Page 200

#

NAME VALUE # NAME VALUE -----------------------------------------------------------------------140 Tx Chan Delay 127.5 ms 141 Next Auto Test N/A 142 Rx Chan Delay 127.5 ms 143 Last Reset Date 16:38:59 03/03/98 144 Cum Outage Time 02:08:48.579 145 Current Time 00:32:56 03/15/98 146 Data Rate N/A 147 Bit Error Rate Max Error 148 Word Errors 501757 149 Clock Errors 6 150 Frame Errors 1 151 Minor Data Error 1 152 Major Data Error 1

154 155 156 157 158 159 160 161

Input 1A Input 1B Input 2A Input 2B Input 3A Input 3B Input 4A Input 4B

Function 175 Rx Function 176 Tx Function 9745>

(I/A) I I I I I I I I

LOG 1 0 4 0 0 1 0 0

162 163 164 165 166 167 168 169

Output 1A Output 1B Output 2A Output 2B Output 3A Output 3B Output 4A Output 4B

#1 SQ I

#2 SQ I

#3 SQ I

#4 SQ I

#5 SQ I

(I/A) A A A A I I I I #6 SQ I

LOG 0 2 0 2 0 2 0 2

#7 SQ I

Figure 6-5. Typical values display for the Digital System

The values displays shown in Figures 6-4 and 6-5 show the code number for each measured parameter, a brief description of its meaning and its measured value. “A” indicates that the parameter is “active” or connected. “I” indicates that the parameter is “inactive” or not connected. “SQ” indicates that the parameter is “squelched”. Full descriptions for each of these measured values are as follows: 140 - Tx Chan Delay

Measured transmit channel delay, in milliseconds.

141 - Next Auto Test

Amount of time until next scheduled test, in hours and minutes.

142 - Rx Chan Delay

Measured receive channel delay, in milliseconds.

143 - Last Reset Date

Time and date of last system reset.

144 - Cum Outage Time

Total amount of time that the system has been interrupted (cumulative outage) in hours, minutes, and seconds since the last reset. This timer is active whenever the “OUTAGE” alarm logic output is active.

145 – Current Time

Current time in 24-hour format, followed by the current date.

146 - Data Rate

The number of data bits received per second.

RFL 9745 September 20, 2007

6 - 11

RFL Electronics Inc. (973) 334-3100

Page 201

147 - Bit Error Rate

A ratio of the number of bit errors received over the total number of bits received, in a one second period. N/A if the data rate is zero. If there are zero bit errors, the number will be 0E-6.

148 - Word Errors

The number of word errors received since the last reset.

149 - Clock Errors

The number of clock errors received since the last reset.

150 - Frame Errors

The number of frame errors received since the last reset.

151 - Minor Data Errors

A ratio of the number of data errors received out of a given number of messages received, as defined by the user. See parameter 013 on page 5-7, and page 6-21 for more information.

152 - Major Data Errors

A ratio of the number of data errors received out of a given number of messages received, as defined by the user. See parameter 012 on page 5-7, and page 6-20 for more information.

Lines 154 through 169 on the values display lists the RFL 9745's eight programmable inputs and outputs. The status of each input or output is listed (Active or Inactive), followed by how many times each input or output has been activated since the last reset (the LOG value). See Section 5 for information on how to label each of these inputs and outputs. 154 to 161 - Inputs

Indicates status and count of how many times that input has gone active.

162 to 169 - Outputs

Indicates status and count of how many times that output has gone active.

Lines 170 through 174 on the RFL 9745 Audio System values display, lists the status of each of the four audio communications channels: 170 - Rcvd Signal Lvl

The signal level being received on each channel (in dBm). If the signal is below the dynamic range, “LOS” will be displayed to indicate a loss of signal.

171 - Tx Function

For an Audio system, indicates whether each channel's transmit function is active or inactive. Tx Function active means the transmitter is sending its high frequency.

172 - Tx Squelch

Indicates whether the squelch feature on each channel's transmitter is active or inactive.

173 - Rx High Freq

Indicates whether each channel's high frequency is being received.

174 - Rx Low Freq

Indicates whether each channel's low frequency is being received.

