The text of a manual · part 29 of 43
Instruction Manual RFL 9745 Teleprotection Channel: Section 6. USING THE RS-232 PORTS TO PROGRAM AND OPERATE THE RFL 9745, pages 240 to 249
Pages 240 to 249 of 394, from Instruction Manual RFL 9745 Teleprotection Channel
The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the RFL RFL-9745
Page 240
6.10.14.1 LEAVING THE EDITING MODE Whenever you are finished editing the Alarm Logic Table, use the "Q" command: 9745-E>Q [ENTER] The "Q" command tells the RFL 9745 to leave the editing mode and return to the "9745-L>" prompt. If you changed any setting while in the programming mode, be sure to use the "SV" command described above to save the changes before invoking the "Q" command; otherwise, your changes will be lost.
6.10.14.2 VIEWING AND EDITING THE ALARM LOGIC TABLE To view the Alarm Logic Table, use the "V" command. 9745-E>V [ENTER] When you invoke the "V" command, an Alarm Logic Table similar to the portion shown in Figure 617 will appear, except that it will have a "9745-E>" prompt at the bottom. To change a line on the Alarm Logic Table, enter its line number and then press the [ENTER] key. 9745-E>12 [ENTER] The selected line from the Alarm Logic Table will appear on the screen. Below it will be a prompt listing the entries that can be made: 012 TIMER NODE11 TIMER1 A_RELAY1A [Primitive],[Input 1],[Input 2 or Timer #],[Output (opt)] Entries are made to the line as follows:
Primitive
The type of gate at the node (AND, OR, NOT, XOR, TIMER, or LATCH). Definitions of each gate type can be found in Section 2 of this manual.
Input 1
The name of the input or node that drives input 1 of the gate. This should be the exact spelling of the input or “nodeX” where X is the node number.
Input 2 or Timer # The name of the input or node that drives input 2 of the gate. This should be the exact spelling of the input or “nodeX” where X is the node number. If the gate is a NOT gate, then this input should be “#0”. If the gate is a timer, then this input should be “X” where X is the timer number. Output
RFL 9745 September 20, 2007
The name of the hardware output that is produced by this node.
6 - 51
RFL Electronics Inc. (973) 334-3100
Page 241
6.10.14.3 DISPLAYING EDITING HELP Any time you need to see a list of all the editing commands, use the "H" command. 9745-E>H [ENTER] When you invoke the "H" command, the Edit Alarm Table Menu shown in Figure 6-21 will re-appear on your screen.
6.10.14.4 SAVING THE EDITED ALARM LOGIC TABLE The "SV" command saves any changes you made to the Alarm Logic Table. The 9745 will go out of service during command execution. 9745-E>SV [ENTER] The "SV" command tells the RFL 9745 to store all the changes in its non-volatile memory. Once the changes are stored, the "9745-E>" prompt will re-appear.
RFL 9745 September 20, 2007
6 - 52
RFL Electronics Inc. (973) 334-3100
Page 242
6.10.15 SAVING NEW LOGIC SETTINGS The "SV" command saves any new settings you made while in the logic programming mode: 9745-L>SV [ENTER] The "SV" command tells the RFL 9745 to store all the changes in its non-volatile memory. Once the changes are stored, the "9745-L>" prompt will re-appear. Before you enter the "SV" command, the RFL 9745 operates according to the old logic parameter settings. Once the "SV" command is entered, the new settings will be in effect.
RFL 9745 September 20, 2007
6 - 53
RFL Electronics Inc. (973) 334-3100
Page 243
6.11 THE TEST MODE You can use APRIL and your terminal to verify RFL 9745 operation. All test functions that are normally done using the keypad on the RFL 9745's front panel can be done using a terminal. To use your PC or terminal to test the RFL 9745, use the "T" command. 9745>T [ENTER] The "T" command tells the RFL 9745 to send a list of all test commands to your terminal. To prevent testing by unauthorized persons, the "T" command is password-protected. If the proper password is entered, a test menu similar to the one shown in Figure 6-23 will appear.
H - Display test menu help Q - Leave test menu C - Change password (superuser authorization required) T - Redisplay tests ## - Run this test 9745-T> Figure 6-23. Typical test menu for the Audio or Digital System
You are now in the test mode, as indicated by the "9745-T>" prompt on your screen. You may now use the test commands to verify the RFL 9745. For more information on each test command, refer to the paragraph numbers listed below. Command
Meaning
Paragraph
H
Display test menu help
.
