Instruction Manual RFL 9745 Teleprotection Channel: Section 10. UCA INTERFACE MODULE, pages 336 to 345
Pages 336 to 345 of 394, from Instruction Manual RFL 9745 Teleprotection Channel
The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the RFL RFL-9745
Page 336
Section 10. UCA INTERFACE MODULE 10.1 INTRODUCTION The RFL 9745 UCA Interface module is used to connect the RFL 9745 to a LAN. This allows a user to access the RFL 9745 via a 10Base-T or 10Base-FL Ethernet LAN using a web browser or any UCA based software package. The module is installed at the rear of the RFL 9745 chassis in place of the upper Solid-State I/O or Solid-State Relay I/O module, and is powered from the RFL 9745 chassis. The rear panel of the RFL 9745 UCA Interface module is shown in Figure 10-1.
RS-232 REMOTE
10 BASE-T
RS-232 LOCAL
TO RFL UNIT
10 BASE-FL TX
RX
REMOTE
105950 UCA INTERFACE
BUS LINK NETWORK TX
TX (red) NETWORK (yellow) LINK (green) BUS (yellow)
Figure 10-1. Rear panel view of RFL 9745 UCA Interface Module
RFL 9745 May 25, 2001
10 - 1
RFL Electronics Inc. (973) 334-3100
Page 337
10.2 INSTALLATION The RFL 9745 UCA Interface module provides an RJ-45 jack on its rear panel for a Cat. 5 cable based network connection, two ST connectors (TX & RX) for multimode fiber based networks, and two DB9 male RS-232 Com ports for serial communication as shown in Figure 10-1. On the ECB (inside the module), switch SW1 selects the mode for networking, 10Base-T or 10Base-FL. The unit’s power must be cycled for a change of switch SW1 to take effect. The 9745 UCA Interface module is powered from the RFL 9745 chassis. There are four LEDs on the back panel of the 9745 UCA Interface module indicating the LAN communication status. Hardware connections are shown in Figure 10-2.
RFL 9745 Chassis RFL 9745 UCA Interface Module
10Base-T or 10Base-FL
LAN
Remote interrogation of 9745
RS-232 remote DTE RFL 9745 Motherboard
RS-232 local DCE
UCA Communication Cable
Figure 10-2. Hardware connections between the 9745 and the 9745 UCA Interface module
RFL 9745 May 25, 2001
10 - 2
RFL Electronics Inc. (973) 334-3100
Page 338
10.3 RS-232 CABLE CONNECTIONS RS-232 cables are needed for the connection between the RFL 9745 UCA Interface module and the RS-232 Com port on the RFL 9745 rear panel, and from the RFL 9745 UCA Interface module to the DTE or DCE equipment. These cables are shown in Figures 10-3 through 10-5. TO 9745 RS-232 REAR PANEL CONNECTOR
TO 9745 UCA INTERFACE MODULE RS-232 LOCAL CONNECTOR TXD
2
RXD
3
3 5
2
GND
9-PIN D-SUBMINIATURE FEMALE CONNECTOR
5 9-PIN D-SUBMINIATURE FEMALE CONNECTOR
Figure 10-3. Cable between RFL 945 chassis and RFL 9745 UCA Interface Module TO 9745 UCA INTERFACE MODULE RS-232 REMOTE CONNECTOR 2
TO DTE TXD
3
3
RXD
2
6
DTR
4
5
GND
5
9-PIN D-SUBMINIATURE FEMALE CONNECTOR
Figure 10-4. Cable between RFL 9745 UCA Interface module and remote port DTE equipment TO 9745 UCA INTERFACE MODULE RS-232 REMOTE CONNECTOR
TO DCE
2
TXD
2
3
RXD
3
6 5
DTR GND
6 5
9-PIN D-SUBMINIATURE FEMALE CONNECTOR
Figure 10-5. Cable between RFL 9745 UCA Interface mofule and remote port of DCE equipment
RFL 9745 May 25, 2001
10 - 3
RFL Electronics Inc. (973) 334-3100
Page 339
10.4 IP CONFIGURATION UCA communication uses the Internet Protocol (IP). The RFL 9745 UCA Interface module gets it’s IP address from the 9745 through the serial RS-232 com port. Therefore the IP address is static and must be configured using the 9745’s APRIL interface. The 9745 UCA Interface module does not support DHCP. The IP address can be modified only with 9745 firmware version 5.0 or later. To do this, connect a PC or laptop to the 9745’s serial communications port. When you get a prompt enter the programming menu by typing P, and then enter the password. To change parameter 059 (IP address) type 059 and then type the IP address in dotted decimal form ( [0-255].