Page 280
FM NOISE CH4 LOW SNR CH4
I I
Indicates the status of Channel 4's FM noise and SNR alarms ("I" for inactive, "A" for active).
BUS ERROR RS232 ACT
I I
Indicates whether a bus error has occurred, or if there is activity on the RS-232 bus ("I" for inactive, "A" for active).
PS FAIL L PS FAIL R
I I
Indicates whether a failure has been detected in either of the RFL 9745's power supply modules ("I" for inactive, "A" for active).
BATTERY LOW
I
Not used on units with capacitor backed RAM.
OUT FAIL 1A OUT SHORT 1A
I I
Indicates whether Output 1A has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 2A OUT SHORT 2A
I I
Indicates whether Output 2A has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 3A OUT SHORT 3A
I I
Indicates whether Output 3A has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 4A OUT SHORT 4A
I I
Indicates whether Output 4A has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 1B OUT SHORT 1B
I I
Indicates whether Output 1B has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 2B OUT SHORT 2B
I I
Indicates whether Output 2B has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 3B OUT SHORT 3B
I I
Indicates whether Output 3B has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 4B OUT SHORT 4B
I I
Indicates whether Output 4B has failed or is shorted ("I" for inactive, "A" for active).
RFL 9745 October 15, 2002
7 - 11
RFL Electronics Inc. (973) 334-3100
Page 281
7.5.3 LEVELS MENU (For Audio System) The following entries appear as items on the front-panel LEVELS menu. Press the LEVELS button to view the first entry. Then press the DOWN button to scroll down the LEVELS menu list. TRANSMIT 1 xx dBm
TRANSMIT 2 xx dBm
These four items show what transmitter output levels, channels 1, 2, 3 and 4 are set to; where xx= the output power level setting in dBm . These level settings can be changed via the front panel. To change the transmit output level proceed as follows: 1.
TRANSMIT 3 xx dBm
TRANSMIT 4 xx dBm
Press the Enter switch to enter the edit mode. A flashing cursor will appear on the bottom line of the display next to the item value.
2.
Press the UP or DOWN switches until the desired transmit level is displayed on the bottom line of the display.
3.
Press the ENTER switch to store the new transmit level. The new transmit level will not change until the ENTER switch is pressed.
4.
Press the DOWN switch to go to the next item on the LEVELS menu.
NOTE These are not actual readings of output levels. Their purpose is to show what the levels are set to. When changing transmit levels for audio channels via the front panel, a TX function LED may momentarily light. This does not indicate a transmit function but rather a reconfiguration of the DSP logic which squelches the transmitter. RECEIVE 1 xx dBm
These four items show Channel 1, 2, 3 and 4 receiver input levels, where xx=the input power level in dBm.
RECEIVE 2 xx dBm RECEIVE 3 xx dBm RECEIVE 4 xx dBm
RFL 9745 October 15, 2002
7 - 12
RFL Electronics Inc. (973) 334-3100
Page 282
CHANNEL DELAY TX 0 MS
Indicates the current transmitted channel delay in milliseconds, based on the last ping pong test.
CHANNEL DELAY RX 0 MS
Indicates the current received channel delay in milliseconds, based on the last ping pong test.
APRIL BAUD RATE 9600
Indicates the current baud rate setting for the RFL 9745’s RS-232 ports. To change the baud rate proceed as follows: 1.
Press the Enter switch to enter the edit mode. A flashing cursor will appear on the bottom line of the display, next to the item value.
2.
Press the UP or DOWN switches until the desired baud rate is displayed on the bottom line of the display.
3.
Press the ENTER switch to store the new baud rate.
4.
Press the DOWN switch to go to the next item on the LEVELS menu.
7.5.4 LOG MENU (For Audio System) The following entries appear as items on the front-panel LOG menu. Press the LOG button to view the first entry. Then press the DOWN button to scroll down the LOG menu list. The term “or user text” indicates that the user has the option of inserting his own names in place of the various input, output, annunciator output, and status output names shown on line one of the front panel display, by using the Alarm and I/O Name Menu as described in Section 6.
TX FUNCTION 1 xxx
Indicates how many times the Channel 1 transmitter has been active since the last system reset.
RX FUNCTION 1 HIGH xxx
Indicates how many times the Channel 1 receiver has received its high frequency tone since the last system reset.
RX FUNCTION 1 LOW xxx
Indicates how many times the Channel 1 receiver has received its low frequency tone since the last system reset.
RFL 9745 October 15, 2002
7 - 13
RFL Electronics Inc. (973) 334-3100
Page 283
TX FUNCTION 2 xxx
Indicates how many times the Channel 2 transmitter has been active since the last system reset.
RX FUNCTION 2 HIGH xxx
Indicates how many times the Channel 2 receiver has received its high frequency tone since the last system reset.
RX FUNCTION 2 LOW xxx
Indicates how many times the Channel 2 receiver has received its low frequency tone since the last system reset.
TX FUNCTION 3 xxx
Indicates how many times the Channel 3 transmitter has been active since the last system reset.
RX FUNCTION 3 HIGH xxx
Indicates how many times the Channel 3 receiver has received its high frequency tone since the last system reset.
