Page 220
6.10.2 CHANGING ALARM AND I/O NAMES You can assign new names to each of the RFL 9745's alarm outputs, inputs, and outputs. These names will appear on the screens you will see while using APRIL, and on the RFL 9745's front-panel display. To change these names, use the "A" command. 9745-L>A [ENTER] When you invoke the "A" command, an Alarm and I/O Name menu similar to the one shown in Figure 6-15 will appear, which is for a 9745 System equipped with the status option. For 9745 Systems not equipped with the status option, parameters 126-131 will not be shown on the menu. If your system has the status option, you must set the Opt Status Board to “yes” in the parameters display in order to view these outputs. See parameter 060 in the menu of Figure 6-7.
# ALARM # NAME ----------------------------------------------------------120 Annunc Relay 1A ALARM RELAY 1A | DUAL COMMS ALARM 121 Annunc Relay 2A ALARM RELAY 2A | HARDWARE WARNING 122 Annunc Relay 3A ALARM RELAY 3A | HARDWARE ALARM 123 Annunc Relay 1B ALARM RELAY 1B | OUTPUT ALARM 124 Annunc Relay 2B ALARM RELAY 2B | NOT USED 125 Annunc Relay 3B ALARM RELAY 3B | NOT USED 126 Annunc Output 1 AUX OUTPUT 1 | DUAL COMMS ALARM 127 Annunc Output 2 AUX OUTPUT 2 | HARDWARE WARN 128 Annunc Output 3 AUX OUTPUT 3 | HARDWARE ALARM 129 Annunc Output 4 AUX OUTPUT 4 | OUTPUT ALARM 130 Annunc Output 5 AUX OUTPUT 5 | NOT USED 131 Annunc Output 6 AUX OUTPUT 6 | NOT USED 140 Input 1A 142 Input 2A 144 Input 3A 146 Input 4A
KEY CH 3 KEY CH 3 KEY CH 4 KEY CH 4
141 Input 1B 143 Input 2B 145 Input 3B 147 Input 4B
KEY CH 2 KEY CH 2 NOT USED NOT USED
150 Output 1A 152 Output 2A 154 Output 3A 156 Output 4A
DUAL GUARD DUAL GUARD DUAL TRIP DUAL TRIP
151 Output 1B 153 Output 2B 155 Output 3B 157 Output 4B
SINGLE GUARD SINGLE GUARD SINGLE TRIP SINGLE TRIP
160 Tx Func 1 LED 162 Tx Func 2 LED 164 Tx Func 3 LED 166 Tx Func 4 LED 168 Seal-in Func LED 9745-L>
High High High Low No
161 Rx Func 1 LED 163 Rx Func 2 LED 165 Rx Func 3 LED 167 Rx Func 4 LED
High High High Low
Figure 6-15. Typical Alarm and I/O Name menu for the Audio or Digital System equipped with the status option
RFL 9745 September 20, 2007
6 - 31
RFL Electronics Inc. (973) 334-3100
Page 221
6.10.3 LABELING INPUTS, OUTPUTS, AND ALARMS Each of the RFL 9745's inputs and outputs can be assigned a name or label up to 16 characters long. Annunciator outputs can be assigned a two-line name, with up to 16 characters in each line. This name will appear on many of the APRIL menus, and will also appear on the RFL 9745's front-panel display. To label the RFL 9745's inputs, outputs, and alarms, use the following procedure: 1.
Press the [A] and [ENTER] keys on your terminal or PC keyboard to view a list of all current alarm and I/O names. A list of current alarm and I/O names will appear on your screen.
2.
Enter the number of the first input or output name to be changed, and press the [ENTER] key on your terminal or PC keyboard. The selected input or output name and its current setting will be displayed. For example, if Parameter 140 (Input 1A) is selected, the following will appear on your screen: 140 Input 1A [line 1]
KEY CH 3
3.
Enter the new name for the input or output (up to 16 characters), and then press the [ENTER] key. The parameter will be redisplayed, showing the new name.
4.
