013 - Run Auto Test (Checkback) Select this item to initiate an automatic checkback test. This test cannot be run in an audio system unless channel one is configured as a modem. In addition to this, test parameter 7 must be enabled.

014 - Run Ping Pong Test

Select this item to immediately run a ping-pong test. This test cannot be run in an audio system unless channel one is configured as a modem. Test parameter 7 does not have to be enabled to run this test.

015 - Reset Log

Select this item to reset the test log. When you do, the following prompt appears: Are you sure? [Yes,No] To answer "yes," press the [Y] key. The test log will be reset, and all tallies will return to zero. If you decide you don't want to reset the test log, press the [N] key. All tallies will remain as they are, and the following message will appear: Reset Log Cancelled

016 - Internal Clock Source

Select this item to connect the 9745 to its internal clock.

017 - Local Loopback

Select this item to connect the transmit output to the receive input, to allow testing of the 9745 off line. Only the RS449 and G.703 boards support this function.

NOTE 1. On a digital system, if the unit is powered ON and the AUTO TEST is enabled but Parameter 008 is set to 0:00 time between tests, the system needs a Manual Checkback to clear the alarm.

RFL 9745 September 20, 2007

6 - 61

RFL Electronics Inc. (973) 334-3100

Page 251

6.12 THE UPDATE MODE The update mode places a display on your terminal that is updated approximately every five seconds to show up-to-date information about RFL 9745 operation. This mode is entered by using the "U" command. 9745>U [ENTER] When the "U" command is entered, the screen on your terminal will be cleared, and replaced by the UPDATE screen shown in Figures 6-26 or 6-27 as applicable. This is a display of all the measured parameter values. The displayed values are updated about once a second when operating at 2400 baud. This screen can be used to monitor RFL 9745 operation. The update display shows the parameter numbers for each item, a brief description of its meaning, and its status. “I” indicates that the parameter is “inactive”. “A” indicates that the parameter is “active”. To exit the update mode, press the [X] key, followed by the [ENTER] key. The screen on your terminal will be cleared, and the "9745>" prompt will re-appear.

Value Update - Type 'X<CR>' to Stop

140 142 144 154 155 156 157 158 159 160 161 170 171 172 173 174

Tx Chan Delay Rx Chan Delay Cum Outage Time Input 1A Input 1B Input 2A Input 2B Input 3A Input 3B Input 4A Input 4B Rcvd Signal Lvl Tx Function Tx Squelch Rx High Freq Rx Low Freq

0.0 ms 141 Next Auto Test N/A 0.0 ms 143 Last Reset Date 09:42:58 03/03/94 01:01:37.196 145 Current Time 09:46:53 03/15/94 I 21 162 Output 1A I 277 I 6 163 Output 1B I 250 I 61 164 Output 2A I 259 I 4 165 Output 2B I 232 I 14 166 Output 3A I 292 I 12 167 Output 3B I 525 I 7 168 Output 4A I 1 I 3 169 Output 4B I 0 -26 N/A -27 -27 dBm I I I A I A I I I I I I I I I I

Figure 6-26. Typical UPDATE screen for the Audio System

RFL 9745 September 20, 2007

6 - 62

RFL Electronics Inc. (973) 334-3100

Page 252

Value Update - Type 'X<CR>' to Stop 140 Tx Chan Delay 127.5 ms 142 Rx Chan Delay 127.5ms 144 Cum Outage Time 00:00:00.000 146 Data Rate 0 147 Bit Error Rate N/A 149 Clock Errors 0 151 Minor Data Error 0 154 Input 1A I 0 155 Input 1B I 0 156 Input 2A I 0 157 Input 2B I 0 158 Input 3A I 0 159 Input 3B I 0 160 Input 4A I 0 161 Input 4B I 0 175 Rx Function SQ I I 176 Tx Function I A A

141 Next Auto Test 143 Last Reset Date 145 Current Time

N/A 23:41:08 01/11/99 23:41:16 01/11/99

148 Word Errors 150 Frame Errors 152 Major Data Error 162 Output 1A 163 Output 1B 164 Output 2A 165 Output 2B 166 Output 3A 167 Output 3B 168 Output 4A 169 Output 4B SQ I I I I A

0 0 0 I I I I I I I I I A

0 0 0 0 0 0 0 0

Figure 6-27. Typical UPDATE screen for the Digital System

If the update screen does not display the parameters as shown in Figures 6-26 or 6-27, or displays the information erratically, your dumb terminal must be set up for VT100 emulation or the CONFIG.SYS file of your PC must be edited to recognize ANSI.SYS. If you have a PC running PC_APRIL, ANSI.SYS needs to be installed to emulate VT100. To do this proceed as follows: 1. Press X [ENTER] to stop the update mode. 2. Type in DDD to get out of windows mode.

