Instruction Manual RFL 9745 Teleprotection Channel: Section 9. USING PC APRIL LITE, pages 316 to 325

Pages 316 to 325 of 394, from Instruction Manual RFL 9745 Teleprotection Channel

The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the RFL RFL-9745

Page 316

Section 9. USING PC APRIL LITE 9.1 PC APRIL LITE FOR WINDOWS 2000 AND XP, OVERVIEW The 9745 communication software was designed when MS DOS based programs were dominant over the Windows Platform. As Windows became more popular, MS DOS became a background program and was eventually dismissed from PCs and lap tops as Windows 2000 and XP no longer relied on a Dos shell. RFL kept pace with this change and developed PC APRIL LITE. This new version of APRIL has the look and feel of any other Windows based program and has automated the UPLOAD, DOWNLOAD and SYSTEM RESTORE functions. The one feature that could not be duplicated was the ability to emulate a 9745. Thus the STAND-ALONE mode was not incorporated into this new PC APRIL. Thus it was called PC APRIL LITE. PC APRIL LITE can also be used to dial into a 9745 using a modem. Please reference Section 4. The following section contains information on how to use PC APRIL LITE software. Two CD’s are supplied with every RFL 9745 system. The first CD contains the RFL9745 Instruction Manual and the PC APRIL LITE software. The second CD contains the Custom Logic File. The official nomenclature of the PC April Lite Software Emulation is SW9745PAL0XX, where XX is the number of the current revision. The first CD contains the PC April Lite installation set-up file and three parameter files. The parameter files are listed below. 1) 6750.bat 2) 9745.bat 3) digital.bat

6750 Analog parameter file 9745 Analog default parameter file 9745 Digital default parameter file

The 9745 system software can be downloaded from the RFL website at rflelect.com. The official nomenclature of the system file is S9745RZZZ.MHX, where ZZZ is the number of the current revision. The system file name will change as new updated versions of the system software are released. This file will enable a user to upload the 9745 system software if the need arises. See paragraph 9.10.2.1 for loading instructions. NOTE The user is advised to copy the PC APRIL LITE parameter files (6750.bat, 9745.bat, and digital.bat) from the CD to the hard drive of a PC.

NOTE The new system software versions should be used only with the latest RFL9745 CPU modules Part No. 107335-X. Operating System Software SW9745SY201 (Version 7.0) or SW9745SY301 (Version 8.0 Australia) cannot be loaded into chassis’s with the following CPU Part Numbers: 105025-X 107330-X

RFL 9745 July 1, 2008

9-1

RFL Electronics Inc. (973) 334-3100

Page 317

9.2 LOADING PC APRIL LITE 1. Insert the CD into your PC and browse to find the APRIL LITE.EXE (1.34MB) 2. Clicking on the file will start the installation. The program will prompt you during the set-up. April Lite will create its own folder and ICON on your desktop. Verify that the following files are in the APRIL LITE directory in drive C.

6750.bat 9745.bat digital.bat

6750.mhx 9745.mhx digital.mhx optic.mhx

PC APRIL LITE can also be obtained from the RFL web site. From the RFL home page click on ‘Customer Service’ then click on ‘RFL Software Utilities.’ You can then chose the file location as you would in any other downloaded program. The software can also be mailed to you on a disk, CD ROM or emailed from an RFL associate. However some firewalls will not permit the program to pass through and a temporary change to the extension might be required. The opening screen for April Lite is shown below:

Figure 9-1. April Lite Opening Screen

RFL 9745 July 1, 2008

9-2

RFL Electronics Inc. (973) 334-3100

Page 318

9.3 PC APRIL LITE CAPABILITIES 1.

Download a logic parameter file from the 9745 to a PC (See paragraph 9.5).

2.

Upload a logic parameter file from a PC to the 9745 (See paragraph 9.6 and note below).

3.

Upload a system file from a PC to the 9745. (See paragraph 9.6).

4.

Upload a system file from a PC to the 9745 if the system file has crashed. (See paragraph 9.8).

5.

Store the output from a 9745 in Log File. (See paragraph 9.9).

Each of these modes will be discussed in detail later in this section.

NOTE If a logic file is uploaded, the corresponding parameter file must also be uploaded. The logic file must be uploaded first, followed by uploading the parameter file.

9.4 ESTABLISHING COMMUNICATIONS Click on “Setup.” A “COM Options” button will appear as shown below.

Figure 9-2. COM Options

Click on “COM Options” the following screen will appear.

RFL 9745 July 1, 2008

9-3

RFL Electronics Inc. (973) 334-3100

Page 319

Figure 9-3. COM Options Set-up

Definitions: Port Most PC/Laptops will use COM 1, there are 8 ports to select from. Baud Rate There are 10 selectable baud rates, however the 9745 will only use the following: 300, 1200, 2400,9600 and 19200. Data Bits/Parity/Stop Bits If not already set to the default values of 8, None and 1 respectively, they must be set now. Flow Control (handshaking) Check “XON/XOFF” Connect Type Only check “Direct” if using an RS-232 interface. Phone# Enter a phone number if a modem is being used. Note, this set-up only needs to be done once unless you are changing the “Connect Type.” After the set-up is complete click the “OK” button. RFL 9745 July 1, 2008

9-4

RFL Electronics Inc. (973) 334-3100

Page 320

After the COM Option and Flow Control dialog box has been completed connection to the 9745 must be made. Click on “Terminal” > “Connect” as shown below.

