Instruction Manual RFL 9745 Teleprotection Channel: Section 6. USING THE RS-232 PORTS TO PROGRAM AND OPERATE THE RFL 9745, pages 210 to 219

Pages 210 to 219 of 394, from Instruction Manual RFL 9745 Teleprotection Channel

The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the RFL RFL-9745

Page 210

Example 5: Editing the Minor Data Error setting (Digital System only) The Minor Data Errors (W, X), are bits used in the primitive logic to inhibit tripping. The Minor Data Error bit is set when W bits are in error out of X bits (where X>15W). Parameter # 013 in Figure 6-9 is presently set for 400 bits in error out of 200000 (400, 200000). This means that if after an interval of 200000 bits if more than 400 bits were in error, the Minor Data Error bit will be set. The next interval of 200000 bits will begin at the point at which the Minor Data Error bit was set. It will then take another interval of 200000 bits with less than 400 bits in error to reset the Minor Data Error bit. Since the errors are detected after the interval, the Minor Data Errors are slow acting. To change the setting of the Minor Data Error, do the following: 1.

Enter the number for the Minor Data Error parameter (13) on your terminal or PC keyboard, and then press the [ENTER] key. The Minor Data Error parameter will be displayed, with information about its setting below it. 013 Minor Data Error 400, 200000 [0-10000 errors out of], [1-1000000 total]>_

2.

Type in W, X where W can have any value from 0 to 10000 and where X can have any value from 1 to 1000000. For example, type in 400, 200000 and then press the [ENTER] key. The Minor Data Error parameter will be re-displayed, set to the new value as follows: 013 Minor Data Error 400, 200000

3.

Enter the “SV” command to save the new Minor Data Error setting. 9745-P>SV

RFL 9745 September 20, 2007

6 - 21

RFL Electronics Inc. (973) 334-3100

Page 211

Example 6: Editing the Alarm BER (Digital System only) The Alarm BER (Alarm Bit Error Rate) is the ratio of error bits to received bits. When this rate is exceeded the BER Alarm bit in the alarm logic will be set. The BER calculation is performed over a one second period. The Alarm BER notation is 1E-02, where the mantissa can be any whole number from 1 to 9 and where the exponent can be any negative whole number from -6 to -2. In the above example, 1E-02 is equivalent to 1x10-2 =1/10+2 which indicates one bit error out of 100 transmitted bits. To change the setting of the Alarm BER, do the following: 1.

Enter the number for the Alarm BER parameter (14) on your terminal or PC keyboard, and then press the [ENTER] key. The Alarm BER parameter will be displayed, with information about its setting below it. 014 Alarm BER 1E-04 [mantissa:1 to 9], [exponent: -6 to -2]>_

2.

Type in the mantissa, and then the exponent. For example, type in 2, -4 and then press the [ENTER] key. The Alarm BER parameter will be re-displayed, set to the new value as follows: 014 Alarm BER

2E-04

This is equivalent to 2 bit errors out of 10000 transmitted bits. 3.

Enter the “SV” command to save the new Alarm BER setting. 9745-P>SV

Clears at 0E-06.

RFL 9745 September 20, 2007

6 - 22

RFL Electronics Inc. (973) 334-3100

Page 212

6.8 READING PARAMETER SETTINGS The "D" command tells the RFL 9745 to send a list of all parameter settings to your terminal. This list of settings is called the "read settings" menu. 9745>D [ENTER] A typical read settings menu for the Audio System appears in Figure 6-10. All the settings described in Section 5 of this manual are shown, but you can't change the displayed values. To change these values, you will have to enter the programming mode. (See paragraph 6.7 for more information.) The programming mode is password-protected, so only authorized persons can change the RFL 9745's parameter settings.

# 999 001 002 003 005 006 008 010

PARAMETER System Label Channel 1 Tone 1 Tx Freq Transmit Level Tone 1 Rx Freq Rx Bandwidth Rx Alarm FM Noise

SETTING SYSTEM LABEL Modem 700 Hz 1000 Hz -15.00 dBm 700 Hz 1000 Hz 380 Hz -33 dBm 75 %

016

Channel 2 not defined

031 032 033 035 036 038 040

Channel 3 Tone 3 Tx Freq Transmit Level Tone 3 Rx Freq Rx Bandwidth Rx Alarm FM Noise

Single 2145 Hz 2445 Hz -15.00 dBm 2145 Hz 2445 Hz 380 Hz -33 dBm 28 %

046 047 048 050 051 053 055 060 062 064 066 068 9745>

Channel 4 Tone 4 Tx Freq Transmit Level Tone 4 Rx Freq Rx Bandwidth Rx Alarm FM Noise Opt Status Board Chan delay alarm Date Hour Adjust Remote Address

Single 1465 Hz 1765 Hz -15.00 dBm 1465 Hz 1765 Hz 380 Hz -33 dBm 28 % Yes 8 ms 08/09 0 888