RFL 9745 September 20, 2007

6 - 12

RFL Electronics Inc. (973) 334-3100

Page 202

175 - Rx Function

For a Digital system, indicates whether the received bits in the data word are active or inactive. This function can be programmed by the user to be squelched.

176 - Tx Function

For a Digital system, indicates whether the received bits in the data word are active or inactive. This function can be programmed by the user to be squelched.

6.7 THE PROGRAMMING MODE You can use APRIL and your terminal to program the RFL 9745. All programming functions that are normally done using the keypad on the RFL 9745's display module can be done using a terminal. To use your PC or terminal to program the RFL 9745, use the "P" command. 9745>P [ENTER] The "P" command tells the RFL 9745 to send a list of all programming commands to your terminal. Since using the programming commands will affect how the RFL 9745 operates, the "P" command is password-protected. If the proper password is entered, a programming menu similar to the one shown in Figure 6-6 will appear.

H - Display programming help Q - Leave programming menu SV - Save new settings C - Change password (superuser authorization required) D - Display present settings and parameter numbers ## - Edit this specific number parameter 9745-P> _ Figure 6-6. Typical programming menu for the Audio or Digital System

RFL 9745 September 20, 2007

6 - 13

RFL Electronics Inc. (973) 334-3100

Page 203

You are now in the programming mode, as indicated by the "9745-P>" prompt on your screen. You may now use the programming commands to re-program the RFL 9745. For more information on each programming command, refer to the paragraph numbers listed below. Command

Meaning

Paragraph

H

Display programming help

.

.

.

.

6.7.1

Q

Leave programming menu

.

.

.

.

6.7.2

SV

Save new settings

.

.

.

.

.

6.7.3

C

Change password

.

.

.

.

.

6.4.2

D

Display current settings and parameter numbers

.

6.7.4

6.7.1 DISPLAYING PROGRAMMING HELP Any time you need to see a list of all the programming commands, use the "H" command. 9745-P>H [ENTER] When you invoke the "H" command, the programming menu shown in Figure 6-6 will re-appear on your screen.

RFL 9745 September 20, 2007

6 - 14

RFL Electronics Inc. (973) 334-3100

Page 204

6.7.2 LEAVING THE PROGRAMMING MODE NOTE Before leaving the Programming Mode, if you don’t use the “SV” command your changes will be lost. Whenever you are finished programming the RFL 9745, use the "Q" command: 9745-P>Q [ENTER] The "Q" command tells the RFL 9745 to leave the programming mode and return to the normal "9745>" prompt. If you changed any setting while in the programming mode, be sure to use the "SV" command described above to save the changes before invoking the "Q" command; otherwise, your changes will be lost.

6.7.3 SAVING NEW PROGRAMMING SETTINGS The "SV" command saves any new settings you made while in the programming mode: 9745-P>SV [ENTER] The "SV" command tells the RFL 9745 to store all the changes in its non-volatile memory. Once the changes are stored, the "9745-P>" prompt will re-appear. Before you enter the "SV" command, the RFL 9745 operates according to the old parameter settings. Once the "SV" command is entered, the new settings will be in effect. The 9745 will go out of service during command execution. The new parameter settings can be verified by re-issuing the "D" command to display the parameter settings list. (For more information on the "D" command, go to paragraph 6.7.4.)

RFL 9745 September 20, 2007

6 - 15

RFL Electronics Inc. (973) 334-3100

Page 205

6.7.4 DISPLAYING AND EDITING PARAMETER SETTINGS To view a list of all current parameter settings, use the "D" command. 9745-P>D [ENTER] When you invoke the "D" command, the RFL 9745 sends a list of all current parameter settings to your terminal. A typical parameter settings display for the Audio system with no channels defined is shown in Figure 6-7. Refer to paragraph 5.5 for recommended parameter settings. # 999 001 002 003 005 006 008 010

PARAMETER System Label Channel 1 Tone 1 Tx Freq Transmit Level Tone 1 Rx Freq Rx Bandwidth Rx Alarm FM Noise

SETTING

016 017 018 020 021 023 025

Channel 2 Tone 2 Tx Freq Transmit Level Tone 2 Rx Freq Rx Bandwidth Rx Alarm FM Noise

