Page 298

Section 8. MAINTENANCE WARNING HAZARDOUS VOLTAGES CAN BE PRESENT INSIDE AN RFL 9745 TERMINAL. BEFORE ATTEMPTING MAINTENANCE, BE SURE TO READ AND COMPLY WITH THE HIGH VOLTAGE WARNING AND SAFETY SUMMARY INFORMATION ON PAGES iii AND iv OF THIS MANUAL.

8.1 INTRODUCTION This section provides maintenance instructions for the RFL 9745 Teleprotection Channel. Topics discussed include using the RFL 9745's diagnostic features to pinpoint problems, a troubleshooting procedure, removal and replacement procedures for the circuit board modules and I/O modules, a procedure for checking and replacing fuses. Information is also provided on how to arrange for service by RFL personnel.

8.2 DIAGNOSTICS 8.2.1 GENERAL DIAGNOSTICS The RFL 9745 Teleprotection Channel has been designed for years of trouble-free service, and does not require normal maintenance. In case of malfunction, its built-in diagnostics can detect a variety of internal system problems: 1.

Each internal module constantly reports its status to the CPU Module. Alarms are generated based on this information.

2.

Each power supply output feeds a comparator that constantly measures all three output levels. If a level goes above or below its set limits, an alarm is generated.

3.

Transmit and receive levels are constantly monitored. Levels can be manually monitored through APRIL (as described in Section 6 of this manual), or by using the front-panel switches (as described in Section 7.)

4.

Trip failures and shorted outputs are sensed and reported through APRIL. (Section 6 contains information on how to access this information.)

5.

The RFL 9745 can be accessed and interrogated by the RFL 9745 at the other end of the communications link. Conversely, you can use the RFL 9745 to access and interrogate the remote RFL 9745 using the Windows Remote APRIL mode described in Section 6 of this manual.

RFL 9745 February 24, 2009

8-1

RFL Electronics Inc. (973) 334-3100

Page 299

6.

The RFL 9745 maintains a sequence-of-events log. In this log, all important events are timestamped, date-stamped, and stored. Events include alarms, trips sent, trips received, and system warnings. A log of the number of operations for each function and alarm is also maintained. (See Section 6 for more information about the sequence-of-events log.)

7.

The RFL 9745 can be configured to do either manual or automatic checkback testing. To perform this test, the local RFL 9745 sends an address request to the remote RFL 9745. Based on the communications channel and the setup of the remote RFL 9745, either no response is made or the remote address is returned. Three possible results can occur:

Received Address Matches Programmed Address

The local and remote RFL 9745s pass both the address test and the checkback test.

Received Address And Programmed Address Do Not Match The local and remote RFL 9745s fail the address test, but pass the checkback test. The Local RFL 9745 Does Not Receive A Valid Response

The local and remote RFL 9745s fail both the address test and the checkback test.

Should a malfunction occur involving the RFL 9745, use the diagnostics described above or standard troubleshooting techniques to determine if the problem is in the RFL 9745, or in some other connected equipment. If the problem lies within the RFL 9745, try and determine which module or I/O module is defective. Once this is done, replacement should solve the problem. (Removal and replacement procedures can be found in paragraph 8.4.) Defective modules can be returned to RFL for repair. (See paragraph 8.7 for more information.)

RFL 9745 February 24, 2009

8-2

RFL Electronics Inc. (973) 334-3100

Page 300

8.2.2 POWER UP TESTS There are two versions of the start up diagnostics. One is very quick and is run on power up every time. The second takes more time and is only run if the test button on the front panel is pressed and held during power on. Each of these is described below. The quick version includes the following tests: 1. SRAM Test

0xAAAA and 0x5555 are written and read from every SRAM location.

2. COMMS Register Test

A bus test is run with the driver board.

3. Interrupt Register Test

Tests the ability to receive and acknowledge interrupts.

4.

NVRAM Test

0xAA and 0x55 are written and read from every NVRAM location.

5.