# PARAMETER

SETTING

004 Boost Level

0 dB

007 Rx Level 009 AM Noise (SNR)

-15 dBm 8 dB

034 Boost Level

0 dB

037 Rx Level 039 AM Noise (SNR)

-15 dBm 8 dB

049 Boost Level

0 dB

052 Rx Level 054 AM Noise (SNR)

-15 dBm 8 dB

061 EE Pot J10 063 Year 1994 065 Time 067 Local Address 069 Reset Log

A 13:47:06 456

Figure 6-10. Typical read settings menu, for the Audio System, with three channels active and one channel not defined

RFL 9745 September 20, 2007

6 - 23

RFL Electronics Inc. (973) 334-3100

Page 213

6.9 VIEWING CONFIGURATION AND SOFTWARE INFORMATION The "F" command tells the RFL 9745 to send a configuration and software version display to your terminal. This display tells you how the RFL 9745 is configured, and what software versions are being used. These parameters cannot be changed by the user in this display, however some of the parameters can be changed by going to other menus. For the Audio System, parameters 076 through 082 can be changed by going to the parameter settings display shown in Figure 6-8. For the Digital System, parameters 076 through 078 can be changed by going to the parameter settings display shown in Figure 6-9. Format: 9745>F [ENTER] Typical configuration and software version displays for the narrowband and wideband Audio Systems are shown in Figures 6-11 and 6-12 respectively. A typical configuration and software version display for the Digital System is shown in Figure 6-13.

9745 070 071 072 073 074 075 076 077 078 079 080 081 082 9745>

Configuration: Software ID BIOS ID System Date BIOS Date Primitive ID Alarm Logic ID Annunc Outputs Local Address Remote Address Channel 1 Channel 2 Channel 3 Channel 4

5.2; (c) 2000 RFL Electronics 3.1; (c) 1994 RFL Electronics 12/10/2002 11:21 03/26/1997 14:02 DEFAULT 9745 AUDIO PRIMITIVE CODE DEFAULT AUDIO ALARM FUNCTION Not Installed 888 888 audio audio audio audio

Figure 6-11. Typical configuration and software version display for the narrow band Audio System

RFL 9745 September 20, 2007

6 - 24

RFL Electronics Inc. (973) 334-3100

Page 214

9745 070 071 072 073 074 075 076 077 078 079 080 081 082 9745>

Configuration: Software ID BIOS ID System Date BIOS Date Primitive ID Alarm Logic ID Annunc Outputs Local Address Remote Address Channel 1 Channel 2 Channel 3 Channel 4

5.2; (c) 2000 RFL Electronics 3.1; (c) 1994 RFL Electronics 12/10/2002 11:21 03/26/1997 14:02 DEFAULT 9745 AUDIO PRIMITIVE CODE DEFAULT AUDIO ALARM FUNCTION Not Installed 888 888 audio – wideband audio – wideband audio – wideband audio – wideband

Figure 6-12. Typical configuration and software version display for the wide band Audio System

9745 070 071 072 073 074 075 076 077 078 083 084 9745>

Configuration: Software ID BIOS ID System Date BIOS Date Primitive ID Alarm Logic ID Annunc Outputs Local Address Remote Address Channel Type Data Rate

5.2; (c) 2000 RFL Electronics 3.1; (c) 1994 RFL Electronics 12/10/2002 11:21 02/26/1997 14:02 DEFAULT 9745 DIGITAL PRIMITIVE CODE DEFAULT DIGITAL ALARM FUNCTION Not Installed 888 888 Digital: RS 449 or X.21 No Clock

Figure 6-13. Typical configuration and software version display for the Digital System

RFL 9745 September 20, 2007

6 - 25

RFL Electronics Inc. (973) 334-3100

Page 215

The configuration and software version display shows the code number for each item, a brief description of its meaning, and its value. Full descriptions for each item are as follows: 070 - Software ID

The version number of the system software installed in your RFL 9745, or the PC April software version when in stand alone mode.

071 - BIOS ID

The version number of the BIOS software (basic input/output software) installed in your RFL 9745.

072 - System Date

The release date and time of the system software revision in your system, and not the date and time that the software was loaded into the 9745.

073 - BIOS Date

The release date and time of the BIOS software revision in your system, and not the date and time that the software was loaded into the 9745.

074 - Primitive ID

The name of the primitive logic table active in your system. The user can expect to see the following variations of Primitive ID: 1. 2. 3. 4. 5. 6. 7.

075 - Alarm Logic ID

DEFAULT 9745 AUDIO PRIMITIVE CODE DEFAULT 6750 AUDIO PRIMITIVE CODE DEFAULT 9745 DIGITAL PRIMITIVE CODE EDIT DEFAULT PRIMITIVE CODE DOWNLOADED PRIMITIVE CODE EXPERT SYSTEM PRIMITIVE CODE DEFAULT 9745 OPTIC PRIMITIVE CODE

The name of the alarm logic table active in your system. The user can expect to see the following variations of Alarm Logic ID: 1. 2. 3. 4.

