The text of a manual · part 31 of 43
Instruction Manual RFL 9745 Teleprotection Channel: Section 6. USING THE RS-232 PORTS TO PROGRAM AND OPERATE THE RFL 9745, pages 260 to 269
Pages 260 to 269 of 394, from Instruction Manual RFL 9745 Teleprotection Channel
The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the RFL RFL-9745
Page 260
6.13.6 ERASING THE SEQUENCE-OF-EVENTS LOG To erase the sequence-of-events log, use the "R" command: 9745-S>R [ENTER] When you invoke the "R" command, the following prompt appears: Are you sure? [Yes,No] To answer "yes," press the [Y] key. The sequence-of-events log will be erased. If you decide you don't want to erase the sequence-of-events log, press the [N] key. The log will remain as it is, and the following message will appear: Reset Sequence Cancelled
6.13.7 LEAVING THE SEQUENCE-OF-EVENTS MODE To leave the sequence-of-events mode, use the "Q" command: 9745-S>Q [ENTER] The "Q" command tells the RFL 9745 to leave the sequence-of-events mode and return to the normal "9745>" prompt.
6.13.8 VIEWING AN INDIVIDUAL EVENT RECORD To view an individual record from the Directory Of Events, enter its record number. For example, to view Record #001, enter a "1": 9745-S>1 [ENTER] An individual record similar to the one shown in Figure 6-30 or 6-31 will appear. The individual event records shown in Figures 6-30 and 6-31 list the record number, the name of the input that changed state to trigger the event, the state the input shifted to at the time of the event, and the date and time the event occurred. Below this, the status of all inputs, outputs, and alarm outputs at the time of the event are listed. This information can be used to analyze the system conditions at the precise instant the event occurred. “A” indicates that the parameter is “active” or connected. “I” indicates that the parameter is “inactive” or not connected. “F” indicates Fail to trip. “SQ” indicates that the parameter is “squelched”. “B” indicates Boost is active for that channel.
RFL 9745 September 20, 2007
6 - 71
RFL Electronics Inc. (973) 334-3100
Page 261
Record 001
Event Trigger: Rx Freq High Ch3 Event Time: 01/11/99, 23:44:14.954
Inactive
Input 1A Input 2A Input 3A Input 4A Input 1B Input 2B Input 3B Input 4B
I I I I I I I I
Output 1A Output 2A Output 3A Output 4A Output 1B Output 2B Output 3B Output 4B
I I I I I I I I
Rx Freq High Ch1 Rx Freq High Ch2 Rx Freq High Ch3 Rx Freq High Ch4 Rx Freq Low Ch1 Rx Freq Low Ch2 Rx Freq Low Ch3 Rx Freq Low Ch4
I I I I I I I I
Annunc Relay 1A Annunc Relay 2A Annunc Relay 3A Annunc Relay 1B Annunc Relay 2B Annunc Relay 3B
A I I I I I
Annunc Output 1 Annunc Output 2 Annunc Output 3 Annunc Output 4 Annunc Output 5 Annunc Output 6
I I I I I I
Tx Function Ch1 Tx Function Ch2 Tx Function Ch3 Tx Function Ch4 Address Test Fail Autotest Timeout
I I I A I I
Run Auto Test FM Noise Ch1 FM Noise Ch2 FM Noise Ch3 FM Noise Ch4 Comms CPU Failure Autotest Complete 9745-S>
I I I I I I I
Channel Delay AM Noise Ch1 AM Noise Ch2 AM Noise Ch3 AM Noise Ch4 Outage Timer Active XMODEM Download
I I A A A A I
Bus Error Left Power Low Right Power Low Battery Failure RS232 Active Test in Progress Bootup in Progress
I I A I A I I
Figure 6-30. Typical individual event record for the Audio System (using default labels) Record 001
Event Trigger: Clock Error Event Time: 01/11/99, 23:40:45.066
Active
Input 1A Input 2A Input 3A Input 4A Input 1B Input 2B Input 3B Input 4B
I I I I I I I I
Output 1A Output 2A Output 3A Output 4A Output 1B Output 2B Output 3B Output 4B
I I I I I I I I
Rx Function 1 Rx Function 2 Rx Function 3 Rx Function 4 Tx Function 1 Tx Function 2 Tx Function 3 Tx Function 4
SQ I I SQ I A A I
Annunc Relay 1A Annunc Relay 2A Annunc Relay 3A Annunc Relay 1B Annunc Relay 2B Annunc Relay 3B
I I I I I I
Annunc Output 1 Annunc Output 2 Annunc Output 3 Annunc Output 4 Annunc Output 5 Annunc Output 6
I I I I I I
Major Data Error Minor Data Error Configuration Err Alarm BER Address Test Fail Autotest Timeout
I I I I I I
Run Auto Test Rx Function 5 Rx Function 6 Rx Function 7 Frame Error Comms CPU Failure Autotest Complete 9745-S>