DUART Test

The ability to transmit and receive characters is tested by putting the DUART into loopback.

6. RTC Test

The real time clock is written to and read from to verify its operation.

7.

0xAAAAA and 0x5555 are written and read from every primitive processor code SRAM location.

TMS 320 Code RAM Test

8. TM S320 Interface Test

Tests the ability of the primitive processor to run programs and respond to inputs.

The long version includes all of the above tests plus the following: 1.

EEROM Test

Tests the ability to write to and read from every location in the EEROM.

2.

FLASH Test

Tests the ability to erase and write to a sector of the FLASH memory.

RFL 9745 February 24, 2009

8-3

RFL Electronics Inc. (973) 334-3100

Page 301

8.2.3 CRASH CODES The BIOS system puts out certain codes when there is a major system failure. These codes are generated by the MC68000 and a full understanding of this processor is required to make use of the codes. The following codes are common and may be of some assistance to the average user. 0x03

Address error.

0x10 or 0x11

Misalignment of the BIOS system software.

0x47

Driver queue overrun. The driver may not be functioning properly.

0x48

Comms queue overrun. The comms board may not be functioning properly.

0x49

System download complete, system restart commencing.

0x4A

System download failure, reattempt download.

8.3 TROUBLESHOOTING Figure 8-1 is a 9745 troubleshooting procedure which provides information on how to isolate problems to a module level. When the faulty module is located, follow the removal and replacement instructions in paragraph 8.4

RFL 9745 February 24, 2009

8-4

RFL Electronics Inc. (973) 334-3100

Page 302

Power ON

Yes

Front Panel illuminate? No

No

“WAITING FOR CPU” message?

Drop Front Panel

Yes Both green Power Yes Supply LED on?

Replace CPU module

No No

Test voltages on Test Points on rear edge of Power Supplies

Only one green Power Supply LED on?

Yes Both Power Supply LEDs off

Bad fuse on Power No Supply module?

No

Bad voltages?

Yes

Yes Verify proper Power in at 9745 Rear?

No Replace fuses

Replace Power Supply

Repair power source

Replace power Supply

“DOWNLOAD SYSTEM REQUIRED” message?

Verify cable connection from Front Panel to Drive Bd?

Yes Suspect module is “holding down” power supply output

Replace one module at a time until bad module is isolated

No

Bad

Yes

C

Good

A

D

B

Figure 8-1. 9745 Troubleshooting procedure – Module level

RFL 9745 February 24, 2009

8-5

RFL Electronics Inc. (973) 334-3100

Page 303

C

D

Refer to 9745 manual to download System file from disk

A

Replace Driver module

B

Repair Connection

No

If Front Panel does not display restored, replace Front Panel module

Self-Test Failure message?

Yes

Alarm LED is on

Replace module in following order:

On Front Panel, scroll thru alarms

CPU, Driver

Yes COMMS Alarm?

I/O(s), COMMS

No

Yes Compare INPUT state on Front Panel with Actual state on Rear Panel

Using Front Panel, RCV level bad?

Yes Use test equipment to check integrity of XMIT source

RCV levels bad on rear terminals?

Compare OUTPUT state on Front Panel with actual state on Rear Panel

No

Compare STATUS items on Front Panel with expected state

Yes RCV signal OK?

No

No

Repair wiring or bad XMIT

Via April, RVCR enabled?

Yes Replace COMMS module recheck programming recheck parameters

Yes Enable RCVR

Replace COMMS module

Repair XMIT source

Figure 8-1 (continued). 9745 Troubleshooting procedure – Module level

RFL 9745 February 24, 2009

8-6

RFL Electronics Inc. (973) 334-3100

Page 304

CAUTION Each module position in the RFL 9745 chassis is dedicated to a specific module type. Modules can suffer component damage if they are installed in the wrong chassis slot. When removing and replacing modules, make sure each module is placed in the proper slot before re-applying power.