Enter the number of the first alarm output name to be changed, and press the [ENTER] key on your terminal or PC keyboard. The selected alarm output name and its current setting will be displayed. For example, if Parameter 120 (Input 1A) is selected, the following will appear on your screen: 120 Annunc Relay 1A DUAL COMMS ALARM RELAY 1A [line 1 line 2]
5.
Alarm outputs can have two-line names, with 16 characters in each line. Enter the name that you want displayed on the first line, a vertical line ( ), and the name that want displayed on the second line. Once the text for both lines is entered, press the [ENTER] key. The parameter will be redisplayed, showing the new name.
6.
Once you have made all the changes you need to make, enter the "SV" command to save your changes: 9745-L>SV
RFL 9745 September 20, 2007
6 - 32
RFL Electronics Inc. (973) 334-3100
Page 222
6.10.4 FRONT-PANEL FUNCTION INDICATORS The eight FUNCTION indicators on the RFL 9745's front panel show the status of the four tone channels. Each indicator can be set to light when a low-frequency tone is being sent or received, or when a high-frequency tone is being sent or received. They normally are set to light on the trip frequency.
6.10.4.1 SETTING FRONT PANEL FUNCTION INDICATORS To set the FUNCTION indicators, use the following procedure: 1.
Press the [A] and [ENTER] keys on your terminal or PC keyboard to view a list of all current alarm names, I/O names, and indicator functions. A list of current alarm names, I/O names, and indicator functions will appear on your screen.
2.
Enter the number for the first TX FUNCTION indicator (160), and then press the [ENTER] key on your terminal or PC keyboard. The selected indicator name and its current setting will be displayed. For example, if Parameter 160 (Tx Func 1) is selected, the following will appear on your screen: 160 Tx Func 1 LED High [High,Low Frequency/Function]>_
3.
If you want the TX FUNCTION 1 indicator to light when Channel 1 is transmitting its high frequency, press the [H] and [ENTER] keys on your terminal or PC keyboard. If you want the indicator to light when Channel 1 is transmitting its low frequency, press the [L] and [ENTER] keys on your terminal or PC keyboard. The indicator name will be re-displayed, along with its new setting. For example, if an "L" was entered for Parameter 160, the following will appear on your screen: 160 Tx Func 1 LED
4.
Low
Enter the number for the first RX FUNCTION indicator (161), and then press the [ENTER] key on your terminal or PC keyboard. The selected indicator name and its current setting will be displayed. For example, if Parameter 161 (Rx Func 1) is selected, the following will appear on your screen: 161 Rx Func 1 LED High [High,Low Frequency/Function]>_
RFL 9745 September 20, 2007
6 - 33
RFL Electronics Inc. (973) 334-3100
Page 223
5.
If you want the RX FUNCTION 1 indicator to light when Channel 1 is receiving its high frequency, press the [H] and [ENTER] keys on your terminal or PC keyboard. If you want the indicator to light when Channel 1 is receiving its low frequency, press the [L] and [ENTER] keys on your terminal or PC keyboard. The indicator name will be re-displayed, along with its new setting. For example, if an "L" was entered for Parameter 161, the following will appear on your screen: 161 Rx Func 1 LED
Low
6.
Repeat steps 2 through 5 for the other TX FUNCTION indicators.
7.
Once all the FUNCTION indicators have been set, enter the "SV" command to save your changes: 9745-L>SV
6.10.4.2 SEALING-IN FRONT PANEL FUNCTION INDICATORS The Seal-in function is a diagnostic tool used to “lock on” any Tx or Rx LED that might filcker or flash on momentarily. The Seal-in function has a default of No (or not Sealed-in). To cause the Tx and Rx LEDs to Seal-in (or lock on), the Yes selection must be made, by typing a Y for Yes, and then pressing [ENTER]. After the Yes selection is made, enter the “SV” command to save your change. The Sealed-in LEDs can only be cleared from the front panel by using the Reset button as described in paragraph 7.5.4. For example, if a”Y” was entered for parameter 168, the following will appear on your screen: 168 Seal-in Func LED
RFL 9745 September 20, 2007
Yes
6 - 34
RFL Electronics Inc. (973) 334-3100
Page 224
6.10.5 SETTING TIMER PARAMETERS The RFL 9745 has several software timers that help control its logic decisions. These timers are defined and named in the logic tables. To set these timers, use the "D" command. 9745-L>D [ENTER] When you invoke the "D" command, a Timer Parameter menu similar to the one shown in Figure 6-16 will appear.