RX FUNCTION 3 LOW xxx
Indicates how many times the Channel 3 receiver has received its low frequency tone since the last system reset.
TX FUNCTION 4 xxx
Indicates how many times the Channel 4 transmitter has been active since the last system reset.
RX FUNCTION 4 HIGH xxx
Indicates how many times the Channel 4 receiver has received its high frequency tone since the last system reset.
RX FUNCTION 4 LOW xxx
Indicates how many times the Channel 4 receiver has received its low frequency tone since the last system reset.
INPUT 1A (or user text) xxx
Indicates how many times Input 1A has been active since the last system reset.
INPUT 1B (or user text) xxx
Indicates how many times Input 1B has been active since the last system reset.
INPUT 2A (or user text) xxx
Indicates how many times Input 2A has been active since the last system reset.
RFL 9745 October 15, 2002
7 - 14
RFL Electronics Inc. (973) 334-3100
Page 284
INPUT 2B (or user text) xxx
Indicates how many times Input 2B has been active since the last system reset.
INPUT 3A (or user text) xxx
Indicates how many times Input 3A has been active since the last system reset.
INPUT 3B (or user text) xxx
Indicates how many times Input 3B has been active since the last system reset.
INPUT 4A (or user text) xxx
Indicates how many times Input 4A has been active since the last system reset.
INPUT 4B (or user text) xxx
Indicates how many times Input 4B has been active since the last system reset.
OUTPUT 1A (or user text) Indicates how many times Output 1A has been active since the last xxx system reset.
OUTPUT 1B (or user text) Indicates how many times Output 1B has been active since the last xxx system reset.
OUTPUT 2A (or user text) Indicates how many times Output 2A has been active since the last xxx system reset.
OUTPUT 2B (or user text) Indicates how many times Output 2B has been active since the last xxx system reset.
OUTPUT 3A (or user text) Indicates how many times Output 3A has been active since the last xxx system reset.
OUTPUT 3B (or user text) Indicates how many times Output 3B has been active since the last xxx system reset.
OUTPUT 4A (or user text) Indicates how many times Output 4A has been active since the last xxx system reset.
RFL 9745 October 15, 2002
7 - 15
RFL Electronics Inc. (973) 334-3100
Page 285
OUTPUT 4B (or user text) Indicates how many times Output 4B has been active since the last system reset. ANNUNC 1A (or user text) Indicates how many times Annunciator Output 1A has been active since xxx the last system reset.
ANNUNC 1B (or user text) Indicates how many times Annunciator Output 1B has been active since xxx the last system reset.
ANNUNC 2A (or user text) Indicates how many times Annunciator Output 2A has been active since xxx the last system reset.
ANNUNC 2B (or user text) Indicates how many times Annunciator Output 2B has been active since xxx the last system reset.
ANNUNC 3A (or user text) Indicates how many times Annunciator Output 3A has been active since xxx the last system reset.
ANNUNC 3B (or user text) Indicates how many times Annunciator Output 3B has been active since xxx the last system reset.
STATUS 1 (or user text) xxx
Indicates how many times Status Output 1 has been active since the last system reset. (Only displayed on units equipped with the optional Status Output Module.)
STATUS 2 (or user text) xxx
Indicates how many times Status Output 2 has been active since the last system reset. (Only displayed on units equipped with the optional Status Output Module.)
STATUS 3 (or user text) xxx
Indicates how many times Status Output 3 has been active since the last system reset. (Only displayed on units equipped with the optional Status Output Module.)
STATUS 4 (or user text) xxx
Indicates how many times Status Output 4 has been active since the last system reset. (Only displayed on units equipped with the optional Status Output Module.)
RFL 9745 October 15, 2002
7 - 16
RFL Electronics Inc. (973) 334-3100
Page 286
STATUS 5 (or user text) xxx
Indicates how many times Status Output 5 has been active since the last system reset. (Only displayed on units equipped with the optional Status Output Module.)
STATUS 6 (or user text) xxx
Indicates how many times Status Output 6 has been active since the last system reset. (Only displayed on units equipped with the optional Status Output Module.)
LAST RESET MM/DD HH:MM:SS
Indicates the date and time of last reset.
CUM OUTAGE TIME
Indicates how long the cumulative outage timer has been active since the last reset.
RESET
This enables you to reset the counters and LEDs from the front panel. To RESET the log counters from the front panel proceed as follows: 1. On the front panel press “LOG”, then press “UP” to access “RESET”. 2. Press “ENTER”, “UP” and “ENTER” to reset the log counters.
RFL 9745 October 15, 2002
7 - 17
RFL Electronics Inc. (973) 334-3100
Page 287
7.5.5 TEST MENU (For Audio System) The following entries appear as items on the front-panel TEST menu. Press the TEST button to view the first entry. Then press the DOWN button to scroll down the TEST menu list. TESTS RUN xxx
The number of autotests run since the last reset.
TIME BETWEEN xxx
The amount of time between autotests.
TESTS PASSED xxx
The number of autotests passed since the last reset.
TESTS FAILED xxx
The number of autotests failed since the last reset.