Single 0 Hz 0 Hz 0.00 dBm 0 Hz 0 Hz 0 Hz 0 dBm 0%

031 032 033 035 036 038 040 046 047 048 050 051 053 055

Channel 3 Tone 3 Tx Freq Transmit Level Tone 3 Rx Freq Rx Bandwidth Rx Alarm FM Noise Channel 4 Tone 4 Tx Freq Transmit Level Tone 4 Rx Freq Rx Bandwidth Rx Alarm FM Noise

Single 0 Hz 0 Hz 0.00 dBm 0 Hz 0 Hz 0 Hz 0 dBm 0% Single 0 Hz 0 Hz 0.00 dBm 0 Hz 0 Hz 0 Hz 0 dBm 0%

060 Opt Status Board 062 Chan delay alarm 064 Date 066 Hour Adjust 068 Remote Address 9745-P>

Single 0 Hz 0 Hz 0.00 dBm 0 Hz 0 Hz 0 Hz 0 dBm 0%

No 0 ms 11/04 0 0

#

PARAMETER

SETTING

004

Boost Level

007 009

Rx Level 0 dBm AM Noise(SNR) 0 dB

019

Boost Level

022 024

Rx Level 0 dBm AM Noise(SNR) 0 dB

034

Boost Level

037 039

Rx Level 0 dBm AM Noise(SNR) 0 dB

049

Boost Level

052 054

Rx Level 0 dBm AM Noise(SNR) 0 dB

061 063 065 067 069

EE Pot J10 Year Time Local Address Reset Log

0 dB

0 dB

0 dB

0 dB

A 0000 13:46:26 0

Figure 6-7. Typical parameter settings display for the Audio System with no parameters set

RFL 9745 September 20, 2007

6 - 16

RFL Electronics Inc. (973) 334-3100

Page 206

A typical parameter settings display for the Audio System with channel 1 set for modem operation is shown in Figure 6-8. A typical parameter settings display for the Digital System is shown in Figure 6-9.

# PARAMETER 999 System Label 001 Channel 1 002 Tone 1 Tx Freq 003 Transmit Level 005 Tone 1 Rx Freq 006 Rx Bandwidth 008 Rx Alarm 010 FM Noise

SETTING CPU BOARD 3 Modem 700 Hz 1000 Hz -5.00 dBm 700 Hz 1000 Hz 450 Hz -35 dBm 75 %

016 Channel 2 not defined

031 Channel 3 not defined

046 Channel 4 not defined

060 Opt Status Board 062 Chan delay alarm 064 Date 066 Hour Adjust 068 Remote Address 9745-P>

Yes 8 ms 03/15 1 123

# PARAMETER

SETTING

004 Boost Level

0 dB

007 Rx Level 009 AM Noise (SNR)

-5 dBm 8 dB

061 EE Pot J10 063 Year 065 Time 067 Local Address 069 Reset Log

A 1994 09:45:19 456

Figure 6-8. Typical parameter settings dispay for the Audio System with Channel 1 set for modem operation

# PARAMETER 999 System Label 011 Functions 1-7 012 Major Data Error 013 Minor Data Error 014 Alarm BER

SETTING Test Unit #1 Digital 6, 500 400, 200000 1E-04

# PARAMETER

SETTING

060 Opt Status Board 063 Year 065 Time 067 Local Address 069 Reset Log 9745>

No 1994 13:47:06 0

062 Chan delay alarm 064 Date 066 Hour Adjust 068 Remote Address

4 ms 08/09 0 888

Figure 6-9. Typical parameter settings display for the Digital System

RFL 9745 September 20, 2007

6 - 17

RFL Electronics Inc. (973) 334-3100

Page 207

To re-program any of the values shown on the parameter settings displays, type in the number in the "#" column, and then press [ENTER]. The parameter will be displayed, with information about its setting below it. Type in the new setting, and then press [ENTER]. The following are several examples of editing Audio or Digital system parameter settings: Example 1: Editing the System Label Parameter Setting. (Audio or Digital systems) 1.

Enter the number for the System Label parameter (999) on your terminal or PC keyboard, and then press the [ENTER] key. The System Label parameter will be displayed, with information about its setting below it. 999 System Label [any string]> _

SUBSTATION 2

2.