Timer Parameters # Timer Attack Decay Name --------------------------------------------------------------001 Prim Timer 1 15.0 0.0 Dual Boost Timer, Channel 3 002 Prim Timer 2 15.0 0.0 Dual Boost Timer, Channel 4 003 Prim Timer 3 15.0 0.0 Single Boost Timer, Channel 2 004 Prim Timer 4 25.0 25.0 Dual Flash Timer, Channel 3 005 Prim Timer 5 25.0 25.0 Dual Flash Timer, Channel 4 006 Prim Timer 6 25.0 25.0 Single Flash Timer, Channel 2 007 Prim Timer 7 0.0 0.0 Command Extend, Function Ch 3 008 Prim Timer 8 0.0 0.0 Command Extend, Function Ch 4 009 Prim Timer 9 0.0 0.0 Command Extend, Function Ch 2 010 Prim Timer 10 20.0 0.0 Dual Guard Timer 011 Prim Timer 11 100.0 12.0 Dual Block Timer 012 Prim Timer 12 20.0 0.0 Single Guard Timer 013 Prim Timer 13 100.0 12.0 Single Block Timer 014 Prim Timer 14 100.0 10.0 Dual Guard Before Trip/TAG 015 Prim Timer 15 0.0 20.0 Dual Trip Hold Timer 016 Prim Timer 16 100.0 40.0 Single Guard Before Trip/TAG 017 Prim Timer 17 0.0 20.0 Single Trip Hold Timer 018 Prim Timer 18 3.0 0.0 Dual Pre-Trip Timer 1 019 Prim Timer 19 3.0 0.0 Single Pre-Trip Timer 1 020 Prim Timer 20 1.5 5.0 Dual Pre-Trip Timer 2/Trip Hyst 021 Prim Timer 21 1.5 5.0 Single Pre-Trip Timer 2/Trip Hyst 041 Alarm Timer 1 100.0 100.0 Dual Comms Alarm Timer 042 Alarm Timer 2 100.0 100.0 Hardware Warning Timer 043 Alarm Timer 3 100.0 100.0 Hardware Fail Timer 044 Alarm Timer 4 100.0 100.0 Output Alarm Timer 045 Alarm Timer 5 100.0 100.0 Pre-Outage Active Timer 9745-L> Figure 6-16. Typical Timer Parameter menu for the Audio or Digital System
RFL 9745 September 20, 2007
6 - 35
RFL Electronics Inc. (973) 334-3100
Page 225
To set a timer, enter its line number from the Timer Parameter Menu, and then press the [ENTER] key: 1 [ENTER] The following prompt will appear on your screen: 001 Prim Timer 1 15.0 0.0 Guard Before Trip/TAG Tone 2 [attack,decay (0-30000 msec in 0.5 inc)]>_ Enter the desired attack and decay values, separated by a comma. The prompt will be re-displayed, with the new settings shown. NOTE The new timer values you enter will not be placed in effect unless the "SV" command is used to save all new logic programming settings. Refer to paragraph 6.10.15 for more information on the "SV" command.
RFL 9745 September 20, 2007
6 - 36
RFL Electronics Inc. (973) 334-3100
Page 226
6.10.6 DOWNLOADING EMBEDDED LOGIC Logic tables can be passed between a PC running PC APRIL LITE and a 9745. Tables generated via PC APRIL LITE or tables supplied by RFL on the PC APRIL CD can be downloaded to the 9745. See section 9 for information on this process.