[0-255].[0-255].[0255] ). Once the 9745 accepts the new IP address you must save the changes by typing SV. Once the change is saved the UCA board will realize it and reboot. For a more detailed description of the APRIL interface consult the 9745 manual. If during the boot process the communication link between the UCA interface and the 9745 fails the IP address of 111.111.111.151 is used by default. If more than one UCA interface in the network defaults to that IP address both may cease to function properly. The default gateway IP address is changed via the built-in configuration Web server. The subnet mask is always 255.255.255.0 (Class C), and is not user configurable. See paragraph 10.8.2 for information on how to change the default gateway IP address. You must reboot the remote unit via the web server (paragraph 10.8.6) or by cycling power locally before the change is effective.
RFL 9745 May 25, 2001
10 - 4
RFL Electronics Inc. (973) 334-3100
Page 340
10.5 PORT REPLICATION The RFL 9745 has two communication ports. One is in the front of the chassis and one in the rear. The rear port is connected to the “local” port on the UCA interface. When the front port is in use it overrides the rear port and therefore will stop all serial communication to the UCA interface. The “remote” port is a replication of the 9745’s rear port. If the “remote” com port is active the port will communicate with the 9745’s rear port through the UCA interface. This also stops the UCA interface from communicating with the 9745. The front port of the 9745 still has the highest priority.
10.6 UCA PARAMETERS The 9745 UCA parameters can be accessed through the LAN by utilizing a UCA based software package. The 9745 Analog UCA Model variables cross-reference table is shown in Table 10-2.
10.7 FILE MANAGEMENT The UCA interface supports a limited number of file transfer services. Supported services are the read (download) and write (upload) services. File delete, rename and directory are not supported.
10.7.1 SYSTEM FILE UPLOAD/DOWNLOAD New versions of software for the RFL UCA Interface module can be uploaded remotely. You must use a fully qualified path i.e. “C:\rfl.exe” to read or write a system file. The old system file remains in effect until the UCA interface is rebooted. To update your code use the following basic procedure: NOTE This procedure will vary depending on the UCA file transfer software you use. (Object Explorer’s File Transfer Utility, etc.)
Step 1. Obtain a copy of the new “RFL.EXE” file. Step 2. Using a web browser logon to the UCA interface’s web server, and enable file download. (You can leave the web browser open for use in the last step) Step 3. Use your UCA file transfer software to send the file to the corresponding device’s C:\ directory. Step 4. Using the web browser, reboot the device.
RFL 9745 May 25, 2001
10 - 5
RFL Electronics Inc. (973) 334-3100
Page 341
10.7.2 SEQUENCE OF EVENTS DOWNLOAD You can download the 9745’s sequence of events using the same file transfer utility. When reading a file from the UCA interface, file download should not be enabled via the web server. The sequence of events file gets updated whenever the file download request happens. Hence the file transfer may seem to be longer than expected, but that is due to the limitation in the 9600 baud serial port. See Table 10-1 for a list of the downloadable Sequence of Events files.
Table 10-1. Downloadable sequence of events files
File Name soe_all soe_dir 1 through 100
RFL 9745 May 25, 2001
Description This contains all the events in detail. This contains the directory of events. These contain the individual events by number.