Type in what you want the new system label to be. The system label can be any combination of letters or numbers up to 16 characters long.

3.

When you are finished entering the new system label, press the [ENTER] key. The System Label parameter will be re-displayed, set to the new value.

4.

Enter the "Q" command to return to the main menu: 9745-P>Q

Example 2: Editing the channel 1 mode parameter setting. (Audio system only) 1.

To configure Channel 1 for FSK modem operation, type in the following: 9745-P>1 [ENTER]

2.

The Channel 1 parameter will be displayed, with information about its setting below it. 001 Channel 1 not defined [Single, Modem, 6750 Modem, Pass, None]> _

3.

There are five settings for this parameter, as listed in the brackets beneath it. To set Channel 1 for modem operation, type in the first letter of "modem" ("M"), and then press [ENTER]. The Channel 1 parameter will be re-displayed, set to the new value. 001 Channel 1

RFL 9745 September 20, 2007

Modem

6 - 18

RFL Electronics Inc. (973) 334-3100

Page 208

Example 3: Editing the system time and date parameter settings. (Audio or Digital system) If your RFL 9745 is connected to an IRIG-B generator, its system clock is being automatically synchronized to the IRIG-B time clock, and no manual setting is required. If you are not using an IRIG-B generator, use the following procedure to set the RFL 9745's system clock:

1.

Enter the number for the Year parameter (63) on your terminal or PC keyboard, and then press the [ENTER] key. The Year parameter will be displayed, with information about its setting below it. 063 Year [any year]> _

2.

Type in the current year, and then press the [ENTER] key. The Year parameter will be re-displayed, set to the new value.

3.

Enter the number for the Date parameter (64) on your terminal or PC keyboard, and then press the [ENTER] key. The Date parameter will be displayed, with information about its setting below it. 064 Date [mm/dd]> _

4.

Type in the current date, and then press the [ENTER] key. The Date parameter will be re-displayed, set to the new value.

5.

Enter the number for the Time parameter (65) on your terminal or PC keyboard, and then press the [ENTER] key. The Time parameter will be displayed, with information about its setting below it. 065 Time [hh:mm:ss]> _

6.

Type in the current time (in 24-hour format), and then press the [ENTER] key. The Time parameter will be re-displayed, set to the new value.

7.

Enter the "SV" command to save your new system time: 9745-P>SV NOTE If you are using IRIG-B and channel 1 is set as a modem, the remote unit will be synchronized through the modem to the same IRIG-B time and date unless it has an IRIGB input as well.

RFL 9745 September 20, 2007

6 - 19

RFL Electronics Inc. (973) 334-3100

Page 209

Example 4: Editing the Major Data Error setting (Digital System only) The Major Data Errors (Y, Z), are bits used in the primitive logic to inhibit tripping. The Major Data Error bit is set when Y bits are in error out of Z bits (where Z>15Y). Parameter # 012 in Figure 6-9 is presently set for 6 bits in error out of 500 (6, 500). This means that if during an interval of 500 bits if more than 6 bits have been detected to be in error, the Major Data Error bit will be set. The next interval of 500 bits will begin at the point at which the Major Data Error bit was set. It will then take another interval of 500 bits with less than 6 bits in error to reset the Major Data Error bit. Since the errors are detected during the interval, the Major Data Errors are fast acting. To change the setting of the Major Data Error, do the following: 1.

Enter the number for the Major Data Error parameter (12) on your terminal or PC keyboard, and then press the [ENTER] key. The Major Data Error parameter will be displayed, with information about its setting below it. 012 Major Data Error 6, 500 [0-10000 errors out of], [1-1000000 total]>_

2.

Type in Y, Z where Y can have any value from 0 to 10000 and where Z can have any value from 1 to 1000000. For example, type in 8, 800 and then press the [ENTER] key. The Major Data Error parameter will be re-displayed, set to the new value as follows: 012 Major Data Error 8, 800

3.

Enter the “SV” command to save the new Major Data Error setting. 9745-P>SV

RFL 9745 September 20, 2007

6 - 20

RFL Electronics Inc. (973) 334-3100