I I I I I I I
Channel Delay Tx Function 5 Tx Function 6 Tx Function 7 Clock Error Outage Timer Active XMODEM Download
I I A A A I I
Bus error Left power low Right power low Battery failure RS232 Active Test in Progress Bootup in Progress
I I A I I I I
Figure 6-31. Typical individual event record for the Digital System (using default labels)
RFL 9745 September 20, 2007
6 - 72
RFL Electronics Inc. (973) 334-3100
Page 262
Record 071
Event Trigger: Input 3B Inactive Event Time: 09/19/01, 11:32:13.691
Input 1A Input 2A Input 3A Input 4A Input 1B Input 2B Input 3B Input 4B
I I I I I I I I
Output 1A Output 2A Output 3A Output 4A Output 1B Output 2B Output 3B Output 4B
I I I I I I I I
Rx Function 1 Rx Function 2 Rx Function 3 Rx Function 4 Tx Function 1 Tx Function 2 Tx Function 3 Tx Function 4
I I I I I I I I
Annunc Relay 1A Annunc Relay 2A Annunc Relay 3A Annunc Relay 1B Annunc Relay 2B Annunc Relay 3B
I I I I I I
Annunc Output 1 Annunc Output 2 Annunc Output 3 Annunc Output 4 Annunc Output 5 Annunc Output 6
I I I I I I
Major Data Error Minor Data Error Configuration Err Alarm BER Address Test Fail Autotest Timeout
I I I I I I
Run Auto Test Rx Function 5 Rx Function 6 Rx Function 7 Frame Error Comms CPU Failure Autotest Complete Optic Tx Fail 9745-S>
I SQ SQ SQ I I A I
Channel Delay Tx Function 5 Tx Function 6 Tx Function 7 Clock Error Outage Timer Active XMODEM Download
I I I I I I I
Bus error Left power low Right power low Battery failure RS232 Active Test in Progress Bootup in Progress
I I I I I I I
Figure 6-32. Typical individual event record for the Optical System (using default labels)
6.14 ADVANCED PARAMETERS OPTION When selected by the user, the Advanced Parameters Option allows the 9745 digital system to display additional parameters in the Programming and Display menus, and to display received modem characters on the Values and Update screens. This option can be enabled from the Test menu as follows: To enable the advanced parameters option, do the following: 1.
Go to the test menu.
2.
Enter the password.
3.
Type in 99 [ENTER]. The following information will be displayed: 9745-T>99 Debug Information [Enable, Disable]
4.
Type in E [ENTER]. The following information will be displayed: Debug Information 9745-T>
5.
Disabled
Enabled
Go back to the values display.
RFL 9745 September 20, 2007
6 - 73
RFL Electronics Inc. (973) 334-3100
Page 263
A typical parameter settings display for the Digital system (with the advanced parameters option disabled) is shown in Figure 6-32. A typical parameter settings display for the Digital system (with the advanced parameters option enabled) is shown in Figure 6-33. Note in Figure 6-33 that the advanced parameters are items 186 through 193. These are pre-programmed at the factory to the recommended values shown, however, they can be re-programmed by the user to suit a particular need. # 999 011 012 013 014
PARAMETER System Label Functions 1-7 Major Data Error Minor Data Error Alarm BER
060 Opt Status Board 063 Year 065 Time 067 Local Address 069 Reset Log 9745>
SETTING Test Unit #1 Digital 6, 500 400, 200000 1E-04
#
PARAMETER
SETTING
No 1994 13:47:06 0
062 Chan delay alarm 064 Date 066 Hour Adjust 068 Remote Address
4 ms 08/09 0 888
Figure 6-33. Typical parameter settings display for the Digital System (with advanced parameters option disabled)
# 999 011 012 013 014
PARAMETER System Label Functions 1-7 Major Data Error Minor Data Error Alarm BER
SETTING Test Unit #1 Digital 6, 500 400, 200000 1E-04
#
PARAMETER
SETTING
060 063 065 067 069
Opt Status Board Year Time Local Address Reset Log
No 1994 13:47:06 0
062 064 066 068
Chan delay alarm Date Hour Adjust Remote Address
4 ms 08/09 0 888
30 30.0 uSec 30 71000 bits/sec 50000 bits/sec
187 #Oks Reset Major 189 #Drop Re-frame 191 #Accept Message
186 #Oks Reset Minor 188 Maximum Jitter 190 #CRC out sync 192 Upper Freq Limit 193 Lower Freq Limit 9745>
30 3 2
Figure 6-34. Typical parameter settings display for the Digital System (with advanced parameters option enabled)
NOTE The values shown for parameters 186 to 193 in Figure 6-33 above, are default values.