8.4 REMOVAL AND REPLACEMENT The following paragraphs provide procedures to be used when removing and replacing RFL 9745 modules and I/O modules. Refer to Figure 8-2 for module locations. WARNING! POWER MUST BE TURNED OFF BEFORE REMOVING OR INSTALLING ANY RFL 9745 MODULES. FAILURE TO DO SO MAY RESULT IN COMPONENT DAMAGE.

8.4.1 CPU AND DRIVER MODULES (Audio and Digital Terminals) The CPU Module and the Driver Module are mounted at the front of the RFL 9745 chassis. To remove either of these modules, proceed as follows: 1.

On the rear panel, place the POWER switch on the Power Supply I/O Module behind the Main Power Supply Module in the OFF position.

2.

If the RFL 9745 is equipped with a redundant power supply, place the POWER switch on the Power Supply I/O Module behind the Redundant Power Supply Module in the OFF position.

3.

Open the door on the front of the RFL 9745 by loosening the two screws that hold it closed, and lowering the door to its open position.

4.

Disconnect any ribbon cables connected to the front edge of the module to be removed.

5.

Pull on the handle on the front of the module, until the module is out of the chassis.

To replace a CPU Module or Driver Module, proceed as follows: 1.

Determine the horizontal slot in the chassis where the module is to be installed. There are three horizontal module slots in the front of the RFL 9745 chassis. The Communications Module is installed in the top horizontal slot. The CPU Module is installed in the middle slot, and the Driver Module is installed in the bottom slot.

2.

Line up the edges of the module circuit board with the card guides in the chassis.

RFL 9745 February 24, 2009

8-7

RFL Electronics Inc. (973) 334-3100

Page 305

3.

Slide the module into the chassis until it is firmly seated.

4.

Reconnect any ribbon cables that were disconnected during module removal.

5.

Raise the front door back into its closed position, and tighten the two thumbscrews to secure it in place.

6.

On the rear panel, place the POWER switch on the Power Supply I/O Module behind the Main Power Supply Module in the ON position.

7.

If the RFL 9745 is equipped with a redundant power supply, place the POWER switch on the Power Supply I/O Module behind the Redundant Power Supply Module in the ON position.

8.4.2 POWER SUPPLY MODULES (Audio and Digital Terminals) All RFL 9745 chassis are equipped with one Power Supply Module; some are equipped with a second redundant supply. To remove a Power Supply Module, proceed as follows: 1.

On the rear panel, place the POWER switch on the Power Supply I/O Module behind the Main Power Supply Module in the OFF position.

2.

If the RFL 9745 is equipped with a redundant power supply, place the POWER switch on the Power Supply I/O Module behind the Redundant Power Supply Module in the OFF position.

3.

Open the door on the front of the RFL 9745 by loosening the two thumbscrews that hold it closed, and lowering the door to its open position.

4.

Loosen the #6 cross slot screw as shown in Figure 8-2.

5.

Pull on the handle or the metal ring (as applicable) on the front of the Power Supply Module, until the Power Supply Module is out of the chassis.

To replace a Power Supply Module, proceed as follows: 1.

Line up the edges of the Power Supply Module circuit boards with the card guides in the chassis.

2.

Slide the Power Supply Module into the chassis until it is firmly seated in its mating connector.

3.

Tighten the #6 cross slot screw as shown in Figure 8-2.

4.

Raise the front door back into its closed position, and tighten the two thumbscrews to secure it in place.

RFL 9745 February 24, 2009

8-8

RFL Electronics Inc. (973) 334-3100

Page 306

#6 cross slot screws

Figure 8-2. Front view of RFL 9745 with front cover folded over

5.

On the rear panel, place the POWER switch on the Power Supply I/O Module behind the Main Power Supply Module in the ON position.

6.

If the RFL 9745 is equipped with a redundant power supply, place the POWER switch on the Power Supply I/O Module behind the Redundant Power Supply Module in the ON position.

RFL 9745 February 24, 2009

8-9

RFL Electronics Inc. (973) 334-3100