Instruction Manual RFL 9745 Teleprotection Channel: Section 9. USING PC APRIL LITE, pages 326 to 335
Pages 326 to 335 of 394, from Instruction Manual RFL 9745 Teleprotection Channel
The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the RFL RFL-9745
Page 326
9.10 PC APRIL DOS MODE 9.10.1 STAND-ALONE MODE In the stand-alone mode the users PC is not connected to the RFL 9745. PC April can be used in stand-alone mode either as a training tool, or to create parameter files or logic files which can be downloaded to an RFL 9745 at a later time. In the stand-alone mode PC April for the RFL 9745 runs identically to the April software resident in the RFL 9745 itself.
9.10.1.1 USING PC APRIL AS A TRAINING TOOL PC April allows the user to get familiar with the 9745 April menus and displays, but without being connected to the 9745. When used as a training tool, all that is needed is the PC April diskette and a PC. Once the contents of the PC April CD is loaded into drive C of the PC as described on page 9-2 of this section, proceed as follows. After the DOS prompt (C:\APRIL>), type PC_APRIL [enter], to view the PC April opening display as shown below.
C:\APRIL>PC_APRIL * * Begin RFL 9745 April for DOS * 9745> Figure 9-15. PC April opening display
RFL 9745 July 1, 2008
9 - 11
RFL Electronics Inc. (973) 334-3100
Page 327
Then type H [enter] to enter the main menu as shown in figure 9-16.
RFL Electronics APRIL(t) Remote Communications, Version 2.0 (c)1993, 1994 H - Display the main menu A - Go to the alarms display V - Go to the values display P - Go to the programming menu (password required) D - Go to the read settings menu F - Go to the configuration and software version display K - Go to the logic programming menu (password required) T - Go to the test menu (password required) U - Enter the update mode X - Exit the update mode S - Go to sequence of events menu B - Load parameters from file (MSDOS only) C - Save current parameters to file (MSDOS only) N - Enter file name (MSDOS only) Z - Exit to DOS (MSDOS only) 9745> Figure 9-16. PC April main menu in stand-alone mode
From this point onward, the user can select April commands to view the alarms display, the values display, and other menus or displays by selecting the letter that corresponds to the command listed in Figure 9-16. The user can also make changes to parameters and tables in order to get familiar with the various PC April commands. Detailed instructions on how to use commands ‘H’ through ‘S’ are described in section 6 of this publication. Instructions on how to use commands ‘B’, ‘C’ , ‘N’ and ‘Z’ are described below. The last page of this section contains the 9745 menu hierarchy which shows all of the PC April commands on one page in addition to the PC April menu structure. Command B
Loads the parameter file from the hard disk or diskette to the RAM of the PC enable the user to edit the file.
C
Saves the parameter file from the RAM of the PC to the hard disk or diskette after the file has been edited by the user.
N
Allows the user to name the parameter file before using the ‘B’ or ‘C’ commands.
Z
Allows the user to return to DOS.
to
RFL 9745 July 1, 2008
Function
9 - 12
RFL Electronics Inc. (973) 334-3100
Page 328
9.10.1.2 USING PC APRIL TO CREATE PARAMETER AND LOGIC FILES PC April can also be used in the stand-alone mode to create parameter and logic files which can be downloaded to an RFL 9745 at a later time. In the stand-alone mode the user can perform the operations described below. 1.
Creating and saving a parameter file:
A parameter file contains 9745 system parameter settings similar to those shown in figure 6-7. The user has the option to change these settings to meet his particular application. For example the user can change the system label, the channel setting, the time and date settings, or other parameter settings. A parameter file can be edited or created by the user through the programming menu. The user enters the main menu by selecting ‘H’ [enter], then enters the programming menu by selecting ‘P’ [enter], and then enters the password. The user can then display the present parameter settings and parameter numbers by selecting ‘D’ [enter]. The parameter settings can then be changed using the ‘##’ command in the programming menu. Three examples of how to change parameter settings are shown in paragraph 6.7.4. When the parameter settings have been changed to the required values, the user selects ‘SV’ [enter] to save the new values. The user then selects ‘Q’ [enter] to return to the main menu, then selects ‘N’ [enter] to name the new parameter file (file name with path), and finally selects ‘C’ [enter] to save the new parameter file. Before creating or overwriting an existing parameter file, the system will verify the file name. If the user does not start off with a parameter file using the /R option in the PC April command string shown above, the parameters will all be initialized to zero. This may cause an error message to appear on the display. The user can ignore the error message, however the zeroed parameters will still be saved in the parameter file. 2.