RFL 9745 September 20, 2007
6 - 74
RFL Electronics Inc. (973) 334-3100
Page 264
Definitions of the advanced parameters in the parameters display are as follows: 186 - #Oks Reset Minor
Number of good CRC (cyclic redundancy check) messages required to restart the Minor Data Error test after a failure.
187 - #Oks Reset Major
Number of good CRC messages required to restart the Major Data Error test after a failure.
188 - Maximum Jitter
The maximum variation allowed in a word (15 bits) before the Clock Errors alarm is set.
189 - #Drop Re-frame
Number of good CRC messages required to abort the re-framing algorithm when the receiver is out of synchronization.
190 - # CRC Out Sync
Number of bad CRC messages required to consider the receiver to be out of sync and invoke the re-framing algorithm.
191 - # Accept Message
# of consecutive messages required to trigger a trip.
192 - Upper Freq Limit
Maximum frequency allowed before the Clock Errors alarm is set.
193 - Lower Freq Limit
Minimum frequency allowed before the Clock Errors alarm is set.
RFL 9745 September 20, 2007
6 - 75
RFL Electronics Inc. (973) 334-3100
Page 265
A typical values display for the Digital system (with the advanced parameters option disabled) is shown in Figure 6-34. A typical values display for the Digital system (with the advanced parameters option enabled) is shown in Figure 6-35. Note in Figure 6-35 that the advanced parameters are items 146 through 152 and lines 199 and 200. The values display is for viewing only and cannot be changed by the user.
#
NAME VALUE # NAME VALUE ---------------------------------------------------------------------140 Tx Chan Delay 6 ms 141 Next Auto Test N/A 142 Rx Chan Delay 6 ms 143 Last Reset Date 16:38:59 03/03/94 144 Cum Outage Time 00:00:00.000 145 Current Time 00:32:56 03/15/94 146 Data Rate N/A 147 Bit Error Rate Max Error 148 Word Errors 501757 149 Clock Errors 6 150 Frame Errors 1 151 Minor Data Error 1 152 Major Data Error 1
154 155 156 157 158 159 160 161
Input 1A Input 1B Input 2A Input 2B Input 3A Input 3B Input 4A Input 4B
Function 175 Rx Function 176 Tx Function 9745>
(I/A) I I I I I I I I
LOG 1 0 4 0 0 1 0 0
#1 SQ I
#2 SQ I
162 163 164 165 166 167 168 169
(I/A) A A A A I I I I
Output 1A Output 1B Output 2A Output 2B Output 3A Output 3B Output 4A Output 4B #3 SQ I
#4 SQ I
#5 SQ I
LOG 0 2 0 2 0 2 0 2 #6 SQ I
#7 SQ I
Figure 6-35. Typical values display for the Digital System (with advanced parameters option disabled)
The values displays shown in Figures 6-34 and 6-35 show the code number for each measured parameter, along with a brief description of its meaning and its measured value. “A” indicates that the parameter is “active” or connected. “I” indicates that the parameter is “inactive” or not connected. “SQ” indicates that the parameter is “squelched”. Full descriptions for each of these measured values can be found in paragraph 6.6.
RFL 9745 September 20, 2007
6 - 76
RFL Electronics Inc. (973) 334-3100
Page 266
#
NAME VALUE # NAME VALUE ---------------------------------------------------------------------140 Tx Chan Delay 6 ms 141 Next Auto Test N/A 142 Rx Chan Delay 6 ms 143 Last Reset Date 16:38:59 03/03/94 144 Cum Outage Time 00:00:00.000 145 Current Time 00:32:56 03/15/94 146 Data Rate 0 147 Bit Error Rate N/A 148 Word Errors 0 149 Clock Errors 9 150 Frame Errors 0 151 Minor Data Error 0 152 Major Data Error 0 (I/A) LOG (I/A) LOG 154 Input 1A I 1 162 Output 1A A 0 155 Input 1B I 0 163 Output 1B A 2 156 Input 2A I 4 164 Output 2A A 0 157 Input 2B I 0 165 Output 2B A 2 158 Input 3A I 0 166 Output 3A I 0 159 Input 3B I 1 167 Output 3B I 2 160 Input 4A I 0 168 Output 4A I 0 161 Input 4B I 0 169 Output 4B I 2 Function 175 Rx Function 176 Tx Function -- press any key-199 Modem Bytes 200 9745>
#1 SQ I
#2 SQ I
01 50.652 01 50.656
#3 SQ I
#4 SQ I
01 50.667 01 50.653
#5 SQ I 01 50.655 01 50.656
#6 SQ I
#7 SQ I
01 50.654 01 50.658
01 50.653 01 50.654
Figure 6-36. Typical values display for the Digital System (with advanced parameters option enabled)
Definitions of the advanced parameters in the values display are as follows: 199 & 200 - Modem Bytes A log of the modem messages sent between the local and remote 9745’s. The modem byte consists of the modem data in hexadecimal format and can have any value from 00 to FF. The time tag is in seconds and milliseconds, and matches the time in the sequence of events display.