RFL 9745 September 20, 2007

6 - 63

RFL Electronics Inc. (973) 334-3100

Page 253

4. At C:\ type EDIT CONFIG.SYS 5. Under the last device line add the following: DEVICE=C:\DOS\ANSI.SYS 6. Click on FILE, then click on SAVE. 7. Click on FILE again, then click on EXIT. 8. Reboot the computer. 9. Go back into PC_APRIL. 10. Enter the Update Mode. 11. This will correct the erratic display.

6.12.1 WINDOWS 95/98 SETUP FOR USE WITH RFL 9745 PC_APRIL SOFTWARE. 1.

From Windows 95/98, open a DOS shell (double-click on MSDOS icon).

2.

From the “C:\” prompt, check for the existence of a file april.bat. If it exists, type del april.bat.

3.

From the “C:\” prompt, type edit config.sys.

4.

After the last DEVICE line add the following line: DEVICE=C:\WINDOWS\COMMAND\ANSI.SYS

5.

Save the file and exit from the Editor.

6.

At the “C:\” prompt, make a directory called \april. (example: md\april)

7.

Enter the April directory (example: cd \april).

8.

Once in the april directory, copy the PC_APRIL software from the RFL supplied diskette into the april directory.

9.

Remain in the april directory and type edit.

RFL 9745 September 20, 2007

6 - 64

RFL Electronics Inc. (973) 334-3100

Page 254

10.

The Editor will allow the creation of batch files that will directly correlate to the Comm port and baud rate previously set from the controls on the front panel of the RFL 9745.

11.

The following command would be entered if Comm 2 and baud rate of 9600 was used: pc_april /c2 /b9600

12.

When finished entering information, save the file as c2b9600.bat.

13.

Another batch file can be created using a different Comm port or baud rate.

14.

Exit the Editor. At the “C:\” prompt, type exit.

15.

The computer must be rebooted in order to acknowledge the change made to the config.sys file.

16

After Windows 95 has been rebooted, click on the right mouse button from the Windows 95 “desktop”. From the menu that appears, select new, then select shortcut.

17.

In the space provided, type the following: c:\april.

18.

Click on next.

19.

Select a name for the shortcut (can be any name).

20.

Click on finish.

21.

Click on the folder icon that was just created, then click on the Batch file associated with the desired Comm port and baud rate for use with PC_April. Example: c2b9600

22.

PC April should now be functioning normally.

23.

To exit PC_April, type Z and Enter key at the 9745 prompt. Example: 9745>Z

24.

Manually close the MSDOS window using standard Win95/98 methodology.

NOTE For Windows NT systems: Device = C:\windows\system32\ANSI.sys

RFL 9745 September 20, 2007

6 - 65

RFL Electronics Inc. (973) 334-3100

Page 255

6.13 THE SEQUENCE-OF-EVENTS MODE The sequence-of-events log is a data file that keeps track of every time one of the RFL 9745's inputs or outputs changes state, and the conditions that existed at that time. The sequence-of-events log is capacitor backed and can store up to 100 records. To view the sequence-of-events log, use the "S" command: 9745>S [ENTER] When you use the "S" command, a sequence-of-events menu similar to the one shown in Figure 6-28 will appear.

H - Display sequence of events help A - Toggle Labels On Event Display, Currently = Default Labels D - Dump All Events To Port E - See Directory of Events L - Toggle Level of Event Triggers, Currently = Level One R - Reset All Events Q - Leave Sequence of Events Menu ## - View this Sequence of Events Record 9745-S> Figure 6-28. Typical sequence-of-events menu for the Audio or Digital System

You are now in the sequence-of-events mode, as indicated by the "!9745-S>" prompt on your screen. You may now use the sequence-of-events commands to view the contents of the sequence-of-events log, toggle the event displays and event triggers, or reset the sequence-of-events log. For more information on each sequence-of-events command, refer to the paragraph numbers listed below. Command

Meaning

H

Display sequence-of-events help

.