Loading a parameter file from the diskette or hard drive to PC April:
An existing parameter file can either be loaded on bootup when PC April is initialized by using the /R option in the command string, or by using the ‘B’ command in the PC April main menu. An example of a command string for loading an existing parameter file when PC April is first initialized is shown below: C:\APRIL>PC_APRIL /Rfile
[enter]
An existing parameter file can also be loaded by using the ‘B’ command from the PC April main menu. From the main menu select the ‘N’ command to name the existing parameter file, then select the ‘B’ command to load the existing parameter file. 3.
Creating and saving a logic file (primitive and alarm):
A primitive logic table contains 9745 system logic settings similar to those shown in figure 6-16. An alarm logic table contains 9745 alarm logic settings similar to those shown in figure 6-17. The user has the option to change settings in any one or both of these tables to meet his particular application. A logic file (primitive and alarm) can be edited or created by the user through the logic programming menu. The user enters the main menu by selecting ‘H’ [enter], then enters the logic programming
RFL 9745 July 1, 2008
9 - 13
RFL Electronics Inc. (973) 334-3100
Page 329
menu by selecting ‘K’ [enter], and then enters the password. To edit the primitive logic table select ‘S’ [enter], and then ‘V’ [enter] to view the table. The primitive logic table can then be edited to the required values using the ‘##’ command in the primitive logic edit menu. When satisfied, the user selects ‘SV’ [enter] to save the new values. The user then selects ‘Q’ [enter] to return to the logic programming menu. To edit the alarm logic table select ‘T’ [enter], and then ‘V’ [enter] to view the table. The alarm logic table can then be edited to the required values using the ‘##’ command in the alarm logic edit menu. When satisfied, the user selects ‘SV’ [enter] to save the new values. The user then selects ‘Q’ [enter] to return to the logic programming menu. From the logic programming menu the user selects ‘N’ to name the new logic table file (primitive and alarm), and then ‘SV’ to save it. Before creating or overwriting the existing logic file, the system will verify the new file name. When the “SV” command is made in the logic programming menu, a file is automatically created which contains the primitive logic table, the alarm logic table, the compiled tables, and the timer names. 4.
Loading a logic file (primitive and alarm) from the diskette or hard drive to PC April:
A logic file (primitive and alarm) can either be loaded on bootup when PC April is initialized by using the /F option in the command string, or by using the ‘O’ command in the PC April logic programming menu. An example of a command string for loading a logic file when PC April is first initialized is shown below: C:\APRIL>PC_APRIL /Ffile
[enter]
A logic file can also be loaded by using the ‘O’ command from the PC April logic programming menu. From the main menu select the ‘K’ command and enter the password to go to the logic programming menu. From the logic programming menu select the ‘N’ command to name the existing logic table file, then select the ‘O’ command to load the logic file.
RFL 9745 July 1, 2008
9 - 14
RFL Electronics Inc. (973) 334-3100
Page 330
9.10.2 WINDOW MODE In window mode, PC April can be run on a PC that is connected to the front panel of an RFL 9745 via an RS232 cable. The RFL 9745 is DTE equipment, so there is no need for a null modem. The user activates either a COM1 or COM2 connection using the /C option and sets the baud rates of the PC and the RFL 9745 to the same value, using the front panel of the RFL 9745 (LEVELS then UPARROW) and the /B option for PC April. If the /B option is not selected, the default baud rate of 9600 will be automatically selected for the PC. When the /C option is selected, PC April will display the ‘W’ (window) command in the main help menu as shown in figure 9-11. Selecting the ‘W’ command puts PC April into window mode, which allows the PC to communicate with the RFL 9745. An exclamation point (‘!’) proceeds all information displayed (except for update mode). At this point, all keyboard entries are routed to the communication port on the RFL 9745, and all output from the RFL 9745 is displayed on the PC screen. The /C option must be selected to enable the PC to communicate with the RFL 9745. The number following the /C option must correspond to the communications port of the PC which is connected to the RFL 9745, or the user will not be able to access the window mode. As an example, at the system prompt (C:\APRIL>), type PC_APRIL /C1 [enter] to start PC APRIL using the COM1 port. Then type H [enter] to enter the main menu as shown in Figure 9-17.
