-232 CONNECTIONS A remote terminal (or a PC with terminal emulation software) may be connected to rear-panel RS-232 connector J1. The following pins are supported: 2 3 5 7 8
RECEIVE DATA (RxD) TRANSMIT DATA (TxD) COMMON (COM) REQUEST-TO-SEND OUT (RTS) CLEAR-TO-SEND OUT (CTS)
J1 is a male 9-pin D-subminiature connector (DB-9P). You must use a female 9-pin D-subminiature connector (DB-9S) to connect to it. The rear-panel RS-232 connector is disabled if an RS-232 device is connected to the front-panel RS-232 connector. This is done to allow a device such as the 9660 to be permanently wired to the rear panel connector, yet still allow access through the front panel connector. The change over occurs because any device connected to the front-panel port must drive the DTR line (pin 4) high. (See Section 4 for more information about the front-panel RS-232 connector.)
RFL 9745 February 24, 2009
3 - 19
RFL Electronics Inc. (973) 334-3100
Page 103
WARNING THE RFL 9745 CHASSIS MUST BE PROPERLY GROUNDED AS DESCRIBED IN THE FOLLOWING PARAGRAPH BEFORE ATTEMPTING TO CONNECT INPUT POWER. IMPROPER GROUND CONNECTIONS MAY RESULT IN SYSTEM MALFUNCTIONS, EQUIPMENT DAMAGE, OR ELECTRICAL SHOCK.
3.5.9 CHASSIS GROUND CONNECTIONS The ground studs next to terminal blocks TB1 and TB3 on the rear panel are the main grounding points for the RFL 9745 terminal. (See Figure 3-10 for location.) Grounding is accomplished by connecting a wire 16 AWG or larger between the ground stud and a solid earth ground. The grounding wires should be kept as short and straight as possible.
REMOTE RS-232
IRIG-B ON
TB3
RXB-4W
TXB-4W (2W A/B)
RXA-4W
TXA-4W
ON
J2 CAUTION TO MAINTAIN SYSTEM INTEGRITY ALL SCREWS MUST BE SECURE FOR PROPER GROUNDING
1 2
TB2
1
2
3
4
5
6
7
RFL Electronics Inc. Boonton, New Jersey, USA
8
TB1 1
J1
2 3
3 OFF
OFF
4
4 5
5
TBA
6
6 9
1
10
16 C
7 OUT 1
8 9+
OUT 2
IN 1
IN 2
IN 3
NC NO
IN 4
C
ANC 1
17 NC
25 NO
C
NC
7
NO
ANC 2
ANC 3
OUT 3
OUT 4
8
!
!
+9 -10
10TBB 9
1
16
10 C
OUT 1
OUT 2
IN 1
IN 2
IN 3
ANC OUT 1
TBC
NC
IN 4
NO
C
ANC 1
ANC OUT 2
ANC OUT 3
17 NC
25 NO
C
ANC 2
ANC OUT 4
NC
NO ANC 3
ANC OUT 5
OUT 3
OUT
ANC OUT 6
12
1
GROUND STUDS
Figure 3-10. Location of ground studs on rear panel of RFL 9745, Audio System
RFL 9745 February 24, 2009
3 - 20
RFL Electronics Inc. (973) 334-3100