.

.

.

6.13.1

A

Toggle Labels On Event Display

.

.

.

.

6.13.2

D

Dump All Events To Port

.

.

.

.

.

6.13.3

E

See Directory Of Events

.

.

.

.

.

6.13.4

L

Toggle Level Of Event Triggers

.

.

.

.

6.13.5

R

Reset All Events

.

.

.

.

6.13.6

Q

Leave Sequence-of-Events menu

.

.

.

.

6.13.7

##

View an event record .

.

.

.

.

6.13.8

RFL 9745 September 20, 2007

Paragraph

.

.

.

6 - 66

RFL Electronics Inc. (973) 334-3100

Page 256

6.13.1 DISPLAYING SEQUENCE-OF-EVENTS HELP Any time you need to see a list of all the sequence-of-events menu commands, use the "H" command. 9745-S>H [ENTER] When you invoke the "H" command, the sequence-of-events menu shown in Figure 6-27 will re-appear on your screen.

6.13.2 SELECTING LABELS ON EVENT DISPLAY To determine how events will be labeled in the sequence-of-events log, use the "A" command: 9745-S>A [ENTER] Each time you invoke the "A" command, the parts of the sequence-of-events log that have userprogrammable labels will toggle between the factory-default labels and the labels that were programmed using the procedures in Section 6.10.2 of this manual.

6.13.3 DUMPING THE SEQUENCE-OF-EVENTS LOG TO A PC I/O PORT (PRINTER PORT) To transfer the event records in the sequence-of-events log from the RFL 9745 to your terminal or PC, use the "D" command: 9745-S>D [ENTER] When you invoke the "D" command, each record will appear as ASCII text on your screen as it is being transferred. When all the events have been dumped, the "9745-S>" prompt will re-appear on your screen.

6.13.4 VIEWING THE DIRECTORY OF EVENTS To view a list of the events presently stored in the sequence-of-events log, use the "E" command: 9745-S>E [ENTER] When you invoke the "E" command, a Directory Of Events similar to the one shown in Figure 6-29 will appear. The Directory Of Events lists each record in the sequence-of-events log, along with the date and time it occurred. It also lists which input changed state to trigger the event, and the state the input shifted to at the time of the event. More information about the Directory Of Events can be found in paragraphs 6.13.5 through 6.13.8.

RFL 9745 September 20, 2007

6 - 67

RFL Electronics Inc. (973) 334-3100

Page 257

040 039 038 037 036 035 034 033 032 031 030 029 028 027 026 025 024 023 022 021 020 019 018 017 016 015 014 013 012 011 010 009 008 007 006 005 004 003 002 001 9745-S>

08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94 08/09/94

13:47:09.735 13:47:09.734 13:45:05:755 13:44:17:859 13:44:17:858 13:40:01:918 13:40:01:917 13:37:55:852 13:37:55:851 13:23:21.009 13:20:55.076 13:20:53.915 13:20:53.396 13:20:53.228 13:20:52.802 13:20:52.481 13:20:52.292 13:20:52.059 13:20:51.856 13:20:51.460 13:20:50.562 13:20:50.355 13:20:49.704 13:20:49.652 13:20:49.650 13:20:49.629 13:20:49.627 13:20:49.441 13:20:49.390 13:20:49.383 13:20:49.199 13:20:49.147 13:20:49.145 13:20:49.123 13:20:48.960 13:20:48.909 13:20:48.903 13:20:48.901 13:15:14.938 13:15:05.005

