Instruction Manual RFL 9745 Teleprotection Channel: Section 7. USING THE 9745 FRONT-PANEL CONTROLS, pages 290 to 297

Pages 290 to 297 of 394, from Instruction Manual RFL 9745 Teleprotection Channel

The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the RFL RFL-9745

Page 290

OUT FAIL 3B OUT SHORT 3B

I I

Indicates whether Output 3B has failed or is shorted ("I" for inactive, "A" for active).

OUT FAIL 4B OUT SHORT 4B

I I

Indicates whether Output 4B has failed or is shorted ("I" for inactive, "A" for active).

7.5.7 LEVELS MENU (For Digital System) The following entries appear as items on the front-panel LEVELS menu. Press the LEVELS button to view the first entry. Then press the DOWN button to scroll down the LEVELS menu list.

APRIL BAUD RATE 19200

Indicates the selected April baud rate. See section 7.5.3 for instructions on how to change the baud rate.

CHANNEL DELAY TX 0 MS

Indicates the current transmit channel delay in milliseconds.

CHANNEL DELAY RX 0 MS

Indicates the current receive channel delay in milliseconds.

7.5.8 LOG MENU (For Digital System) The following entries appear as items on the front-panel LOG menu. Press the LOG button to view the first entry. Then press the DOWN button to scroll down the LOG menu list. TX FUNCTION 1 xxx

Indicates how many times Transmitted Function 1 has been active since the last system reset.

TX FUNCTION 2 xxx

Indicates how many times Transmitted Function 2 has been active since the last system reset.

TX FUNCTION 3 xxx

Indicates how many times Transmitted Function 3 has been active since the last system reset.

RFL 9745 October 15, 2002

7 - 21

RFL Electronics Inc. (973) 334-3100

Page 291

TX FUNCTION 4 xxx

Indicates how many times Transmitted Function 4 has been active since the last system reset.

TX FUNCTION 5 xxx

Indicates how many times Transmitted Function 5 has been active since the last system reset.

TX FUNCTION 6 xxx

Indicates how many times Transmitted Function 6 has been active since the last system reset.

TX FUNCTION 7 xxx

Indicates how many times Transmitted Function 7 has been active since the last system reset.

RX FUNCTION 1 xxx

Indicates how many times Received Function 1 has been active since the last system reset.

RX FUNCTION 2 xxx

Indicates how many times Received Function 2 has been active since the last system reset.

RX FUNCTION 3 xxx

Indicates how many times Received Function 3 has been active since the last system reset.

RX FUNCTION 4 xxx

Indicates how many times Received Function 4 has been active since the last system reset.

RX FUNCTION 5 xxx

Indicates how many times Received Function 5 has been active since the last system reset.

RX FUNCTION 6 xxx

Indicates how many times Received Function 6 has been active since the last system reset.

RX FUNCTION 7 xxx

Indicates how many times Received Function 7 has been active since the last system reset.

RFL 9745 October 15, 2002

7 - 22

RFL Electronics Inc. (973) 334-3100

Page 292

KEY FNT 1 (or user text) xxx

Indicates how many times Input 1A has been active since the last system reset.

KEY FNT 3 (or user text) xxx

Indicates how many times Input 1B has been active since the last system reset.

KEY FNT 1 (or user text) xxx

Indicates how many times Input 2A has been active since the last system reset.

KEY FNT 3 (or user text) xxx

Indicates how many times Input 2B has been active since the last system reset.

KEY FNT 2 (or user text) xxx

Indicates how many times Input 3A has been active since the last system reset.

KEY FNT 4 (or user text) xxx

Indicates how many times Input 3B has been active since the last system reset.

KEY FNT 2 (or user text) xxx

Indicates how many times Input 4A has been active since the last system reset.

KEY FNT 4 (or user text) xxx

Indicates how many times Input 4B has been active since the last system reset.

GUARD FNT 1 (or user text) xxx

Indicates how many times Output 1A has been active since the last system reset.

GUARD FNT 3 (or user text) xxx

Indicates how many times Output 1B has been active since the last system reset.

TRIP FNT 1 (or user text) xxx

Indicates how many times Output 2A has been active since the last system reset.

RFL 9745 October 15, 2002

7 - 23

RFL Electronics Inc. (973) 334-3100

Page 293

TRIP FNT 3 (or user text) xxx

Indicates how many times Output 2B has been active since the last system reset.

GUARD FNT 2 (or user text) xxx

Indicates how many times Output 3A has been active since the last system reset.

GUARD FNT 4 (or user text) xxx

Indicates how many times Output 3B has been active since the last system reset.

TRIP FNT 2 (or user text) xxx

Indicates how many times Output 4A has been active since the last system reset.

TRIP FNT 4 (or user text) xxx

Indicates how many times Output 4B has been active since the last system reset.

COMMS WARNING (or user text) xxx

Indicates how many times Annunciator Output 1A has been active since the last system reset.

COMMS ALARM (or user text) xxx

Indicates how many times Annunciator Output 1B has been active since the last system reset.

OUTPUT ALARM (or user text) xxx

Indicates how many times Annunciator Output 2A has been active since the last system reset.

HARDWARE WARNING (or user text) Indicates how many times Annunciator Output 2B has xxx been active since the last system reset.

NOT USED (or user text) xxx

Indicates how many times Annunciator Output 3A has been active since the last system reset.

HARDWARE ALARM (or user text) xxx

Indicates how many times Annunciator Output 3B has been active since the last system reset.