RFL Electronics APRIL(t) Remote Communications, Version 2.0 (c)1993, 1994 H - Display the main menu A - Go to the alarms display V - Go to the values display P - Go to the programming menu (password required) D - Go to the read settings menu F - Go to the configuration and software version display K - Go to the logic programming menu (password required) T - Go to the test menu (password required) U - Enter the update mode X - Exit the update mode S - Go to sequence of events menu W - Window remote April B - Load parameters from file (MSDOS only) C - Save current parameters to file (MSDOS only) N - Enter file name (MSDOS only) Z - Exit to DOS (MSDOS only) 9745>
Figure 9-17. PC April main menu where PC is connected to an RFL 9745
RFL 9745 July 1, 2008
9 - 15
RFL Electronics Inc. (973) 334-3100
Page 331
The user can access functions which interact between the PC and the RFL 9745 via the PC keyboard function keys. This is to allow the user to route files on the PC to the RFL 9745 and vice versa. The following function key commands are supported: F1 - Display this help F2 - Upload logic (TABLES) or SYSTEM file to RFL 9745 via XMODEM F3 - Upload parameter (batch) file to RFL 9745 F4 - Download parameters from RFL 9745 and save in file F5 - Download logic from RFL 9745 and save in file F6 - Store output from RFL 9745 in a log file When the user presses a function key command ‘F2’, ‘F3’, ‘F4’ or ‘F5’, a box appears on the PC screen with the file name to be read or written. The user can edit the file name including the path. If the user wishes to cancel the command, he can press ‘Esc’. If the user presses ‘Enter’, a verify is run on the file. If a file is to be read but does not exist, a beep sounds and the command does not continue. If a file is to be written but already exists, the user is asked to confirm overwriting the file. In this mode of operation (PC April connected to an RFL 9745) the user can perform the operations described in the following sections.
RFL 9745 July 1, 2008
9 - 16
RFL Electronics Inc. (973) 334-3100
Page 332
# PARAMETER 999 System Label 001 Channel 1 002 Tone 1 Tx Freq 003 Transmit Level 005 Tone 1 Rx Freq 006 Rx Bandwidth 008 Rx Alarm 010 FM Noise
SETTING 9745 DEMO UNIT Modem 700Hz 1000Hz -15.00 dBm 700Hz 1000Hz 380Hz -33 dBm 75%
016 Channel 2 017 Tone 2 Tx Freq 018 Transmit Level 020 Tone 2 Rx Freq 021 Rx Bandwidth 023 Rx Alarm 025 FM Noise
Single 2900Hz 3050Hz -15.00 dBm 2900Hz 3050Hz 380Hz -33 dBm 28%
031 Channel 3 032 Tone 3 Tx Freq 033 Transmit Level 035 Tone 3 Rx Freq 036 Rx Bandwidth 038 Rx Alarm 040 FM Noise
Single 2145Hz 2445Hz -15.00 dBm 2145Hz 2445Hz 380Hz -33 dBm 28%
046 Channel 4 047 Tone 4 Tx Freq 048 Transmit Level 050 Tone 4 Rx Freq 051 Rx Bandwidth 053 Rx Alarm 055 FM Noise
Single 1465Hz 1765Hz -15.00 dBm 1465Hz 1765Hz 380Hz -33 dBm 28%
060 Opt Status Board 062 Chan delay alarm 064 Date 066 Hour Adjust 068 Remote Address
No 8 ms 10/12 0 0
#
PARAMETER
SETTING
004
Boost Level
0 dB
007 Rx Level 009 AM Noise (SNR)
-15 dBm 5 dB
019
0 dB
Boost Level
022 Rx Level 024 AM Noise (SNR)
-15 dBm 8 dB
034
0 dB
Boost Level
037 Rx Level 039 AM Noise (SNR)
-15 dBm 8 dB
049
0 dB
Boost Level
052 Rx Level 054 AM Noise (SNR)
-15 dBm 8 dB
061 063 065 067 069
A 2000 14:15:55 0
EE Pot J10 Year Time Local Address Reset Log
Figure 9-18. 9745.BAT Parameter File (Narrow)
RFL 9745 July 1, 2008
9 - 17
RFL Electronics Inc. (973) 334-3100
Page 333
9.10.2.1 HOW TO UPLOAD A SYSTEM FILE FROM THE PC TO THE 9745 CAUTION Before uploading the SYSTEM file, you must first determine the system software version (Software ID) by following the directions in paragraph 6.9.