Figure 9-4. Making a Connection to the 9745

Once a connection is made a confirmation is displayed, click “OK.”

Figure 9-5. Connection Confirmation

At this point you should press the enter key on your PC and a ‘9745>’ prompt will appear. PC April Lite will now work exactly as PC April for DOS as outlined in Section 6 of the this Manual with the exception of Stand Alone mode and the F1 commands (Upload/Download) described in the following sections. The Upload/Download functions have been simplified in PC April Lite.

9.5 DOWNLOADING LOGIC AND PARAMETER FILES FROM THE 9745 Once you click on “Download from 9745” two options will appear. “Download Logic File” and “Download Parameter File.” It does not matter which one you do first. Both files are downloaded in the same manner.

Figure 9-6. Downloading Logic and Parameter Files

RFL 9745 July 1, 2008

9-5

RFL Electronics Inc. (973) 334-3100

Page 321

If this is a digital system you must check “Digital System.” Then edit the logic name. The default is “FLASH.MHX.” You can browse to place the file in any folder you wish. The receiving protocol remains “APRIL commands.” Click on the “Receive” button.”

Figure 9-7. Downloading File from 9745

You will now see the download dialog box and the word “wait” will be shifting in the “Status” line for several seconds as shown below. If you choose a preexisting file, PC Lite will prompt you with a warning that the file will be replaced. Clicking “YES” will allow the process to continue. Clicking no will allow you to pick a different file name. If the file already exists April Lite will prompt you to either change the name or overwrite the file with “OK” and “YES” buttons.

RFL 9745 July 1, 2008

9-6

RFL Electronics Inc. (973) 334-3100

Page 322

Figure 9-8. Downloading Process Dialog boxes

Once the download begins, the “File” line may refresh several times until the entire file is transferred.

Once the download is completed click the “OK” button, then “Exit” to continue.

RFL 9745 July 1, 2008

9-7

RFL Electronics Inc. (973) 334-3100

Page 323

Figure 9-9. Downloading Confirmation

All downloaded files are stored in the April Lite folder.

9.6 UPLOADING LOGIC, PARAMETER AND SYSTEM FILES TO THE 9745 Clicking on “Upload to 9745” will give you four options as shown below.

Figure 9-10. Uploading to 9745

An “Upload Logic File” must be performed before you can perform an “Upload Parameter File.” Uploading the System File, Logic, and Parameter Files are preformed in the same manner. However it is recommended that the System file be done at a baud rate of 19200. For this you must go back to “COM options.”

RFL 9745 July 1, 2008

9-8

RFL Electronics Inc. (973) 334-3100

Page 324

Click on “Upload Logic File.” Then browse to/or enter the MHX file name. The Protocol should be Xmodem. Then click send as shown below.

Figure 9-11. Uploading to 9745

In the “Last event” line the word “wait” will again shift for several seconds then begin the upload.

Figure 9-12. Uploading Process Dialog boxes

The upload will take just over 1 minute. You can track its progress by watching the “Elapsed” and “Remaining” time lines. When the upload is completed click on the “OK” button then “Exit.” As shown below.

Figure 9-13. Uploading Confirmation

RFL 9745 July 1, 2008

9-9

RFL Electronics Inc. (973) 334-3100

Page 325

9.7 UPLOADING A CRASHED 9745 The “Upload System File from BIOS Mode” (See fig. 5-10) is only used when the 9745’s operating system “crashes.” The LCD of the 9745 will display “DOWNLOAD REQUIRED”. This can happen by : • Accidentally loading a logic table MHX file rather than a System File. • The System File was corrupted. • The upload was disrupted during an upload of a System File, or during an upgrade. The read out shown below will be the only response you will receive from a crashed 9745.

Figure 9-14. Uploading a Crashed 9745

When a 9745 crashes it will automatically boot down to a 2400 baud rate. You must reset the “COM Options” to 2400 baud and reconnect to the 9745. Click on “Upload to 9745” and select “Upload System File from BIOS Mode.” Select the proper file and continue with the restore. It will take approximately 64 minutes to restore. It is recommended that the logic and parameter files be reloaded to prevent possible logic/parameter damage. If you should choose to upgrade your 9745’s Operating System and do not have access to the original MHX or BAT Files, you may use the “Upgrade” button to Automatically step you through the downloading, upgrading and uploading of the MHX and BAT files.

9.8 SAVING 9745 DISPLAYS, EVENTS, AND LOGS To save any information on the screen such as parameters, alarm status, configuration, etc…You can simply use your mouse to highlight and copy/paste to a word document. This takes the place of F6 in the original PC April for DOS version.

9.9 AUTOMATIC UPGRADE This feature performs an automatic download of the logic and parameter files. It then uploads the System file (MHX), logic MHX and parameter BAT file. April Lite will prompt you to browse and name files as it steps through the process. This procedure is recommended when you do not have access to the original logic MHX file. Not uploading the original logic MHX file deletes the logic name and number (lines 74 and 75) in the Configuration display. Uploading the original logic file restores line 74 and 75.

RFL 9745 July 1, 2008