NEXT TEST START xxx
The amount of time until the next autotest.
CHANNEL 1 SHIFT
This causes the channel 1 transmitter to shift its frequency. This can be done from the front panel only if front panel testing is enabled. (See paragraph 6.11.3).
CHANNEL 2 SHIFT
This causes the channel 2 transmitter to shift its frequency. This can be done from the front panel only if front panel testing is enabled. (See paragraph 6.11.3).
CHANNEL 3 SHIFT
This causes the channel 3 transmitter to shift its frequency. This can be done from the front panel only if front panel testing is enabled. (See paragraph 6.11.3).
CHANNEL 4 SHIFT
This causes the channel 4 transmitter to shift its frequency. This can be done from the front panel only if front panel testing is enabled. (See paragraph 6.11.3). To shift a channel frequency proceed as follows: 1.
Press the ENTER switch to enter the edit mode. A flashing cursor will appear on the bottom line of the display, next to the item value.
RFL 9745 October 15, 2002
2.
Press the UP or DOWN switches until the desired shift is displayed (LOW or HIGH).
3.
After frequency shift tests are completed, press the ENTER switch to restore the unit to normal operation.
7 - 18
RFL Electronics Inc. (973) 334-3100
Page 288
CHECKBACK AND ADDRESS TEST
This allows the user to execute a Checkback and Address Test (This is also referred to as Autotest). Press the ENTER button to run the test and view the results. This selection will appear only if channel one is configured as a modem.
PING PONG
This allows the user to execute a Ping Pong Test to measure the channel delay. Press the ENTER button to run the test and view the results. This selection will appear only if channel one is configured as a modem.
AUTOTEST
This causes the unit to execute an RFL 6750 autotest. This selection will appear only if channel one is configured as a 6750 modem.
The contents of the front panel menus for the digital system are shown in the following sections.
7.5.6 STATUS MENU (For Digital System) The following entries appear as items on the front-panel STATUS menu. Press the STATUS button to view the first entry. Then press the DOWN button to scroll down the STATUS menu list.
RX FUNCTION 1 RX FUNCTION 2
I I
Indicates whether Receive Function 1 or Receive Function 2 is active or inactive ("I" for inactive, "A" for active).
RX FUNCTION 3 RX FUNCTION 4
I I
Indicates whether Receive Function 3 or Receive Function 4 is active or inactive ("I" for inactive, "A" for active).
RX FUNCTION 5 RX FUNCTION 6
I I
Indicates whether Receive Function 5 or Receive Function 6 is active or inactive ("I" for inactive, "A" for active).
RX FUNCTION 7 TX FUNCTION 1
I I
Indicates whether Receive Function 7 or Transmit Function 1 is active or inactive ("I" for inactive, "A" for active).
TX FUNCTION 2 TX FUNCTION 3
I I
Indicates whether Transmit Function 2 or Transmit Function 3 is active or inactive ("I" for inactive, "A" for active).
TX FUNCTION 4 TX FUNCTION 5
I I
Indicates whether Transmit Function 4 or Transmit Function 5 is active or inactive ("I" for inactive, "A" for active).
RFL 9745 October 15, 2002
7 - 19
RFL Electronics Inc. (973) 334-3100
Page 289
TX FUNCTION 6 TX FUNCTION 7
I I
Indicates whether Transmit Function 6 or Transmit Function 7 is active or inactive ("I" for inactive, "A" for active).
CLOCK ERRORS A FRAME ERRORS I
Clock errors are active when the variation in the received word exceeds the min/max frequency limits of the max jitter setting. Frame errors are active when the receiver has lost sync. ("I" for inactive, "A" for active).
MINOR DATA ERROR MAJOR DATA ERROR
I I
Indicates whether the number of Minor Data Error bits or Major Data Error bits have exceeded the user defined settings. ("I" for inactive, "A" for active).
TRANSMIT FAIL
I
Indicates whether the fiber optic emitter has failed ("I" for inactive [emitter has not failed], "A" for active[emitter has failed] ).
BUS ERROR RS232 ACT
I I
Indicates whether a bus error has occurred, or if there is activity on the RS-232 bus ("I" for inactive, "A" for active).
PS FAIL L PS FAIL R
I I
Indicates whether a failure has been detected in either the left or right 9745 power supply module ("I" for inactive, "A" for active).
BATTERY LOW
I
Not used on units with capacitor backed RAM.
OUT FAIL 1A OUT SHORT 1A
I I
Indicates whether Output 1A has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 2A OUT SHORT 2A
I I
Indicates whether Output 2A has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 3A OUT SHORT 3A
I I
Indicates whether Output 3A has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 4A OUT SHORT 4A
I I
Indicates whether Output 4A has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 1B OUT SHORT 1B
I I
Indicates whether Output 1B has failed or is shorted ("I" for inactive, "A" for active).
OUT FAIL 2B OUT SHORT 2B
I I
Indicates whether Output 2B has failed or is shorted ("I" for inactive, "A" for active).
RFL 9745 October 15, 2002
7 - 20
RFL Electronics Inc. (973) 334-3100