RFL 9745 September 20, 2007
6 - 37
RFL Electronics Inc. (973) 334-3100
Page 227
6.10.7 RESTORING DEFAULT LOGIC If you want to return the RFL 9745's logic tables to RFL default logic, use the "F" command: 9745-L>F [ENTER] When you invoke the "F" command, the following prompt will appear on your screen for an Audio System: 089 Logic Tables Primitive: Downloaded, [9745,6750,Alarm]>_
Alarm: Downloaded
The following two default Primitive Logic Tables are available for an audio system: 9745 Audio - This default provides one single channel function and one dual channel function. (See Figure 2-26) 6750 Audio - This default gives the same functionality as the 6750. (See Figure 2-27) The following default Primitive Logic Table is available for a digital system: 9745 Digital - This default provides four digital functions. (See Figure 2-29) The following default Alarm Logic Table is available for an audio system: 9745 - Audio alarms (See Figure 2-28) The following default Alarm Logic Table is available for a digital system: 9745 - Digital alarms (See Figure 2-30) To reset the primitive to the desired default, enter the appropriate default name: 9745, 6750, or Alarm, and then press [Enter]. NOTE The Logic Tables will not return to their default values unless you use the "SV" command to save all new logic programming settings. Refer to paragraph 6.10.15 for more information on the "SV" command.
RFL 9745 September 20, 2007
6 - 38
RFL Electronics Inc. (973) 334-3100
Page 228
6.10.8 THE PRIMITIVE LOGIC TABLE The Primitive Logic Table controls all logic decisions made by the RFL 9745. Normally, It is set at the factory according to the default logic diagram supplied with the equipment. A copy of this diagram can be found in Section 2 of this manual, or in the "as supplied" drawings furnished with the equipment. The user has the option to generate his own primitive logic diagram and primitive logic table to satisfy a particular requirement. To output (view) the Primitive Logic Table, use the "G" command. 9745-L>G [ENTER] When you invoke the "G" command, a Primitive Logic Table will appear, similar to the portion shown in Figure 6-17. You will be able to view the table, but you won't be able to make any changes. If you want to change the Primitive Logic Table, use the "S" command described in paragraph 6.10.13.
# Gate: 001 OR 002 AND 003 NOT 004 NOT 005 OR ... ... ... ... ... ... ... ... 097 OR 098 NOT 099 OR 100 OR 101 NOT 9745-L>
Input 1: AM2H_CH3 AM2L_CH3 AM1L_CH3 AM2L_CH3 FM_CH3 ... ... ... NODE96 NODE97 INPUT2A NODE99 NODE100
Input 2: AM1H_CH3 AM1L_CH3 #0 #0 S/N_CH3 ... ... ... INPUT1A #0 NODE54 NODE75 #0
Output:
...
Figure 6-17. Portion of a typical Primitive Logic Table for the Audio System
RFL 9745 September 20, 2007
6 - 39
RFL Electronics Inc. (973) 334-3100
Page 229
6.10.9 THE ALARM LOGIC TABLE The Alarm Logic Table controls all the logic decisions the RFL 9745 makes to produce its alarm outputs. Normally, it is set at the factory according to the default alarm logic diagram supplied with the equipment. A copy of this diagram appears in Section 2 of this manual, or in the "as supplied" drawings furnished with the equipment. The user has the option to generate his own alarm logic diagram and alarm logic table to satisfy a particular requirement. To output (view) the Alarm Logic Table, use the "M" command. 9745-L>M [ENTER] When you invoke the "M" command, an Alarm Logic Table similar to the portion shown in Figure 618 will appear. You will be able to view the table, but not make any changes. If you want to change the Alarm Logic Table, use the "T" command as described in paragraph 6.10.14.
# Gate: 001 OR 002 AND 003 OR 004 OR 005 AND ... ... ... ... ... ... 044 TIMER 045 AND 046 OR 047 TIMER 048 AND 9745-L>
Input 1: AM1H_CH3 AM1L_CH3 NODE1 AM1H_CH4 AM1L_CH4 ... ... ... NODE43 NODE44 ADD_FAIL NODE46 NODE47
Input 2: AM2H_CH3 AM2L_CH3 NODE2 AM2H_CH4 AM2L_CH4 ... ... ... TIMER5 #1 CHKBK TIMER6 #1
Output:
.. ... ... A_OUTPUT3 A_RELAY3A A_OUTPUT4
Figure 6-18. Portion of a typical Primitive Logic Table for the Audio System