.
.
.
.
6.11.1
Q
Leave test menu
.
.
.
.
.
.
6.11.2
C
Changing the password
.
.
.
.
.
6.4.2
T
Redisplay tests
.
.
.
.
.
6.11.3
.
The 9745 Digital system has an advanced parameters option which can be used for system testing and which can be enabled or disabled. See paragraph 6.14 for further instructions.
RFL 9745 September 20, 2007
6 - 54
RFL Electronics Inc. (973) 334-3100
Page 244
6.11.1 DISPLAYING TEST MENU HELP Any time you need to see a list of all the test menu commands, use the "H" command. 9745-T>H [ENTER] When you invoke the "H" command, the test menu shown in Figure 6-22 will re-appear on your screen.
6.11.2 LEAVING THE TEST MODE When you are finished testing the RFL 9745, use the "Q" command: 9745-T>Q [ENTER] The "Q" command tells the RFL 9745 to leave the test mode and return to the normal "9745>" prompt.
RFL 9745 September 20, 2007
6 - 55
RFL Electronics Inc. (973) 334-3100
Page 245
6.11.3 DISPLAYING RFL 9745 TESTS To view a list of all RFL 9745 test parameters, use the "T" command. 9745-T>T [ENTER] When you invoke the "T" command, the RFL 9745 sends a list of all test parameters to your terminal. Typical test parameter lists for the Audio and Digital systems are shown in Figures 6-24 and 6-25 respectively.
TEST MENU 001 Subchannel Test 002 Disable Tx of Function 004 Operations Since Reset 005 Cumulative Outage Time Checkback: 006 Tests/Reset on Front Panel 007 Auto Tests 008 Time Between Tests 009 Next Test Start 010 Tests Run Since Reset 011 Tests Passed 012 Tests Failed 013 Run Auto Test 014 Run Ping Pong Test 015 Reset Log 9745-T>
Ch 1:E Ch 1:0 02:20:30.282
Ch 2:E Ch 2:0
Ch 3:E Ch 3:4
Ch 4:E Ch 4:0
Disabled Disabled N/A 10:09 10 1 9
Figure 6-24. Typical test parameter list for the Audio System
NOTE Channel 1 must be set to 6750 modem or modem to program parameters 7 through 14.
RFL 9745 September 20, 2007
6 - 56
RFL Electronics Inc. (973) 334-3100
Page 246
TEST MENU 003 Override of Function 004 Operations Since Reset 005 Cumulative Outage Time 006 Tests/Reset on Front Panel 007 Auto Tests 008 Time Between Tests 009 Next Test Start 010 Tests Run Since Reset 011 Tests Passed 012 Tests Failed 013 Run Auto Test 014 Run Ping Pong Test 015 Reset Log 016 Internal Clock Source 017 Local Loopback 9745-T>
Fn 1:X 2:X Fn 1:0 2:0 Fn 5:0 02:20:30.282
3:X 4:X 3:0 6:0 7:0
5:X 4:0
6:X
7:X
Disabled Disabled N/A 10:09 10 1 9
Disabled Disabled
Figure 6-25. Typical test parameter list for the Digital System
The test parameter list shows the code number for each item, and a brief description of its meaning. Most items also have their values listed. Full descriptions for each item on the test parameter list are as follows:
CAUTION Running Subchannel Tests or Override Function Tests on in-service units may result in unwanted operations such as causing a trip or losing guard. Extreme caution should be used in running these tests.