Rx Freq High Ch2 Rx Freq High Ch2 RS232 active Rx Freq High Ch2 Rx Freq High Ch2 Rx Freq High Ch2 Rx Freq High Ch2 Rx Freq High Ch2 Rx Freq High Ch2 RS232 active Input 1A Input 2A Input 2A Input 1A Input 2A Input 2A Input 2A Input 2A Input 2A Input 2A Input 3B Input 3B Fail to trip 1B Output 3B Output 1B Rx Freq Low Ch2 Rx Freq High Ch2 Fail to trip 1B Output 3B Output 1B Fail to trip 1B Output 3B Output 1B Rx Freq High Ch2 Fail to trip 1B Output 3B Rx Freq High Ch4 Rx Freq High Ch3 RS232 active RS232 active

Inactive Active Active Inactive Active Inactive Active Inactive Active Inactive Inactive Inactive Active Active Inactive Active Inactive Active Inactive Active Inactive Active Active Inactive Active Active Inactive Inactive Active Inactive Active Inactive Active Inactive Inactive Active Active Inactive Active Inactive

Figure 6-29. Typical Directory of Events for the Audio System

NOTE If the same event trigger changes state within 0-3 ms, the first event may not be recorded in a Sequence Of Events record. Trip Logic events are always acted upon by the 9745 logic co-processor even though the recording of the event may not be in the Sequence Of Events record.

RFL 9745 September 20, 2007

6 - 68

RFL Electronics Inc. (973) 334-3100

Page 258

6.13.5 SELECTING LEVELS FOR EVENT TRIGGERS To determine the levels that will trigger an event in the sequence-of-events log, use the "L" command: 9745-S>L [ENTER] Each time you invoke the "L" command, the trigger levels will toggle between their Level 1 and Level Two values. As shown in the tables below Level 1 has four event triggers, Level 2 Analog has 27 event triggers, and Level 2 Digital has 31 event triggers. When the SOE is set to Level 2 the event log will fill up much faster than if the SOE was set to Level 1. This is because Level has more event triggers. If your system has flasher logic, the increased activity tends to fill up the SOE log very fast. Systems that are inherently noisy have the same effect. For these situations you may want to set the SOE to Level 1. Level 2 is normally used for troubleshooting intermittent problems or for normal system monitoring. Level 2 will record noise events as the occur. Level 1 will record noise events only if they trigger an alarm. In Level 1 you will know that an alarm has occurred but you will not know what events led up to it.

6.13.5.1 LEVEL 1 EVENT TRIGGERS FOR ANALOG AND DIGITAL SYSTEMS. A change of state of any of the following items will trigger the storage of an event. Input 1A - 4B Output 1A - 4B Ann. Relay 1A - 3B Ann. Output 1 - 6

RFL 9745 September 20, 2007

6 - 69

RFL Electronics Inc. (973) 334-3100

Page 259

6.13.5.2 LEVEL 2 EVENT TRIGGERS FOR ANALOG SYSTEMS. A change of state of any of the following items will trigger the storage of an event. Input

1A - 4B

RX Low

1-4

Boot-up in progress

Output

1A - 4B

RX Enable

1-4

Xmodem download

Ann. Relay

1A - 3B

Boost

1-4

Run Autotest

Ann. Output

1-6

Outage timer

Test in progress

Output FTT

1A - 4B

Left power supply low

Autotest complete

Output short

1A - 4B

Right power supply low

Autotest timeout

TX Enable

1-4

Bus Error

Address test fail (Checkback)

TX Func.

1-4

Comms CPU Fail

Channel delay fail (Ping-Pong)

RX High

1-4

Battery Fail

RS-232 Act

6.13.5.3 LEVEL 2 EVENT TRIGGERS FOR DIGITAL SYSTEMS. A change of state of any of the following items will trigger the storage of an event. Input

1A - 4B

Battery Fail

Minor Data Alarm

Output

1A - 4B

Boot-up in progress

Configuration Error

Ann. Relay

1A - 3B

Xmodem download

Alarm BER

Ann. Output

1-6

Run Autotest

Clock Error

Output FTT

1A - 4B

Test in progress

Frame Error

Output short

Autotest complete

TX Function 1-7

Outage timer

Autotest timeout

RX Function 1-7

Left power supply low

Address test fail (Checkback)

RX Enable

Right power supply low

Channel delay fail (Ping-Pong)

Optic TX Fail(1)

Bus Error

RS-232 Act

Comms CPU Fail

Major Data Alarm

Note 1. Only digital systems that are using fiber optics have an “Optic TX Fail” event.