DEFAULT AUDIO ALARM FUNCTION EDIT DEFAULT ALARM FUNCTION DOWNLOADED ALARM FUNCTION 9745 ALARM LOGIC

076 - Annunc Outputs

This will indicate either "Installed" or "Not Installed," depending on whether or not the annunciator outputs are installed.

077 - Local Address

This is the address assigned by the user to the local RFL 9745. This address can be changed by editing the parameter settings shown in Figures 6-8 and 6-9.

RFL 9745 September 20, 2007

6 - 26

RFL Electronics Inc. (973) 334-3100

Page 216

078 - Remote Address

This is the address assigned by the user to the remote RFL 9745. This address can be changed by editing the parameter settings shown in Figures 6-8 and 6-9.

079 - Channel 1

This will indicate either “audio” or “none” depending on whether Channel 1 is an audio channel, or not installed.

080 - Channel 2

This will indicate either “audio” or “none” depending on whether Channel 2 is an audio channel, or not installed.

081 - Channel 3

This will indicate either “audio” or “none” depending on whether Channel 3 is an audio channel, or not installed.

082 - Channel 4

This will indicate either “audio” or “none” depending on whether Channel 4 is an audio channel, or not installed.

083 - Channel Type

This will indicate the type of Digital I/O card that is installed in the system. The user can expect to see any one of the following variations: 1. 2. 3. 4. 5. 6. 7.

084 - Data Rate

Digital: RS449 or X.21 Digital: Fiber Optics Digital: G.703 Codirectional Digital: G.703 Contradirectional Digital: Short Haul Fiber Digital: Unknown media Digital card not installed

This will display the actual measured data rate rounded off to the nearest thousand bits/second ( for example: “64 K bits/second” ), or will display “No Clock” if data is not present.

NOTE The RFL 9745's communication channels cannot be mixed. The channels will be either audio, digital, fiber optic, or not installed.

RFL 9745 September 20, 2007

6 - 27

RFL Electronics Inc. (973) 334-3100

Page 217

CAUTION The RFL 9745 has powerful logic programming capabilities. This allows persons with extensive programming experience to modify the logic inside the RFL 9745 so that it can respond to conditions that exist in your system. Improper logic settings may result in system malfunctions, false trips, or other undesirable conditions. Be sure to read and fully understand the paragraphs describing the logic/alarm programming language in Section 2 of this manual before attempting to enter the logic programming mode.

6.10 THE LOGIC PROGRAMMING MODE The logic programming mode allows you to use the RFL 9745's powerful logic programming capabilities to tailor its logic to suit your specific application. To enter the logic programming mode, use the "K" command. 9745>K [ENTER] The "K" command tells the RFL 9745 to send a list of all logic programming commands to your terminal. To prevent use by unauthorized persons, the "K" command is password-protected.

Logic Programming Menu H - Display logic menu help A - Go to Alarm and I/O Name menu C - Change Password (superuser authorization required) D - Go to Timer Parameter menu E - Download Embedded Logic F - Restore Default Logic G - Output Primitive Logic Table M - Output Alarm Logic Table Q - Leave Logic Programming menu R - Go to Default Logic Configuration menu S - Edit Primitive Processor Logic Table T - Edit Alarm Logic Table ## - Edit this specific number parameter SV - Save Programming and Assemble Default Logic 9745-L>

Figure 6-14. Typical logic programming menu for the Audio or Digital System

RFL 9745 September 20, 2007

6 - 28

RFL Electronics Inc. (973) 334-3100

Page 218

You are now in the logic programming mode, as indicated by the "9745-L>" prompt on your screen. You may now use the logic programming commands to modify how the RFL 9745 operates. For more information on each logic programming command, refer to the paragraph numbers listed below.

Command

Meaning

H A C D E F G M Q R S T SV

Display logic menu help . . . Go to Alarm and I/O Name menu . . Changing the Password . . . Go to Timer Parameter menu . . . Download Embedded Logic . . . Restore Default Logic . . . . Output Primitive Logic Table . . . Output Alarm Logic Table . . . Leave Logic Programming menu . . Go to Default Logic Configuration menu . Edit Primitive Processor Logic Table . . Edit Alarm Logic Table . . . Save Programming and Assemble Default Logic

RFL 9745 September 20, 2007

Paragraph

6 - 29

. . . . . . . . . . . . .

. . . . . . . . . . . . .

6.10.1 6.10.2 6.4.2 6.10.5 6.10.6 6.10.7 6.10.8 6.10.9 6.10.10 6.10.11, 12 6.10.13 6.10.14 6.10.15

RFL Electronics Inc. (973) 334-3100

Page 219

6.10.1 DISPLAYING LOGIC PROGRAMMING HELP Any time you need to see a list of all the logic programming commands, use the "H" command. 9745-L>H [ENTER] When you invoke the "H" command, the logic programming menu shown in Figure 6-13 will re-appear on your screen.

RFL 9745 September 20, 2007

6 - 30

RFL Electronics Inc. (973) 334-3100