RFL 9745 September 20, 2007
6 - 57
RFL Electronics Inc. (973) 334-3100
Page 247
001 - Subchannel Test
For the Audio system, selecting this item from the test parameter list tells the RFL 9745 to start a subchannel test. This test allows the user to shift the transmitted frequency of channel 1, 2, 3 or 4 to the previously defined high or low value, regardless of the logic table. After 5 minutes, the subchannel test will automatically time out and the 9745 will go back to transmitting the frequency defined in the primitive logic. The user can also stop the test at any time by pressing any key on the keyboard. This test will not work on channel 1 if it is defined as a modem. Example: Enter the Test Menu by typing T[Enter] after the 9745 prompt. Enter the password and then type [Enter]. Then type in 1[Enter] to select Subchannel Test. Observe the following on the display: Subchannel Test [ Channel# ], [ H,L ] To force the 9745 to transmit the lower frequency on channel 3 press the following keys: [3], [L] [Enter] Observe the following on the display: Channel 3 forced low Press any key to stop>
002 - Disable Tx of Function
For the Audio system, selecting this item from the test parameters list allows the user to individually enable or disable the RFL 9745's four channels. To do this, enter "E" for enable or "D" for disable for each channel, separated by commas: Example: Type in 2[Enter] to select Disable of Tx Function. Observe the following on the display: Disable Tx of Function Ch 1:E Ch 2:E Ch 3:E Ch 4:E [Enable, Disable], [E,D], [E,D], [E,D] To enable Channels 1 and 2 and disable Channels 3 and 4, press the following keys: [E] [,] [E] [,] [D] [,] [D] [Enter]
RFL 9745 September 20, 2007
6 - 58
RFL Electronics Inc. (973) 334-3100
Page 248
Observe the following on the display: Disable Tx of Function Ch 1:E Ch 2:E Ch 3:D Ch 4:D [Enable, Disable], [E,D], [E,D], [E,D] If a "U" is displayed for any channel, there is a condition that exists that is preventing the channel from being initialized. The channel may not exist in your system. Two channel systems have channels 3 and 4, three channel systems have channels 1, 3 and 4, and four channel systems have channels 1, 2, 3 and 4. LED’s will work normally.
003 - Override of Function
For the Digital system selecting this item from the test parameter list tells the RFL 9745 to start an Override of Function test. This test allows the user to individually override the RFL 9745’s seven functions. To do this enter a “1” or a “0” if you want the 9745 to transmit a “1” or a “0” for that function. After 5 minutes the Override of Function test will automatically time out, and the 9745 will go back to transmitting the output functions defied in the primitive logic. The user can also stop the test at any time by presing any key on the keyboard. An “X” means that there is no override for that function. This test can also be done in the remote mode. Example: Enter the Test Menu by typing T[Enter] after the 9745 prompt. Enter the password and then type [Enter]. Then type in 3[Enter] to select Override of Function. Observe the following on the display: Override of Function Fn 1:X 2:X 3:X 4:X 5:X 6:X 7:X [0,1,X] To transmit a “1” for functions 1,2 and 3 and ” 0” for functions 4,5,6 and 7 press the following keys: [1], [1], [1], [0], [0], [0], [0] [Enter] Observe the following on the display: Override of Function Fn 1:1 2:1 3:1 4:0 5:0 6:0 7:0 Press any key to stop> You must enter a value for each of the seven functions.
RFL 9745 September 20, 2007
6 - 59
RFL Electronics Inc. (973) 334-3100
Page 249
004 - Operations Since Reset
This is a display item only. For the Audio system, this display shows how many times each channel has switched from a low to high frequency since the last time the RFL 9745 was reset. For the Digital system, this display shows how many times each function has gone from a “0” to a “1” since the last time the 9745 was reset.
005 - Cumulative Outage Time
This is a display item only. It lists the total amount of outage time since the last time the RFL 9745 was reset, in hours, minutes, seconds and milliseconds.
006 - Tests/Reset on Front Panel
This selection allows the user to either enable or disable test initiation at the front panel. If front panel tests are permitted, see Section 7 for information on how to run them.
007 - Auto Tests1
This selection allows the user to either enable or disable local automatic testing. If automatic testing is permitted, the next two parameters ,008 and 009, will determine the time between tests, and when the test will be run.
008 - Time Between Tests
This item determines how long the RFL 9745 will pause between tests. It can be set by the user anywhere from 1 to 24 hours, in 1minute steps.
009 - Next Test Start
This item can be set by the user, and determines when the next RFL 9745 test will occur. The test time is specified in hours and minutes; using 24-hour time (Add 12 hours to any time past 12:59 p.m.)
010 - Tests Run Since Reset
This is a display-only item. It shows how many tests have been run since the last time the RFL 9745 was reset.
011 - Tests Passed
This is a display-only item. It shows how many tests have passed since the last time the RFL 9745 was reset.
012 - Tests Failed
This is a display-only item. It shows how many tests have failed since the last time the RFL 9745 was reset.
RFL 9745 September 20, 2007
6 - 60
RFL Electronics Inc. (973) 334-3100