RFL 9745 September 20, 2007
6 - 77
RFL Electronics Inc. (973) 334-3100
Page 267
6.15 THE WINDOW REMOTE APRIL MODE NOTE The Window Remote APRIL mode cannot be entered in the audio version unless channel one of the RFL 9745's four channels is set to the modem configuration. If channel one is not configured as a modem, the “W” command will not appear in the main menu. Refer to Section 5 of this manual for more information on channel setup.
The Window Remote APRIL mode allows the user at one RFL 9745 to access the RFL 9745 at the other end of the communications link. To enter the Window Remote APRIL mode, use the "W" command Format: 9745>W [ENTER] When you invoke the "W" command, the remote RFL 9745's APRIL command main menu will appear on your screen. This is similar to the screen you would see by invoking the "H" (help) command, except the remote RFL 9745's system label will appear at the top of the screen and a "W_9745>" prompt will appear at the bottom. The screen will take longer to be displayed than other APRIL screens; this is because the modem link between the local and remote RFL 9745s operates at 300 baud, so it takes longer to send the information. (As discussed in Section 4, the APRIL baud rate for data transfer between the RFL 9745 and your terminal or PC is set to either 300, 1200, 2400, 9600, or 19,200). If a PC is connected to a local 9745 and a user interrogates the remote 9745 which is in local use, the following message will be displayed: REMOTE IN LOCAL USE. There must be inactivity at the RS232 port and front panel of the remote site for a minimum of five minutes before the remote site will respond to an interrogation from the local site. This prevents modifications to the remote site by two users at the same time. The Window Remote APRIL mode has the same capabilities as the local APRIL mode, with the following two exceptions. A user cannot: 1. Invoke the “W” command (You cannot place the remote RFL 9745 in the Window Remote APRIL mode). 2. Upload or download files across the remote window path. When you are finished accessing the remote RFL 9745, you can exit the Window Remote APRIL mode by entering three capital "X's": Format: W_9745>XXX(do not press [ENTER] key) The April command menu will re-appear on the screen, with the normal “!9745>” prompt. You will notice that the screen will be written at the regular speed again (either 300, 1200, 2400, 9600, or 19,200 baud). RFL 9745 September 20, 2007
6 - 78
RFL Electronics Inc. (973) 334-3100
Page 268
NOTE When you are using Window Remote April from a local RFL 9745, if the local or the remote 9745’s are running AUTOTEST, you will be automatically exited from the Window Remote April mode. The W prompt will be replaced by the 9745 prompt. The user must reenter the Window Remote April mode. If you want to stay in the Window Remote April mode without being interrupted, make sure that AUTOTEST is disabled at both the local and remote 9745’s.
6.16 RETURNING TO NORMAL RFL 9745 OPERATION Once you are finished accessing the RFL 9745 using APRIL, make sure you have returned to the "9745>" prompt: 1.
If you were in the Programming or Test Mode, press the [Q] and [ENTER] keys to return to the "9745>" prompt.
2.
If you were in the Update Mode, press the [X] and [ENTER] keys to return to the "9745>" prompt.
When the "9745>" prompt is displayed, simply disconnect your PC or terminal from the RFL 9745's RS-232 connector. If you accessed the RFL 9745 through an RFL 9660 Digital Switch, type in the deselect code (normally "BYE") to deselect the port, and then enter the "Q" command to terminate the session. (Refer to the RFL 9660 Instruction Manual for more information.)
RFL 9745 September 20, 2007
6 - 79
RFL Electronics Inc. (973) 334-3100
Page 269
This page intentionally left blank
RFL 9745 September 20, 2007
6 - 80