10 - 6
RFL Electronics Inc. (973) 334-3100
Page 342
10.8 USING THE BUILT-IN WEB SERVER Every UCA interface has a built-in web server for configuration. The IP address must already be known for the web server to function. The web may be used while the unit is using the default IP address, however it must be the only one on the network using the default IP address. You can use any HTML browser ( Netscape Navigator or Internet Explorer ) to view and use the web server. To access it type http://{IP_address} in the location or address field of your browser, where {IP_Address} is the IP address of the unit you want to configure. You will need to enter the Administrator password. NOTE The units are shipped with a default Administrator password of “rfl”. Once you’ve entered the password you will see a welcome page. Click on the Continue button. You are now presented with the following options: Change Administrator Password Gateway IP Address NSAP Address GOOSE Transmit Parameters GOOSE Receive Parameters Enable Download Reboot Each option will be discussed in the following paragraphs. Illustrations of most pages are shown in Figures 10-6 through 10-15 towards the end of this section. These illustrations are what you would see using Netscape Navigator. Your browser may have a slightly different appearance.
10.8.1 CHANGING ADMINISTRATOR PASSWORD This option is used to change the Administrator password. The passwords are case sensitive and only have a minimum length of 1 character. Valid characters are [A-Z], [a-z], and [0-9]. Passwords are case sensitive. You will need to enter the new password twice. Once the password is entered the change is effective immediately.
10.8.2 CHANGING GATEWAY IP ADDRESS This option is used to change the default gateway IP address. See section on IP configuration for more information on the gateway IP address. To change the Gateway IP address click on this option, enter the new address in the form field, and then click on done. The change only takes effect if the unit is rebooted.
10.8.3 CHANGING NSAP ADDRESS This option is used to change the NSAP address, which is used for GOOSE messages. To change it, click on this option, enter the new NSAP address in the form field, and then click on done. The change only takes effect if the unit is rebooted. RFL 9745 May 25, 2001
10 - 7
RFL Electronics Inc. (973) 334-3100
Page 343
10.8.4 CHANGING GOOSE TRANSMIT PARAMETERS This option is used to change the GOOSE Transmit parameters. The user configurable settings are the multicast MAC address each packet is addressed to, and the IED. To change the parameters, click on this option, enter the new value in the form field, and then click on done. The change only takes full effect if the unit is rebooted.
10.8.5 CHANGING GOOSE RECEIVE PARAMETERS This option is used to change the GOOSE Receive parameters. These parameters are used to map GOOSE inputs to the 9745 Trip Inputs. The user configurable settings are the multicast MAC address and the IED each Trip Input is “listening to”. The DNA index is selectable from 1-32. The bitpair value which sets each input to active or inactive can be set to 00, 01, 10, or 11. To change the parameters, click on this option, enter the new value in the form field, and then click on done. The change only takes effect if the unit is rebooted. Refer to Figure 10-13 for Goose Receive Parameters Setup.
10.8.6 ENABLE DOWNLOAD The UCA interface supports UCA File services that write to the UCA interface itself. Certain system files cannot be overwritten until the download is enabled via the web. This adds password protection to the upload feature. To enable the upload, click on this link and then you will get an “Are you sure?” page to make sure you want to upload system files. NOTE System files uploaded in this manner are not effective until the next reboot.
10.8.7 REBOOT This option is used to reboot the UCA interface’s computer. Here too you will get an “Are you sure?” question page. Once you confirm your intent to reboot, the unit will reboot after a delay of 2 seconds. The time it takes for the unit to reboot varies from unit to unit, but should not take longer than 1 minute. Once you reboot you will have to re-enter the web server by typing the IP address of the unit in the location or address field of the browser. You will also have to enter the password again.
RFL 9745 May 25, 2001
10 - 8
RFL Electronics Inc. (973) 334-3100
Page 344
10.9 ILLUSTRATIONS OF THE UCA CONFIGURATION WEB SERVER
Figure 10-6. Password entry
Figure 10-7. Welcome page
RFL 9745 May 25, 2001
10 - 9
RFL Electronics Inc. (973) 334-3100
Page 345
Figure 10-8. Main Menu
Figure 10-9. Change Administrator
RFL 9745 May 25, 2001
10 - 10
RFL Electronics Inc. (973) 334-3100