RFL 9745 October 15, 2002

7 - 24

RFL Electronics Inc. (973) 334-3100

Page 294

LAST RESET MM/DD/YY,HH:MM

Indicates the date (month, day and year), and time (hour and minute) of the last reset.

CUM OUTAGE TIME HH:MM:SS or #Days,#Hrs

Indicates how long the cumulative outage timer has run since the last reset. If the Cumulative Outage Time is less than one day, the format is hours, minutes and seconds; If greater than one day the format is days and hours.

RESET

Enables the user to reset the counters and LEDs from the front panel. Press ENTER when this is displayed to initiate the resetting of these items. Then select YES(Y), or NO(N) using the UP or DOWN buttons. Press the ENTER button to execute the reset.

7.5.9 TEST MENU (For Digital System) The following entries appear as items on the front-panel TEST menu. Press the TEST button to view the first entry. Then press the DOWN button to scroll down the TEST menu list.

TESTS RUN xxx

Indicates the number of tests run since last reset.

TIME BETWEEN HH:MM

Indicates the amount of time between automatic tests. The format is hours and minutes.

TESTS PASSED xxx

Indicates the number of autotests passed since last reset.

TESTS FAILED xxx

Indicates the number of autotests failed since last reset.

NEXT TEST START HH:MM

Indicates the amount of time until the next automatic test.

AVG. BER

Indicates the average Bit Error Rate.

RFL 9745 October 15, 2002

7 - 25

RFL Electronics Inc. (973) 334-3100

Page 295

WORD ERRORS

Indicates the number of Word Errors received since the last reset.

CLOCK ERRORS

Indicates the number of Clock Errors received since the last reset.

FRAME ERRORS

Indicates the number of Frame Errors received since the last reset.

MINOR DATA ERROR

Indicates the number of Minor Data Errors received since the last reset.

MAJOR DATA ERROR

Indicates the number of Major Data Errors received since the last reset.

FUNCTION 1 TEST

Allows the user to override Function 1 as specified in the logic table. Press ENTER, then use the UP and DOWN buttons to select active or inactive. ("I" for inactive, "A" for active).

FUNCTION 2 TEST

Allows the user to override Function 1 as specified in the logic table. Press ENTER, then use the UP and DOWN buttons to select active or inactive. ("I" for inactive, "A" for active).

FUNCTION 3 TEST

Allows the user to override Function 1 as specified in the logic table. Press ENTER, then use the UP and DOWN buttons to select active or inactive.("I" for inactive, "A" for active).

FUNCTION 4 TEST

Allows the user to override Function 1 as specified in the logic table. Press ENTER, then use the UP and DOWN buttons to select active or inactive.("I" for inactive, "A" for active).

FUNCTION 5 TEST

Allows the user to override Function 1 as specified in the logic table. Press ENTER, then use the UP and DOWN buttons to select active or inactive.("I" for inactive, "A" for active). Allows the user to override Function 1 as specified in the logic table. Press ENTER, then use the UP and DOWN buttons to select active or inactive.("I" for inactive, "A" for active).

FUNCTION 6 TEST

FUNCTION 7 TEST

RFL 9745 October 15, 2002

Allows the user to override Function 1 as specified in the logic table. Press ENTER, then use the UP and DOWN buttons to select active or inactive.("I" for inactive, "A" for active).

7 - 26

RFL Electronics Inc. (973) 334-3100

Page 296

CHECKBACK TEST This allows the user to initiate a Checkback Test to confirm the presence of a remote unit. Press the ENTER button to run the test and view the results.

PING PONG

This allows the user to initiate a Ping Pong test to measure the channel delay. Press the ENTER button to run the test and view the results.

CLOCK SOURCE

Use the ENTER button to select Enabled or Disabled. When “Enabled” is selected, causes the internal 9745 clock to be active. When “Disabled” is selected, causes the internal 9745 clock to be inactive. This parameter is valid only when the RS449 board is installed.

LOCAL LOOPBACK

Allows the user to activate internal relays to connect the transmitter output to the receiver input, to facilitate off-line testing of the RFL 9745. Press the ENTER button to toggle the selection from Enabled to Disabled. Only the RS449 and G.703 boards support this function.

RFL 9745 October 15, 2002

7 - 27

RFL Electronics Inc. (973) 334-3100

Page 297

7.6 SHORT HAUL FIBER I/O MODULE FRONT PANEL INDICATORS The Short Haul FIO module is used to enable the RFL 9745 to communicate with a remote RS-449 port using dual fiber cables in conjunction with the fiber service unit. The Short Haul FIO module front panel is shown in Figure 7-2, and its connectors and indicators are described in Table 7-4.

FIBER DATA TX

RCV 105065-4

SHORT HAUL FIO

Figure 7-2. Short Haul FIO front panel Table 7-4. Connectors and Indicators, Short Haul FIO module

Name/Description TX RCV FIBER DATA LED (green)

Function Type ST bayonet connector for fiber optic transmitter Type ST bayonet connector for fiber optic receiver When the green FIBER DATA LED is “on”, the Short Haul FIO is receiving data from the FIBER SERVICE UNIT.

7.7 FIBER SERVICE UNIT FRONT AND REAR PANEL INDICATORS Refer to Fiber Service Unit Instruction Data Sheet (publication number: ID C37.94FSU) for information on FSU front and rear panel indicators and installation instructions.

RFL 9745 October 15, 2002

7 - 28