NOTE After you perform the “controlled system software upload” the RFL 9745 LCD will display the following message: SETUP REQUIRED. This means that the parameter file must be uploaded. You can do this by following the instructions in paragraph 9.6. If your software ID is 4.8, the baud rate of the 9745 may change to 2400 or may stay the same, after the system software upload is complete. If the baud rate changes you will get erroneous characters on your PC display such as: ςςςς , ↑↑↑↑, ≈≈≈≈ , ≥≤ , or ⎫⎫⎫⎫. If this happens you must change the baud rate of your PC to 2400 before loading the parameter file. If you are writing over a version other than 4.8 the baud rate of your 9745 will stay the same and you don’t have to change the baud rate of the PC to match it.
RFL 9745 July 1, 2008
9 - 18
RFL Electronics Inc. (973) 334-3100
Page 334
Table 9-1. RFL 9745 Menu Hierarchy H. Display the main menu. A. Go to the alarms display. V. Go to the values display. P. Go to the programming menu. H. Display programming help. Q. Leave programming menu. SV.Save new settings. C. Change password. D. Display present settings and parameter numbers. ##. Edit this specific number parameter. D. Go to the read settings menu. F. Go to the configuration and software version display. K. Go to the logic programming menu. H. Display logic menu help. A. Go to alarm and I/O name menu. C. Change password. D. Go to timer parameter menu. E. Download SYSTEM or TABLES (Replaced by PC APRIL LITE) F. Restore default logic. G. Output primitive logic table. M. Output alarm logic table. Q. Leave logic programing menu. R. Go to default logic configuration menu. S. Edit primitive processor logic table. Q. Leave edit menu. V. View table. H. Display help. ##. Edit this record. SV.Save Programming and Assemble Logic. T. Edit alarm logic table. Q. Leave edit menu. V. View table. H. Display help. ##. Edit this record. SV.Save Programming and Assemble Logic. ##. Edit this specific number parameter. SV.(MSDOS) Save programming and compile logic. N. Name logic file (MSDOS only). These parameters are only seen in stand alone mode O. Load logic file (MSDOS only). T. Go to the test menu. H. Display test menu help. Q. Leave test menu. C. Change password. T. Redisplay tests. ##. Run this test. U. Enter the update mode. X. Exit the update mode. S. Go to sequence of events menu. H. Display sequence of events help. A. Toggle labels on events dispay, curently=default labels. D. Dump all events to port. E. See directory of events. L. Toggle level of event triggers, currently=level two. R. Reset all events. Q. Leave sequents of events menu. ##.View this sequence of events record. B. Load parameters from file (MSDOS only). C. Save current parameters to file (MSDOS only). These parameters are only seen in stand alone mode N. Enter file name (MSDOS only). Z. Exit to DOS (MSDOS only).
Main Menu
RFL 9745 July 1, 2008
Sub Menu
Sub-sub Menu
9 - 19
RFL Electronics Inc. (973) 334-3100
Page 335
This page intentionally left blank
RFL 9745 July 1, 2008
9-20